La Marche AUPS-2K-A1-ABD1-24V150A Installation And Operation Manual

A series uninterruptible power supply system; aups series
Table of Contents

Advertisement

Quick Links

La Marche Manufacturing Company | www.lamarchemfg.com
AUPS
A-Series UPS / Uninterruptible Power
Supply System
106 Bradrock Dr. Des Plaines 60018-1967
Tel: 847 299 1188
Fax: 847 299 3061
Installation and Operation Manual
CPN 137679
Instruction Drawing Number: P25-LAUPS-1
Revision A00
Rev. Date: 01/18
i
ECN: 21597

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the AUPS-2K-A1-ABD1-24V150A and is the answer not in the manual?

Questions and answers

Summary of Contents for La Marche AUPS-2K-A1-ABD1-24V150A

  • Page 1 La Marche Manufacturing Company | www.lamarchemfg.com AUPS A-Series UPS / Uninterruptible Power Supply System Installation and Operation Manual 106 Bradrock Dr. Des Plaines 60018-1967 Instruction Drawing Number: P25-LAUPS-1 Tel: 847 299 1188 Fax: 847 299 3061 CPN 137679 Revision A00 Rev.
  • Page 2: Electrical Safety

    Important Safety Instructions Before using this equipment, read all manuals and other documents related to this AUPS system and other equipment connected to this system. Always have a copy of an inverter’s manual on file nearby, in a safe place; if a replacement copy of a manual is needed, it can be found at www.lamarchemfg.com.
  • Page 3: Unit Location

    If any damage is observed, take pictures and contact the carrier immediately to file a damage claim. Contact La Marche for a Return Material Authorization number to have the system sent back for evaluation and repair.
  • Page 4: Table Of Contents

    Table of Contents Important Safety Instructions ........................i Electrical Safety ............................i Mechanical Safety ............................i Battery Safety ............................i Unit Location ............................. ii Check for Damages ........................... ii Returns for Service ............................ ii Inspection Checklist ........................... ii Handling ..............................ii Table of Contents ............................
  • Page 5 3.1.2 Starting/Stopping the AUPS .......................14 Factory Settings ...........................18 Understanding the Alarms ......................18 Digital Control Board – Rectifier Section..................18 Selecting the Charging Mode – Rectifier Section ................19 3.5.1 Equalize Timer Modes .......................19 Adjusting Parameters – Rectifier Section ..................19 3.6.1 Settings Menu ..........................20 3.6.1.1 Float/Eq Voltage .........................20 3.6.1.2...
  • Page 6: Table Of Figures

    Table of Figures Figure 1 - AUPS Case Footprint ........................3 Figure 2 - Input Terminals Connection (Schematic – 240VAC input shown) ............. 4 Figure 3 - AC Connections (AC Load, AC Bypass & Rectifier AC) ..............6 Figure 4 - DC Input/Battery Connection ......................7 Figure 5 - User Connections to Rectifier Alarm Contacts on S2A-198 Board .............
  • Page 7: Model Scope/General Description

    (if any), refer to the cover page of the manual package. If the manual package that is included with the unit is no longer available, contact La Marche and provide the model or serial number of the unit to...
  • Page 8: Equipment Handling

    Equipment Handling Storing the AUPS If the AUPS is to be stored for more than a few days after delivery, it should be stored within its shipping container. The location chosen for storage should be within an ambient temperature of -40 to 185° F (-40 to 85°C) with a non-condensing relative humidity of 0 to 95%.
  • Page 9: Installation

    Installation Mounting the AUPS When mounting the AUPS in ANY configuration, consider the size and weight of the unit. The floor must be able to support the weight of the unit, as well as an additional safety factor. Verify the method of mounting and the weight of the AUPS using Tables 1 and 2.
  • Page 10: Changing Transformer Taps - Rectifier Ac Input

    Changing Transformer Taps – Rectifier AC Input NOTE: This procedure refers only to AUPS systems that accept three input voltages of 120, 240, and 208 VAC at the Rectifier AC Input [Voltage code: ABD]. Before wiring AC power to the AUPS, check the wiring of the power transformer PT, to be sure it is connected for the correct AC input voltage.
  • Page 11: Making The Ac Connections

