WARNINGS The Following Safety Precautions Must Be Strictly Adhered To At All Times. 1. YOU AS THE OWNER OR OPERATOR OF BOSTON GEAR EQUIPMENT HAVE THE RESPONSIBILITY TO HAVE THE USERS OF THIS EQUIPMENT TRAINED IN ITS OPERATIONS AND WARNED OF ANY POTENTIAL HAZARDS OF SERIOUS INJURY.
® MEX (55) 53 63 23 31 MTY (81) 83 54 10 18 BETAplus ventas@industrialmagza.com DIST. AUTORIZADO QRO (442) 1 95 72 60 Section I – General Information INTRODUCTION This manual contains installation, operation, and maintenance and repair instructions for Boston BETAplus Single- Phase Adjustable-Speed DC Motor Controllers.
® MEX (55) 53 63 23 31 MTY (81) 83 54 10 18 BETAplus ventas@industrialmagza.com DIST. AUTORIZADO QRO (442) 1 95 72 60 Section II – Installation Before starting the installation, read this section thoroughly. In addition, a thorough review of the Ratings And Specifications (Section VI) is recommended.
® MEX (55) 53 63 23 31 MTY (81) 83 54 10 18 BETAplus ventas@industrialmagza.com DIST. AUTORIZADO QRO (442) 1 95 72 60 5. ISOLATION TRANSFORMER – While not required, an isolation transformer can provide the following advantages: a. Reduce the risk of personal injury if high voltage drive circuits are accidentally touched. b.
® MEX (55) 53 63 23 31 MTY (81) 83 54 10 18 BETAplus ventas@industrialmagza.com DIST. AUTORIZADO QRO (442) 1 95 72 60 TABLE 2. JUMPER J4 POSITIONS MOTOR ARMATURE CURRENT RATING (AMPERES)* JUMPER POSITION 2 HP Maximum 3 HP Maximum 100% *Select the position closest to the motor nameplate armature current rating.
® MEX (55) 53 63 23 31 MTY (81) 83 54 10 18 BETAplus ventas@industrialmagza.com DIST. AUTORIZADO QRO (442) 1 95 72 60 INITIAL STARTUP Remove the controller cover (if used) by removing the four cover screws. Be sure all wiring is correct and all connections are tightened securely. Be sure the controller is calibrated correctly.
® MEX (55) 53 63 23 31 MTY (81) 83 54 10 18 BETAplus ventas@industrialmagza.com DIST. AUTORIZADO QRO (442) 1 95 72 60 Section III – Operation POWER ON/OFF The controller energizes when the AC voltage is supplied to the controller. NOTE: Whenever the AC supply voltage is applied to the controller, the motor shunt field is energized with rated voltage, and potentially hazardous voltage is present at the motor armature terminals.
® MEX (55) 53 63 23 31 MTY (81) 83 54 10 18 BETAplus ventas@industrialmagza.com DIST. AUTORIZADO QRO (442) 1 95 72 60 SPEED CONTROL Motor speed is directly proportional to the setting of the MOTOR SPEED potentiometer or the magnitude of an external speed reference signal, as applicable.
® MEX (55) 53 63 23 31 MTY (81) 83 54 10 18 BETAplus ventas@industrialmagza.com DIST. AUTORIZADO QRO (442) 1 95 72 60 Section IV – Maintenance and Repair GENERAL Keep the controller dry and free of dust, dirt, and debris. No parts require periodic replacement. Periodically disconnect the AC line to the controller and check all wire terminations to be sure they are tight.
® MEX (55) 53 63 23 31 MTY (81) 83 54 10 18 BETAplus ventas@industrialmagza.com DIST. AUTORIZADO QRO (442) 1 95 72 60 MAXIMUM SPEED (ARMATURE FEEDBACK) The MAX SPD potentiometer adjusts maximum speed by setting maximum armature voltage. The voltage range is from 50% to 100% of rated armature voltage.
® MEX (55) 53 63 23 31 MTY (81) 83 54 10 18 BETAplus ventas@industrialmagza.com DIST. AUTORIZADO QRO (442) 1 95 72 60 OFFSET An offset adjustment is desirable when a 4 to 20 mA speed reference signal is used. The MIN SPD potentiometer compensates for the 4 mA offset.
® MEX (55) 53 63 23 31 MTY (81) 83 54 10 18 BETAplus ventas@industrialmagza.com DIST. AUTORIZADO QRO (442) 1 95 72 60 TROUBLESHOOTING TABLE 5. TROUBLESHOOTING INDICATION POSSIBLE CAUSE CORRECTIVE ACTION AC line open Be sure rated AC line voltage is applied to the controller Operator controls inoperative or Repair accordingly.
Page 25
® MEX (55) 53 63 23 31 MTY (81) 83 54 10 18 BETAplus ventas@industrialmagza.com DIST. AUTORIZADO QRO (442) 1 95 72 60 TROUBLESHOOTING TABLE 5. TROUBLESHOOTING (continued) INDICATION POSSIBLE CAUSE CORRECTIVE ACTION Check shunt field current.(1) Low shunt field current causes excessive armature current.
Page 26
® MEX (55) 53 63 23 31 MTY (81) 83 54 10 18 BETAplus ventas@industrialmagza.com DIST. AUTORIZADO QRO (442) 1 95 72 60 TROUBLESHOOTING TABLE 5. TROUBLESHOOTING (continued) INDICATION POSSIBLE CAUSE CORRECTIVE ACTION AC line voltage fluctuating Observe line voltage with a voltmeter or oscilloscope.
® MEX (55) 53 63 23 31 MTY (81) 83 54 10 18 BETAplus ventas@industrialmagza.com DIST. AUTORIZADO QRO (442) 1 95 72 60 Section V – Parts List TABLE 6. PARTS LIST, BETAplus CONTROLLERS BOSTON PART NUMBER PART RATING RBS2 RBS3 Control Board 64971...
® MEX (55) 53 63 23 31 MTY (81) 83 54 10 18 BETAplus ventas@industrialmagza.com DIST. AUTORIZADO QRO (442) 1 95 72 60 SPECIFICATIONS (continued) TABLE 11. DIP SWITCH S3 SETTINGS Segment Position Segment Description (Closed) (Open) Low voltage tachometer generator signal (8 - 30 VDC) High voltage tachometer generator signal (31 - 175 VDC) Armature feedback Tachometer feedback with armature feedback backup...
Page 32
® MEX (55) 53 63 23 31 MTY (81) 83 54 10 18 BETAplus ventas@industrialmagza.com DIST. AUTORIZADO QRO (442) 1 95 72 60 SPECIFICATIONS (continued) 10. POWER CONVERSION -The DC power bridge consists of four SCR’s and a freewheeling diode. Each device is rated at least 600 PIV.