Loreme ICL70 Configuration Handbook

Ethernet / rs485 gateway

Advertisement

Quick Links

Ethernet / RS485 Gateway
CONFIGURATION HANDBOOK
ICL70
LOREME 12, rue des Potiers d'Etain Actipole BORNY - B.P. 35014 - 57071 METZ CEDEX 3
Phone 03.87.76.32.51
Contact : Commercial@Loreme.fr - Technique@Loreme.fr
Download manual at : www.loreme.fr
REV0.1.2 - 07/07/17
E 1

Advertisement

Table of Contents
loading

Summary of Contents for Loreme ICL70

  • Page 1 Ethernet / RS485 Gateway CONFIGURATION HANDBOOK ICL70 LOREME 12, rue des Potiers d'Etain Actipole BORNY - B.P. 35014 - 57071 METZ CEDEX 3 Phone 03.87.76.32.51 Contact : Commercial@Loreme.fr - Technique@Loreme.fr Download manual at : www.loreme.fr REV0.1.2 - 07/07/17...
  • Page 2: Table Of Contents

    2) Recommendation of use ........................... p15 2.1) General remarks ........................... p15 2.2) Power Supply ..........................p15 2.3) Inputs / Outputs ..........................p15 WIRING ................................p16 LOREME 12, rue des Potiers d'Etain - 57071 Metz  03.87.76.32.51 - Email: Commercial@Loreme.fr - Technique@Loreme.fr...
  • Page 3: Device Presentation

     TABLE OF CONTENTS Device Presentation RJ45 Ethernet 24 V DC power supply terminals OLED display  2 lines of 8  characters  Push buttons  RS485 end-of-line resistors (125 Ohms) switch. Heating relay output, between C / R contacts 2 RS485 links (A1/B1, A2/B2) Dry contact connection terminals with 24 V DC bias (client module)
  • Page 4: Implementation Diagram

          Sensor sup- ply activation on the ser- vers M12 DER M12 DER Controller with PASSIV PASSIV RS485 link LOREME 12, rue des Potiers d'Etain - 57071 Metz  03.87.76.32.51 - Email: Commercial@Loreme.fr - Technique@Loreme.fr...
  • Page 5: Front Face Visualization

     TABLE OF CONTENTS Front face visualization When powering up, the device reads and displays the current revision of the measurement and Ethernet part for about 1 second. R:0.1.2 0.1: Hard & Soft revision of the measurement part. Soft revision of the Ethernet part. "-"...
  • Page 6: Configuration Via The Front Face

       PORT? Press to increase or to decrease the port number and to validate it. 10000 The default port number is 10000. LOREME 12, rue des Potiers d'Etain - 57071 Metz  03.87.76.32.51 - Email: Commercial@Loreme.fr - Technique@Loreme.fr...
  • Page 7: Heating Relay Thresholds

     TABLE OF CONTENTS 4) Heating relay thresholds  TEMP AL? Press (Yes) button to access to the temperature threshold setting.  (Y-N) Press (No) button to skip the rubric. THRESH.?   to modify the value in 0.1 °C step. ...
  • Page 8: Terminal Link Setting

    To modify the terminal parameters while the latter is connected, it is necessary to disconnect it. When reconnecting, the new parameters will be taken into account. LOREME 12, rue des Potiers d'Etain - 57071 Metz  03.87.76.32.51 - Email: Commercial@Loreme.fr - Technique@Loreme.fr...
  • Page 9: Terminal Mode

     TABLE OF CONTENTS Terminal mode 1) Visualization When the terminal connection is established, the ICL70 displays the temperature and relative humidity measurements from the embedded sensor every 2 seconds. 45.3 % Temp: 26.3 °C Note: When connecting to a client device, frames from the controller may be momentarily displayed on the terminal.
  • Page 10: Password

    Enter the threshold value for the temperature (5 °C at factory out). HUMIDITY THRESHOLD? 80.0 % Enter the threshold value for the relative humidity (80 % at factory out). E 10 LOREME 12, rue des Potiers d'Etain - 57071 Metz  03.87.76.32.51 - Email: Commercial@Loreme.fr - Technique@Loreme.fr...
  • Page 11: Embedded Sensor Measurements Offset

    - Use the "+" and "-" keys to adjust the offset, the measure is directly modified. - Type on "Enter" to save the adjusted offset. - The ICL70 switches to the offset setting mode of the relative humidity measurement. OFFSET: 0 % offset function, offset value.
  • Page 12: Ethernet Part Firmware Update

    - Step 2: Click on « Browse.. » and search the file « xxxxx. rom » that you receive by e-mail. - Click on « Next » E 12 LOREME 12, rue des Potiers d'Etain - 57071 Metz  03.87.76.32.51 - Email: Commercial@Loreme.fr - Technique@Loreme.fr...
  • Page 13  TABLE OF CONTENTS - select the line « No other file to install » - Click on « Next » - Click on « Next » - Wait that all lines become green and end with « succeeded.. » message. - Close the windows and quit the "Deviceinstaller"...
  • Page 14: Measurement Part Firmware Update

    FIRMWARE LOADER Rev3 READY TO TRANSFER... The device is now in the firmware load mode and is waiting for the firmware file. This file is provide by LOREME and contain the firmware code in Intel HEX format. Select the « Transfer », « Send a text file ... » in the HyperTerminal menu.
  • Page 15: Emc Consideration

    1) Introduction To meet its policy concerning EMC, based on the Community directives 2014/30/EU & 2014/35/EU, the LOREME company takes into account the standards relative to this directives from the very start of the con- ception of each product. The set of tests performed on the devices, designed to work in an industrial environment, are made in accor- dance with IEC 61000-6-4 and IEC 61000-6-2 standards in order to establish the EU declaration of confor- mity.
  • Page 16: Wiring

    Link to sensors on a server: Pair Red / Black: 24 VDC supply. Pair Blue / White: RS485 A / B connection. E 16 LOREME 12, rue des Potiers d'Etain - 57071 Metz  03.87.76.32.51 - Email: Commercial@Loreme.fr - Technique@Loreme.fr...