    Table 4 – AC/DC & Ground Wire Size Minimum Requirements (All wires specified in the table are rated at 90 °C or 194 °F) NOTE: These are recommended sizes per La Marche Standards. The National Electrical Code (NEC) and Local Wiring Codes must be followed.
  • Page 12: Rectifier Ac Input Connection Procedure

    2.3.1 Rectifier AC Input Connection Procedure First, connect an adequate earth ground lead (use Table 4 for sizing) to the terminal marked with a “GROUND” symbol inside the system. Run the Rectifier AC input wiring to terminals marked L1 and L2 or L3 of the terminal block TB1 inside the system (for systems with transformer taps, use Table 3 for input connections).
  • Page 13: Making The Dc Input/Battery Connections

    Making the DC Input/Battery Connections Before making any of DC input connections, make sure you have read and fully understand the DC Connection Procedure below. Ensure that the Battery breaker is set to the OFF position. Select proper size for the DC wiring from Table 4.
  • Page 14: Alarm Connections

    Alarm Connections Eight alarm relays (and 10 alarm LEDs) are included on the rectifier section as a standard feature of the AUPS. The included alarms are Low DC Current, Low DC Voltage, High DC Voltage, High Voltage Shutdown, AC Failure, Negative Ground Detection, Positive Ground Detection, and Summary. Five status indicator relays (and 11 status LEDs) are included on the inverter section as a standard feature of the AUPS.
  • Page 15: Figure 8 - S2A-240 Display Board

    LEDs are provided on the inverter section for the following status indicators: Phase Lock, Auto Retransfer, Manual Retransfer, Load on Preferred Source, Load on Alternate Source, Utility Available, Inverter Available, Load Voltage, Load Current, Load VA, Utility Voltage, Utility Frequency, Inverter Voltage, and Inverter Frequency.
  • Page 16: Alarm Connection Procedure

    2.5.1 Alarm Connection Procedure Before making any connections to the AUPS, ensure that the AC power is off at the main breaker box and that all of the system’s breakers are off. Verify that no voltage is present by using a voltmeter at all input and output terminals.
  • Page 17: Understanding The Alarms

    Installing External Temperature Compensation (Option 11W/11Y) The natural voltage of a battery changes as a function of temperature change. As the battery temperature rises, the effective voltage of the battery decreases. Without Temperature Compensation, the rectifier will always produce a set constant output voltage. As the battery temperature increases, this constant voltage will then induce a higher output current from the rectifier.
  • Page 18: Enabling/Disabling Ground Detection

    1.5mA is reached (or exceeded). NOTE: La Marche Mfg. Co. is primarily a manufacturer of battery chargers and not ground detection systems. If a more precise system is needed, many ground detection systems are compatible with La Marche products.
  • Page 19: Remote Equalize

    Remote Equalize A terminal is provided on the AUPS (RE) for a Remote Equalize function. The rectifier may be remotely forced into Equalize by connecting the “RE” terminal (on TS-5 terminal) to negative. CAUTION: Damage to the unit will result if the Remote Equalize Terminals are shorted to any other AC or DC voltage source or ground on positive grounded chargers.
  • Page 20: Operation

    Operation Starting the AUPS All equipment is shipped from the factory fully checked and adjusted based on the customer order. Do not make any adjustments unless the equipment has been powered-up and the settings have been determined to be incorrect. 3.1.1 Checking the Installation Before attempting to start up the AUPS, check and verify that all connections are correct.
  • Page 21: Factory Settings

    Stopping the AUPS Procedure When shutting down the AUPS, switch off the ON/OFF switch (inverter section) first, and then switch of the AC breakers, followed by the DC breakers. Factory Settings All AUPS systems are default set based on 12, 24, or 60 lead acid cells for 24VDC, 48VDC, or 125VDC respectively.
  • Page 22: Understanding The Alarms

