  • Page 1 INSTALLATION INSTRUCTIONS (English) WWW.BRINKAIRFORLIFE.NL 614485-C...
  • Page 3 Renovent Sky 200 (Plus) STORE NEAR THE APPLIANCE This appliance can be used by children aged from 8 years and above and persons with reduced physical, sensory or mental capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning use of the appliance in a safe way and understand the hazards involved.
  • Page 4: Table Of Contents

    Table of contents page Delivery..................................Scope of delivery ............................... Accessories Renovent Sky 200 ..........................Application ................................4 Version..................................Technical information ..............................Connections and dimensions ............................ Fan graph .................................. Exploded view appliance ............................Operation .................................. Description................................. Bypass conditions..............................Frost protection................................Renovent Sky Plus version............................
  • Page 5: Delivery

    Scope of delivery Before starting installation of the heat recovery unit, check that it has been supplied complete and undamaged. The scope of delivery of the heat recovery unit Renovent Sky 200 includes the following components: 1: Heat recovery appliance 2: Wall mounting bracket kit;...
  • Page 6: Accessories Renovent Sky 200

    Chapter 1 Delivery Accessories Renovent Sky 200 Electric postheater 310730 Electric (extra) preheater 310740 Splitter RJ12 510472 sensor eBus surface-mounted 532126 Transmitter wireless remote control 2 positions (with. battery) 532170 Transmitter wireless remote control 4 positions (with. battery) 532171 Receiver wireless remote control (for battery version) 532172 Kit wireless remote control 2 positions (1 transmitter &...
  • Page 7 Silencer- / air distribution box 100 x 50 mm (12x) 423012 200 mm 660 mm 482 mm Silencer- / air distribution box 130 x 60 mm (12x) 423013 200 mm 660 mm 482 mm Servicetool 531961 Renovent Sky 200 Rev. C...
  • Page 8: Application

    The Renovent Sky 200 comes ready to plug in with a 230 V mains plug. The appliance comes as standard with a “Brink Air control”, but connection of a simple 4-way switch is possible as well.
  • Page 9: Version

    Chapter 3 Version 3.1 Technical information Renovent Sky 200 Supply voltage [V/Hz] 230/50 Protection degree IP30 Dimensions (w x d x h) [mm] 1000 x 660 x 198 Duct diameter [mm] Ø160 External diameter condensate discharge [“] Weight [kg] 24,5...
  • Page 10: Connections And Dimensions

    1 To dwelling 2 To atmosphere 3 From dwelling 4 From atmosphere 5 Electric connections 6 Connection condensate discharge Fan graph Note: The value stated in the circle is the capacity per fan (in Watt) = [W] Renovent Sky 200 Rev. C...
  • Page 11: Exploded View Appliance

    17 Service connector 18 Sleeve low voltage cable 19 Sleeve cable 230 V. postheater or extra preheater 20 Mains cable 230 V. 21 9-pole connector (only for Plus version) 22 Connector eBus Fall Protection front panel Renovent Sky 200 Rev. C...
  • Page 12: Operation

    See §9 for more information on the connection possibilities of connectors X14 and X15. Hole for gland to be mounted by installer (for sleeve cable postheater/ extra preheater). Renovent Sky 200 Rev. C...
  • Page 13: Installation

    The Renovent Sky 200 can directly be mounted to the wall or the condensate discharge ceiling using the mounting brackets supplied for that purpose. possible to replace them in due course.
  • Page 14: Placing The Appliance For Ceiling Mounting

    Chapter 5 Installation 1005 mm Click! Appliance disconnecting from mounting bracket Condensate discharge Renovent Sky 200 Rev. C...
  • Page 15: Placing The Appliance For Wall Mounting

    . 2 5 m 5 0 5 m i n . 2 5 m m i n . 1 0 0 m 6 7 0 Click! Appliance disconnecting from mounting bracket Condensate discharge Renovent Sky 200 Rev. C...
  • Page 16: Connecting The Condensate Discharge

