3. For reorder purposes the CRFF-E, CRFF-E-ARS and CRFF-E-ARSM model number, configuration code and serial number should be recorded. This information is located on the product and serial number labels, located adjacent to the electrical box. If you cannot locate the FO# please contact Krueger for this information. Read and Save These Instructions To reduce the riskkof fire, electrical shock, or injury to persons, observe the following 1.
Page: 4 of 26 Installation The CRFF-E Series Critical Room Fan Filter Units are completely assembled at the factory with the exception of the optional ¼” (0.64 cm)-20 eyebolts, which can be used when hanging the unit from an overhead structure.
ON/OFF Switch - Speed/Airflow Adjustment All CRFF-E series units are equipped with a two-position rocker switch (ON/OFF), which is located on the side of the electrical box, on top of the unit. Unless otherwise specified, units are furnished with a Universal Control Card to enable adjustment of airflow or set to preferred communication mode.
ANALOG INPUT “COM” GREEN LED FOR SYSTEM/RPM STATUS ANALOG INPUT “SIGNAL” RPM TEST PROBE JACK “SIGNAL” RPM TEST PROBE JACK “COM” MANUAL SPEED POT Krueger | 1401 N Plano Rd | Richardson, TX 75081 | 972.680.9136 | kruegerinfo@krueger-hvac.com | www.krueger-hvac.com...
Page 7
Note: Network mode can be configured using either DIP switch setting shown above. DIP switch pictorials are for reference and may be labeled differently by the manufacturer. Krueger | 1401 N Plano Rd | Richardson, TX 75081 | 972.680.9136 | kruegerinfo@krueger-hvac.com | www.krueger-hvac.com...
Page 8
Installation, Operation, & Maintenance for CRFF-E Series Page: 8 of 26 Control Modes (continued) Example of binary S2 switch settings Krueger | 1401 N Plano Rd | Richardson, TX 75081 | 972.680.9136 | kruegerinfo@krueger-hvac.com | www.krueger-hvac.com...
Page 9
RED NETWORK LED GREEN STATUS LED RJ45 Network Cable Connections RS-485 Bus Power Bus Power 0V (GND) 0V (GND) Pass Through Pass Through Krueger | 1401 N Plano Rd | Richardson, TX 75081 | 972.680.9136 | kruegerinfo@krueger-hvac.com | www.krueger-hvac.com...
Page 10
Note: Register 24 may be read in network mode to determine the value of 0-10VDC signal that may be connected. For example, a pressure transducer may be conected to indicate unit static pressure Krueger | 1401 N Plano Rd | Richardson, TX 75081 | 972.680.9136 | kruegerinfo@krueger-hvac.com | www.krueger-hvac.com...
3. Check air velocity and if low, conduct the “Low Air Velocity” procedure outlined above. 4. Conduct smoke and photometer test on HEPA filte . Seal or replace HEPA filter as necessar . Krueger | 1401 N Plano Rd | Richardson, TX 75081 | 972.680.9136 | kruegerinfo@krueger-hvac.com | www.krueger-hvac.com...
• A flow index of 04 flashes an extra long, then 4 shor • A flow index of 100 flashes 10 longs, then an extra lon Krueger | 1401 N Plano Rd | Richardson, TX 75081 | 972.680.9136 | kruegerinfo@krueger-hvac.com | www.krueger-hvac.com...
5. Reassemble by reversing the above steps. Note: To keep the filter in top operating condition, washing the foam prefilter is recommended every three to six months. Krueger | 1401 N Plano Rd | Richardson, TX 75081 | 972.680.9136 | kruegerinfo@krueger-hvac.com | www.krueger-hvac.com...
This will give a 0.11” overlap between the venturi ring and the blower. PREFILTER MOTOR FIGURE 4: MOTOR REPLACEMENT VENTURI RING BLOWER WHEEL ON/OFF SWITCH Power Entrance Krueger | 1401 N Plano Rd | Richardson, TX 75081 | 972.680.9136 | kruegerinfo@krueger-hvac.com | www.krueger-hvac.com...
THE INNER SCREW PREFILTER WALL AND WASHER GROMMET PLENUM MOTOR / BLOWER MOTOR ASSEMBLY WELLNUT BAFFLE ASSEMBLY VENTURI RING GEL SEAL FILTER SCREEN BLOWER WHEEL Krueger | 1401 N Plano Rd | Richardson, TX 75081 | 972.680.9136 | kruegerinfo@krueger-hvac.com | www.krueger-hvac.com...
The rest of the fit and function will be a direct replacement. Follow the procedure in the IOM for motor swap for your particular FFU. Old Cable Style Krueger | 1401 N Plano Rd | Richardson, TX 75081 | 972.680.9136 | kruegerinfo@krueger-hvac.com | www.krueger-hvac.com...
Page 19
ECM motors are self-testing and sized for the motor being used inside the unit they can’t compete with the airflows from a duct blower motor. Krueger | 1401 N Plano Rd | Richardson, TX 75081 | 972.680.9136 | kruegerinfo@krueger-hvac.com | www.krueger-hvac.com...
Page: 20 of 26 Wiring Diagrams 4 Pin MTA Motor Connector Remote Run Indicator LED 4 pin Control Cable 5 pin Power Cable Universal Card Wiring Diagram Krueger | 1401 N Plano Rd | Richardson, TX 75081 | 972.680.9136 | kruegerinfo@krueger-hvac.com | www.krueger-hvac.com...
Page 21
Note: Register 24 may be read in network mode to determine the value of 0-10VDC signal from the pressure transducer connected to indicate unit interal static pressure. Universal Card Wiring Diagram w/ Continous Filter Monitoring Krueger | 1401 N Plano Rd | Richardson, TX 75081 | 972.680.9136 | kruegerinfo@krueger-hvac.com | www.krueger-hvac.com...
Page 22
Installation, Operation, & Maintenance for CRFF-E Series Page: 22 of 26 Wiring Diagrams (continued) Infrared Speed Control Remote Mounted Visual Control Unit Krueger | 1401 N Plano Rd | Richardson, TX 75081 | 972.680.9136 | kruegerinfo@krueger-hvac.com | www.krueger-hvac.com...