    Parameter Default Value Low DC Voltage Shutdown 1.73 V/C for LA, 1.1 V/C for NC High DC Voltage Shutdown 2.65 V/C for LA, 1.65 V/C for NC Current Limit 150% of nominal output current Transfer Time 1 millisecond (not adjustable) Preferred Source Inverter Load Voltage Window Upper Limit...
  • Page 23 NEGATIVE GROUND ALARM will trigger and the red NEGATIVE GROUND FAULT LED will turn on if 1.2mA or greater current is measured between the negative terminal of the battery and earth ground. The alarm will clear once the negative ground condition is no longer present. If the rectifier has Ground Detection disabled, this alarm will not function.
  • Page 24: Digital Control Board - Rectifier Section

    Digital Control Board – Rectifier Section The AUPS is available with an LCD or VFD digital control board for the rectifier section. Figure 13 - Rectifier Front Panel After the AUPS has completed the startup sequence, AC ON and FL green LED indicators on the rectifier front panel will be lit, additional indicators will be lit according to the system’s status as pictured above in Figure 13.
  • Page 25: Selecting The Charging Mode - Rectifier Section

    Selecting the Charging Mode – Rectifier Section The AUPS rectifier has two different settings for DC output voltage, Float Mode and Equalize Mode. Float charging mode is used for all normal battery charging needs. Equalize mode is used when it is necessary to Equalize (or balance) the level of charge across all cells present in the battery.
  • Page 26: Settings Menu

    3.6.1 Settings Menu In the Settings Menu, the user can access and change various parameters used by the rectifier section of the AUPS. To access the Settings Menu, press the MENU button, select “Settings Menu”, and press the ENTER button. Once in the Settings Menu, the user can navigate the menus with the up and down arrows.
  • Page 27: Advanced Settings

    Alarm Thresholds The Alarm Thresholds setting allows the user to determine the current or voltage value at which an alarm triggers. The threshold can be changed for Low Current Alarm, Low Current Alarm Reset, Overload Alarm, Low Voltage Alarm, Low Voltage Alarm Reset, End of Discharge Alarm, High Voltage Alarm, and High Voltage Shutdown Alarm.
  • Page 28 Equalize Timer Hours The Equalize timer hours setting changes the amount of time that the rectifier remains in the Equalize charging cycle once activated. When an Equalize cycle is started the rectifier will remain in Equalize Mode until the time selected by this setting has passed.
  • Page 29: Test Menu

    3.6.1.4 Return to Defaults The 4 option in the Settings Menu is “Return to Defaults”. This option resets all user-adjustable settings to the factory defaults. It is important to note that the factory defaults are not necessarily the correct settings for the specific DC system.
  • Page 30: Aups Rectifier Customer Configuration Menu

    3.6.3 Rectifier Customer Configuration Menu AUPS Rectifier Customer Configuration Menu...
  • Page 33: Digital Display - Inverter Section

    3.7 Digital Display – Inverter Section Figure 14 - Inverter Front Panel Once the inverter section is powered up, the Load Voltage LED will be ON and the display will show the actual load voltage. In order to view the next parameter, toggle the Cal/Select switch down. Status Indicator LEDs Phase Lock LED is ON when the inverter and the utility sources are operating in phase.
  • Page 34: Adjusting Parameters - Inverter Section

    Adjusting Parameters – Inverter Section All equipment is shipped from the factory fully checked and adjusted based on the customer order. Do not make any adjustments unless the equipment has been powered-up and the settings have been determined to be incorrect.
  • Page 35 Inverter Voltage Window Upper Limit The maximum allowable/acceptable limit on the Inverter Voltage defaults to the Output Voltage setting +10%. Thus, an inverter with an output voltage of 120 Volts will have a default setting of approximately 132 Volts. There are no limits on max and min settings for this. The display units are in Volts-RMS. Due to display resolution, the ability to adjust this setting to an exact voltage may not be possible.
  • Page 36: Service

    Service All work inside the AUPS should be performed by qualified personnel. La Marche is not responsible for any damages caused by an unqualified technician. Before working inside the AUPS, ensure all power is off at the main breaker box and the battery has been removed from the rectifier’s DC output terminals, either by removing the battery cables or...
  • Page 37: Troubleshooting Procedure - Rectifier Section

    4. Result of the check of the AC and DC breakers. NOTE: When ordering replacement parts, drawings, or schematics, provide the model number, serial number, and description of problem, if available. La Marche Phone Number: (847) 299-1188 24-hour Emergency Number: (847) 296-8939...
  • Page 38: Troubleshooting Chart - Rectifier Section