    Before connecting the condensate discharge to the appliance, cannot be removed from the appliance for service pour water into the U-trap to create an air trap. purposes! 3/4” Detachable coupler Detachable coupler Renovent Sky 200 Rev. C...
  • Page 17 Chapter 5 Installation 60 mm Renovent Sky 200 Rev. C...
  • Page 18 Chapter 5 Installation 60 mm Renovent Sky 200 Rev. C...
  • Page 19: Electric Connections

    The “Brink Air control” that comes as standard with the appliance must be connected to the eBus connector. This (detachable) 2-pole eBus connector is mounted on the outside of the appliance (see also §10.1).
  • Page 20: Display

    Settings in the “Brink Air control” software is set for the English language. In the setting menu “Brink Air of the Renovent Sky 200 can be called up and changed with Control”, §6.4.2, you can choose a language.
  • Page 21: View On Display

    Chapter 6 Display View on Display When the Renovent Sky is in operating mode, the “Brink Air control” display indicates a number of different values: Flow rate indicator 10.54 01.03.16 Fan indicator HRU-Ventilation 0 8 :0 0 17:0 0 Fault symbol...
  • Page 22: Main Menu

    Chapter 6 Display Main menu Pressing the right-hand setting knob on the “Brink Air control” takes you to the MAIN MENU 10.54 23/11/15 In this main menu you can use the right-hand setting knob to HRU-Ventilation 0 8 :0 0 17:0 0 select one of the 3 available manuals (rotate to select and press - Device information §6.4.1...
  • Page 23: Device Information Menu

    Airflow extract 0 m³/h Airflow extract 0 m³/h T dwelling 20.0 °C T dwelling 20.0 °C T atmosphere 15.3 °C T atmosphere 15.3 °C 0.0 % 0.0 % CO2-Sensor 1 CO2-Sensor 2 CO2-Sensor 3 CO2-Sensor 4 Renovent Sky 200 Rev. C...
  • Page 24: Basic Settings Menu

    - Language Installer - Clock - Date - Key lock Language In this menu you can choose a language; ex factory the “Brink Air Control” is set for the English language. The optional languages are: Dutch 10.56 01.03.16 10.58 01.03.16...
  • Page 25: Installer Menu

    Min. PPM ebus CO2-Sensor 3 Max.PPM ebus CO2-Sensor 3 Min. PPM ebus CO2-Sensor 4 Max.PPM ebus CO2-Sensor 4 Offset flow Default position switch 10.59 01.03.16 Airflow - mode 0 50m³/h Standard: 50 m³/h Range: 0 or 50 m³/h Renovent Sky 200 Rev. C...
  • Page 26: Fault

    Chapter 7 Fault Trouble shooting When the appliance control system detects a fault, it is indi- cated on the display of the “Brink Air control” with a spanner symbol, possibly together with a fault code. Non-locking fault 10.59 01.03.16 Messages...
  • Page 27: Display Codes

    If mode 2 of a multiple switch does not work, the modular connector of the multiple switch has been connected the wrong way round. Cut off one of the RJ connectors to the multiple switch and mount a new connector the other way round. Renovent Sky 200 Rev. C...
  • Page 28: Maintenance

    LED at the switch lights up. Filter It is not permitted to use the appliance without 10.54 01.03.16 HRU-Ventilation 0 8 :0 0 17:0 0 Filter 10.54 01.03.16 HRU-Ventilation Manual Filter ca. 10 sec. 10.54 01.03.16 HRU-Ventilation Manual Filter Renovent Sky 200 Rev. C...
  • Page 29 Chapter 8 Maintenance Click! 10.54 01.03.16 HRU-Ventilation Manual Filter 5 sec. Filterreset 10.54 01.03.16 HRU-Ventilation 0 8 :0 0 17:0 0 Renovent Sky 200 Rev. C...
  • Page 30: Maintenance Installer

