Combined alarm package

Advertisement

3.0
Adjusting Parameters
All equipment is shipped from the factory fully checked and adjusted based on the model number. Do not make any
adjustments unless the equipment has been powered-up and the alarm thresholds have been determined to be incorrect.
If the alarm thresholds have been determined to be incorrect, adjustments may be made as detailed below.
Adjust the output voltage/output current to the desired threshold. Turn the corresponding potentiometer so that the
LED is off; refer to Figure 2 for potentiometer and LED location. Slowly turn the potentiometer the opposite direction
until the LED just turns on.
P3 – High Voltage Alarm Threshold Adjustment
LED2 –
High Voltage Alarm LED
P2 – Low Voltage Alarm Threshold Adjustment
P4 – Low Current Alarm Threshold Adjustment
LED1 –
Low Voltage Alarm LED
Figure 2 – Alarm LEDs and Threshold Potentiometer
LED3 –
Low Current Alarm LED