Download Print this page

Neptronic SARB24TH Installation Instructions And Specification

Sarb series networkable iaq room sensors

Advertisement

Quick Links

Models
Models
Temp
SARB24TH
SARB24TG
SARB24TV
SARB24TGH
SARB24TGVH
* Networkable: BACnet MS/TP or Modbus (selectable via menu)
Features
Inputs and outputs
o One analog input (AI1)
o One binary input (BI1)
o Two analog outputs (2 AO), commandable via network
o Two binary outputs (2 BO), commandable via network
Enthalpy and dew point calculations (available via network)
Display or hide all the required access for user interaction
Backlit LCD with simple icon and text-driven menus
Selectable Fahrenheit or Celsius scale
BACnet® MS/TP or Modbus (selectable via menu)
o Select MAC address via menu or via network
o Automatic baud rate detection
o Network service port via on-board mini USB connector

Technical Specifications

Description
Temperature Sensor
Sensor range
Display resolution
Humidity Sensor (SARB24TH, SARB24TGH and SARB24TGVH)
Sensor range
Display resolution
CO
Sensor (SARB24TG, SARB24TGH and SARB24TGVH)
2
Operating principle
Sensor range
Accuracy
Response time
VOC Sensor (SARB24TV and SARB24TGVH)
Operating principle
Sensor range
Response time
Start up time
Other
Inputs
Outputs
BACnet
Modbus
Communication Connections
Electrical connection
Operating temperature
Storage temperature
Relative humidity
SARB-161128-ESA.docx
RH
CO2
VOC
Networkable*
-40ºC to 125ºC [-40ºF to 257ºF]
±0.1ºC [0.2ºF]
5 to 95% RH
0.1% RH
Self-calibrating, Non-Dispersive Infrared (NDIR)
400 to 2000 ppm
±30 ppm ±3% of reading (Accuracy is defined after minimum 3 weeks of continuous operation)
2 minutes by 90%
Self-calibrating, Non-Dispersive Infrared (NDIR)
0-1000 ppb isobutylene equivalent tVOCs
< 5 seconds for tVOC
15 minutes
1 Analog input: 0-10Vdc or Thermistor (10k Type 3)
1 Binary input: digital input (dry contact)
2 Binary outputs (BO1 and BO2), dry contracts 24Vac, 1A max 3A in-rush
2 Analog outputs (0 to 10Vdc)
®
BACnet
MS/TP @ 9600, 19200, 38400, 57600 or 76800 bps (B-ASC)
Modbus RTU slave @ 9600, 19200, 38400 or 57600. Selectable parity and stop bit configuration:
No parity, 2 stop bit | Even parity, 1 stop bit | Odd parity, 1 stop bit
24 AWG twisted-shield cable (Belden 9841 or equivalent)
2
0.8 mm
[18 AWG] minimum
0ºC to 50ºC [32ºF to 122ºF]
-30ºC to 50ºC [-22ºF to 122ºF]
5 to 95 % non-condensing
SARB Networkable IAQ Room Sensors
Specification and Installation Instructions
SARB Series
SARB Series
Page | 1

Advertisement

loading
Need help?

Need help?

Do you have a question about the SARB24TH and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Neptronic SARB24TH

  • Page 1: Technical Specifications

    SARB Series Temperature Sensor Sensor range -40ºC to 125ºC [-40ºF to 257ºF] ±0.1ºC [0.2ºF] Display resolution Humidity Sensor (SARB24TH, SARB24TGH and SARB24TGVH) Sensor range 5 to 95% RH Display resolution 0.1% RH Sensor (SARB24TG, SARB24TGH and SARB24TGVH) Self-calibrating, Non-Dispersive Infrared (NDIR)
  • Page 2 Binary Output 1 (BO1) COM for BO2 (ext 24V) If JP2 is set to A+B Binary Output 2 (BO2) Analog Input (AI1) Binary Input 1 (BI1) Analog Output 1 (AO1) Analog Output 2 (AO2) BACnet/Modbus A+ BACnet/Modbus B- www.neptronic.com Page | 2...
  • Page 3 C. Pull all wires through the holes in the base. D. Secure the base to the wall using wall anchors and screws (supplied). Make the appropriate connections. Mount the control module on the base and secure using the screw. www.neptronic.com Page | 3...
  • Page 4: Programming Mode

    Modbus Addrss Modbus Baud Rate Modbus port Config “Show Sensor Value” Auto NP2S (1-246) (default) (no parity, 2 stop bits) EP1S (even parity, 1 stop bit) 9.6k, 19.2k, 38.4, 57.6k OP1S (odd parity, 1 stop bit) www.neptronic.com Page | 4...
  • Page 5: Operation Mode

    Lock or unlock display of sensor readings Next/previous sensor reading Enable/disable backlight NOTE: The display of each sensor reading can be enabled or disabled via program (PGM) mode. www.neptronic.com Page | 5...
  • Page 6 Programmable up to 32 characters. The default value is Model_Name Description Programmable up to 32 characters. The default value is "Networkable Room Sensor" Object_Type Device System_Status Always OPERATIONAL (0) Vendor_Identifier Always 153 Vendor_Name Always Neptronic Model_Name Example, SARGVH Firmware_Revision currently, 1.01 Application_Software_Version currently, 1.25 Protocol_Version Always 1 Protocol_Revision...
  • Page 7 Binary Output (BO) Name Description Writable Notes Present Value 0 = Open, 1 = Close BO.1 StatusBO1 Binary output 1 Relinquish Default Present Value 0 = Open, 1 = Close BO.2 StatusBO2 Binary output 2 Relinquish Default www.neptronic.com Page | 7...
  • Page 8 Present Value 2= 10K Thermistor 3= 0_10Volt Unit type displayed on the 1= Metric MSV.19 Local Units Present Value thermostat 2= Imperial Unit type displayed via 1= Metric MSV.20 Network Units Present Value network 2= Imperial www.neptronic.com Page | 8...
  • Page 9 The uses Modbus communication protocol over serial line in the RTU mode and provides a Modbus network interface between client devices and Neptronic devices. These instructions assume that you are familiar with Modbus terminology. The following are the requirements for Modbus: •...
  • Page 10 Regi Data Writa ster Description Range Type Index MSB = Neptronic ID MSB = 18 40000 Unsigned LSB = Modbus address of current device LSB = 1-246 Unsigned 0, 9600, 19200, 38400, or 57600, 0 = Auto Baud Rate Detection...
  • Page 11 B4: Keypad Upperleft Lock B7: Program Mode Lock 40035 Lock options Bit String 0 = Off, 1 = On 0 = Off, 1 = On B5: Keypad Bottomleft Lock [B8 – B15]: Reserved 0 = Off, 1 = On www.neptronic.com Page | 11...
  • Page 12 SARB Networkable IAQ Room Sensors Specification and Installation Instructions Notes www.neptronic.com Page | 12...