FAULT FINDING GUIDE
CUSTOMER HAD AN ALARM
Ask them to press the Full set button and tell you
The LED's indicate the cause of the alarm and also the setting status at the time.
MAINS LED FLASHING
Mains failure (Restore supply)
ZONE LED FLASHING (in exit)
Check that doors and windows are closed.
Flashing with tamper LED. (A detector has an open tamper).
Flashing with Battery LED. (The detectors battery needs replacing).
ALARM LED ON Full alarm. The LEDs indicate what caused the alarm.
If Engineer reset is programmed into the panel an engineer reset will be required before
the system can be re-armed.
FLASHING WITH ZONE LED
gered
tem was armed.
FLASHING WITHOUT A ZONE LED An engineer reset is required.
BATTERY LED ON
The control panel's battery is disconnected or needs re-
placement.
FLASHING:
Detector has a low battery. The zone LED will flash
to
SIGNALLING LED ON
The system is being blocked by a continuous transmission.
FLASHING
If flashing on its own, an external line monitor has
signalled
Flashing together with a zone indicator. The system is set as a
system and the detector indicated by the flashing zone LED has failed to report in. ( Re-
site the detector where there is good radio reception. Use the RSSI output to check.
CONTACT TRANSMITTER NOT WORKING Check the magnetic contact is operating
correctly. Open lid and check what zone it should be on. Go into the panel engineer mode
and check if it has been programmed onto the correct zone.
Note: the panel will not allow you to program a detector onto two zones. When pro-
grammed onto a zone any previous zone allocation will be deleted.
PIR NOT WORKING
The detector needs 6 minutes to settle on power up.
Set the control into operator walk test mode and walk test the detector with the cover
removed. Removing the cover opens the tamper and overrides the 2 minute inhibit timer.
If the test jumper inside is fitted and the cover replaced it overrides the 2 minute inhibit,
but allows you to walk test it without a tamper alarm.
CUSTOMER HAS FORGOTTEN THEIR CODE Open the panel and short out the MEM
jumper. The user and engineer codes will be restored to the factory defaults 1234 & 4679.
No other programming is affected.
what indicators are on.
A detector on soak test has trig-
whilst the sys-
indicate which one.
that the telephone line is at fault.
s u p e r v i s e d
15
FM4000X and FM4001
CONTROL PANEL
INSTALLATION INSTRUCTIONS
2 6 J u n 1 5 : 4 1 : 2
2
P a n e l d i s a r m e d
ZONES
SIGNALLING
LOW
TAMPER
BATTERY
FM Electronics Ltd
Manufacturer of quality wireless products
CI-123 iSS 2
FIRE
PANIC
FULL SET
PART SET
OFF
ALARM
MAINS ON
FM4000X