Performance Ratings - EcoSmart ES50LVS Installation, Operation And Maintenance Manual

Select multi-speed air handler
Table of Contents

Advertisement

PERFORMANCE RATINGS

ES50LVS
Performance Data - Hot Water Capacities (BTUH) @ 70°F Entering Air Temperature
ecosmart
ES50LVS
CFM
GPM
110°F
3
10,640
300
4
10,910
5
11,070
3
13,170
400
4
13,640
5
13,920
3
15,370
500
4
16,050
5
16,470
3
17,280
600
4
18,190
5
18,770
3
18,950
700
4
20,110
5
20,850
3
20,440
800
4
21,840
5
22,740
3
21,760
900
4
23,400
5
24,480
Air Pressure Drop: 0.04 IWC
Entering Water Temperature
120°F
130°F
140°F
13,320
16,010
18,700
13,650
16,400
19,160
13,850
16,640
19,430
16,510
19,850
23,200
17,080
20,530
23,980
17,430
20,940
24,460
19,260
23,170
27,090
20,100
24,170
28,250
20,630
24,790
28,970
21,660
26,070
30,490
22,800
27,420
32,050
23,510
28,270
33,040
23,780
28,620
33,480
25,210
30,330
35,470
26,130
31,420
36,730
25,650
30,880
36,140
27,390
32,960
38,550
28,510
34,300
40,100
27,310
32,900
38,500
29,360
35,340
41,340
30,690
36,930
43,190
150°F
160°F
170°F
21,400
24,100
26,800
21,910
24,670
27,430
22,220
25,020
27,820
26,550
29,910
33,270
27,440
30,900
34,370
27,990
31,510
35,040
31,020
34,950
38,890
32,330
36,420
40,520
33,150
37,340
41,530
34,920
39,360
43,810
36,700
41,350
46,010
37,810
42,600
47,390
38,360
43,250
48,140
40,620
45,770
50,940
42,050
47,380
52,710
41,410
46,690
51,980
44,150
49,770
55,390
45,920
51,740
57,580
44,120
49,760
55,410
47,360
53,390
59,430
49,460
55,750
62,040
WATER PD
(FT-WG)
@140°F
180°F
29,500
4.38
30,190
4.83
30,610
7.23
36,640
4.38
37,840
4.83
38,570
7.23
42,840
4.38
44,620
4.83
45,720
7.23
48,260
4.38
50,670
4.83
52,180
7.23
53,040
4.38
56,110
4.83
58,050
7.23
57,280
4.38
61,020
4.83
63,420
7.23
61,070
4.38
65,490
4.83
68,340
7.23
5 |
P a g e

Advertisement

Table of Contents
loading

This manual is also suitable for:

Es90lvs