    Batteries are Fully Charged current should increase. Defective Power Diodes/Diode Refer to Section 4.3.3. Modules/Triac Defective S2A-341S Control Board Contact La Marche Service Department for further troubleshooting instructions. Defective Shunt Defective Resonating Capacitor(s) Refer to Section 4.3.4. Defective Batteries Check battery cells.
  • Page 39: Ground And Short Circuit Test

    Refer to Section 4.3.3. Ordering Replacement Parts Contact La Marche to place an order for spare or replacement parts. To order replacement parts; please provide the model and serial number of the AUPS system, the part needed, and the quantity required.
  • Page 40: Troubleshooting And Replacing Power Silicon Diodes/Modules

    4.3.3 Troubleshooting and Replacing Power Silicon Diodes/Modules 1 On the ohmmeter, set the switches on “ohms”, “DC”, and “Rx100” scale and isolate one end of the diode by disconnecting the wires attached to the nipple (or pigtail) end of the diode (only one end of the diode must be disconnected).
  • Page 41: Troubleshooting Procedure - Inverter Section

    La Marche Service Technicians are available to help with troubleshooting or with scheduling unit service. When calling for a service inquiry or for troubleshooting assistance, be sure to have all of the following information on hand: 1.
  • Page 42: Troubleshooting Chart - Inverter Section

    Troubleshooting Chart – Inverter Section Isolate from all power sources prior to performing any interior verifications or part replacements. Symptom Possible Cause Overload Condition Shorted Equipment or Component on AC Output Inverter AC Breaker Trips Defective AC Breaker Shorted SCRs in Static Switch, refer to Section 4.5.1 Capacitor Pre-Charge Circuitry Improperly Used Defective C1, C2, or C4 Capacitor...
  • Page 43: Checking The Scr Module

    Overloaded Prime Source Ordering Replacement Parts Contact La Marche to place an order for spare or replacement parts. To order replacement parts; please provide the model and serial number of the AUPS system, the part needed, and the quantity required.
  • Page 44: Appendix A: Aups Specifications

    Appendix A: AUPS Specifications UPS kVA Rating (Up to 15) kVA – 1 Phase 1 Phase: 120VAC, 208VAC, 220VAC, 240VAC, & 480VAC AC Input Voltage 3 Phase: 208VAC, 240VAC, 380VAC, & 480VAC AC Input Range -10% / +10% Input Frequency 50Hz or 60Hz (+/-5%) AC Output Voltage 1 Phase: 120VAC, 208VAC, 220VAC &...
  • Page 45: Appendix B: Aups Model Number Chart

    Appendix B: AUPS Model Number Chart UPS Output / Bypass Input AC Input DC Bus Model Number Rectifier Inverter Volts Amps Freq. Freq AUPS - Phase Phase Volts (V) Amps (A) Capacity Input (Hz) (Hz) 2K-A1-ABD1-24V150A 16.67 120/208/240 52/30/26 2K-A1-C1-24V150A 16.67 2K-A1-BD3-24V150A 16.67...
  • Page 46: Appendix C: Field Installable Accessory Kits

    Appendix C: Field Installable Accessory Kits La Marche offers multiple accessory kits that are available for purchase separately from the AUPS systems. These accessories are installable in the field. Not all accessory kits will be installable in all enclosures. –...
  • Page 47: Appendix D: Manufacturer's Warranty

    (4) years of this five (5) year warranty period, the warranty covers parts replacement only and no labor or other services are provided by La Marche, nor is La Marche obligated to reimburse the owner or any other person for work performed.
  • Page 48: Appendix E: Manufacturer's Extended Parts Warranty

    Should minor adjustments be required, the local La Marche sales representative should be contacted to provide this service only. All sales are final. Only standard La Marche units will be considered for return. A 25% restocking fee is charged when return is factory authorized. Special units are not returnable.
  • Page 49: Appendix F: Document Control And Revision History

    Appendix F: Document Control and Revision History Part Number: 137679 Instruction Number: P25-LAUPS-1 Issue ECN: 21597 21597- 01/18...

Table of Contents