IVC3 Control System
Rev 1.0
IV Produkt Control Unit IVC3
IVC3 Basic Manual 2004-12-15.doc

Advertisement

Table of Contents
loading

Summary of Contents for IV Produkt IVC3

  • Page 1 Basic Manual IVC3 Control System Rev 1.0 IV Produkt Control Unit IVC3 IVC3 Basic Manual 2004-12-15.doc...
  • Page 2 3.5 Alarm pump/cooler 3.6 Alarm revolving heat recovery, VVX 3.7 AUX-input 3.8 Temperature deviation alarm 4. Time schedule 5. Manual overrun of output 6. LED 6.1 LED – RUN 6.2 LED – ALARM IV Produkt Control Unit IVC3 IVC3 Basic Manual 2004-12-15.doc...
  • Page 3 7.4 Analogue input (passive sensor) 7.5 Digital input (from free contacts) 8. Parameter lists 8.1 Menu – ”Status” 8.2 Menu – ”Setup” 8.3 Menu – ”Settings” 8.4 Menu – ”Clock” 9. Communications 3/18 IV Produkt Control Unit IVC3 IVC3 Basic Manual 2004-12-15.doc...
  • Page 4: Introduction

    1. Introduction The control unit IVC3 is used to control an Air Handling Unit (AHU) with supply and exhaust air fans, revolving heat recovery (Rot VVX), heater (electric or water) and cooler 2. Function 1.1 Start up At start up the exhaust fan (EA) starts at set speed and the heat recovery at 100%. After 1 minute the supply fan (SA) starts and control unit starts temperature regulation.
  • Page 5: Heater

    B-alarm generates. The revolving heat recover are running 12 minutes every 4 hour for conditioning. 2.5 Heater By IVC3 an electrical or a water heater-battery can be controlled (selected in operation unit).. Setup Setting Description Config.
  • Page 6: Electrical Heater

    Visible only when Cool battery is selected as Installed. 2. 7 Chill recovery IVC3 can in operating terminal be configured for chill recovery (Cool recycl., Not installed / Installed). In cooling sequence the VVX will start if outdoor temperature exceeds extract air temperature more than 2°...
  • Page 7: Supply Air Control

    Outdoors temperature is according to set value shifting between control mode summer and winter. Shift point differs by a 2° hysteresis and 30 minutes delayed changing to supply air control. 7/18 IV Produkt Control Unit IVC3 IVC3 Basic Manual 2004-12-15.doc...
  • Page 8: Control Sequence

    VVX or with an increasing output signal at analogue VVX) and finally increased output signal to heater. The sequence is opposite at cooling request. Sequences Output signal (V) HEATER COOLER Recovery Dead zon 2ºC Set point Supply temp. (ºC) supply 8/18 IV Produkt Control Unit IVC3 IVC3 Basic Manual 2004-12-15.doc...
  • Page 9: Night Cooling

    20° during one hour. 2.10.1 Night cooling, extract air temperature sensor The IVC3 will after operating-time wait a set delay before starting night cooling. Controller measures extract air temperature for 5 minutes to decide if night cooling is needed. If extract air temperature after check exceeds set start limit (Night cooling start) the unit run until extract air temperature are more than 1°...
  • Page 10: Night Heating

    20° during one hour 2.11.1 Night heating, extract air temperature sensor The IVC3 will after operating-time wait a set delay before starting night heating. Controller measures extract air temperature for 5 minutes to decide if night heating is needed. If extract air temperature after check not exceeds set start limit (Night heating start) the unit would than continue until extract air temperature are more than 1°...
  • Page 11: Outdoor Compensated Setpoint

    (Climate dep. vent., se chapter 2.8.4) 2.13 Outdoor compensated setpoint IVC3 are configurable for outdoor temperature compensation of set point. Summer and/or winter compensation are available. Two limits for outdoor temperature and a compensation value for each summer and winter can be set.
  • Page 12: Alarms

    Setting Description Delay Fan Alarm 0-60 min Time delay in IVC3 before a B-alarm is set and unit stops. 3.2 Fire alarm Alarm activates by external fire alarm equipment. Alarm at open contact. Result: alarm category A, unit stops. 3.3 Freeze protection alarm Freeze alarm activates if temperature drops below set alarm limit.
  • Page 13: Aux-Input

    Four different time events are to be set for workdays (1-5) and four events for weekend (6-7) when configured as groups. IVC3 is equipped with a real time clock for weekdays, hours and minutes. The real time clock has power back-up.
  • Page 14: Manual Overrun Of Output

    LED on operating terminal and controller indicates RUN and ALARM status. 6.1 LED – RUN Diodstatus Function Dark Unit stop Pulse Manual run Normal run 6.2 LED - ALARM Diodstatus Function Dark No alarm FastLit Alarm 14/18 IV Produkt Control Unit IVC3 IVC3 Basic Manual 2004-12-15.doc...
  • Page 15: Digital Output (Relay)

    2. Extended operation input 3. Rotation guard VVX (inductive sensor) 4. Fire alarm 5. Alarm heater pump / alarm electrical heater 6. Alarm cooler pump / alarm cooler 7. AUX-input 15/18 IV Produkt Control Unit IVC3 IVC3 Basic Manual 2004-12-15.doc...
  • Page 16: Parameter Lists

    Delay before an A or B-alarm is set up. 3 min Not used at emergency stop. Delay Fan Alarm 0-60 min Time delay in IVC3 before a B-alarm is set 3 min of and unit stops. Manual operation Off/On Make outputs available for manual overrun Off...
  • Page 17 Switch on point. Visible only when Cool battery is selected as Installed. DX cool stop 0 – 100% Switch off point. Visible only when Cool battery is selected as Installed. 17/18 IV Produkt Control Unit IVC3 IVC3 Basic Manual 2004-12-15.doc...
  • Page 18: Menu – "Clock

    -button or -button to Dag 6-7 manoeuvre in time schedule. 00:00 Stop 06:00 Stop 12:00 Stop 18:00 Stop 9. Communication IVC3 communicates by RS232 with a MODBUS-RTU protocol. (Separate manual). 18/18 IV Produkt Control Unit IVC3 IVC3 Basic Manual 2004-12-15.doc...