    Chapter 8 Maintenance Maintenance installer Swing open the front panel (can also be taken from the hinges, if required). Renovent Sky 200 Rev. C...
  • Page 31 Chapter 8 Maintenance there may still be some condensate left in the condensate Rinse the exchanger bin! with hot water and a regular detergent. max. 45 ºC Renovent Sky 200 Rev. C...
  • Page 32 Chapter 8 Maintenance Renovent Sky 200 Rev. C...
  • Page 33 > ± 25 sec 10.54 23/11/15 HRU-Ventilation 08:00 17:00 Clic k! Filter reset; see §8.1 point 6 Press the Return key ( ) to leave any selected menu and the appliance will return to operating mode. Renovent Sky 200 Rev. C...
  • Page 34: Elektric Diagram

    Motor bypass pre-heater temperature extract fan temperature switch board connector valve sensor sensor external “Brink Air sensor 0-10 V RH-sensor post-heater output 0-10V 24V. switch (optional) control” applicable post-heater input contact Renovent Sky 200 Rev. C...
  • Page 35: Electric Connections Accessories

    1 or 2. The boost mode can be reset by putting the switch to setting 3 for longer than 2 seconds or by switching it to absence mode ( Renovent Sky 200 Rev. C...
  • Page 36: Coupling Several Appliances

    Important: Because of polarity sensitivity, always connect contacts X1-1 to X1-1 and contacts X1-2 to X1-2. Never connect X1-1 and X1-2. A maximum of 10 appliances (1 Master + 9 Slave max.) 10.4 Connection RH (humidity)-sensor Cable sleeve Setting parameter 28 & 29 (§12) Renovent Sky 200 Rev. C...
  • Page 37: Connection Postheater Or Extra Preheater

    ) The strain reliever to be installed by the installer (not supplied with the appliance) for feeding the 230 volt cable to the postheater or extra preheater. 230V 50Hz Connection extra preheater 230V 50Hz Setting parameter 11 (§12)) Renovent Sky 200 Rev. C...
  • Page 38: Connection Geo Heat Exchanger

    Chapter 10 Electric connections accessories 10.6 Connection geo heat exchanger 30°C 25°C Minimum temperature Maximum temperature To dwelling To atmosphere From dwelling 15°C From atmosphere 10°C 3°C 0°C Setting parameter 25, 26 & 27 (§12) Renovent Sky 200 Rev. C...
  • Page 39: Connecting External Switch Contact

    Connections no. 3 and no. 4 standard 0-10 volt input; connections no. 1 and no. 2 can optionally be used as 0-10 volt input as well. Setting parameter 19, 20 & 21 (§12) Renovent Sky 200 Rev. C...
  • Page 40: Service

    When ordering parts, in addition to the article code number Example (see exploded view), please state the type of the heat recovery appliance, the serial number, the year of production and the Appliance type : Renovent Sky 200 name of the part: Serial number : 424000172501 Year of production...
  • Page 41 Cable with power plug 230 volt * 533009 Heating coil 375 W preheater 533020 Air Control 510498 The mains cable has a print connector. When replacing it, always order a replacement mains cable Brink without prior notice. Renovent Sky 200 Rev. C...
  • Page 42: Setting Values

    0 (= Extract fan off) 2 (= Flow rate mode 1) Extract fan mode 3 (= Flow rate mode 2) 4 (= Flow rate mode 3) switching input 1 5 (= Multiple switch) 7 (= No extract fan activation) Renovent Sky 200 Rev. C...
  • Page 43 0,5 °C (Above this temperature the valve opens.) FACTORY SETTING RENOVENT ADJUSTING RANGE OFF (= RH-sensor not active) RH-sensor ON (= RH-sensor active) +2 most sensitive Sensitivity 0 default setting RH-sensor RH-sensor -2 least sensitive Renovent Sky 200 Rev. C...
  • Page 44 Flow correction 100% 90% - 110% Default position switch 0 - 1 FACTORY SETTING RENO- ADJUSTING RANGE VENT SKY Brink Connect function (exter- nal, Brink connect no RH sen- Brink Connect sor) Brink Connect (internal) Renovent Sky 200 Rev. C...
  • Page 45: Declaration Of Conformity

    Chapter 13 Declaration of conformity DECLARATION OF CONFORMITY Manufacturers: Brink Climate Systems B.V. Address: P.O. Box 11 NL-7950 AA Staphorst, The Netherlands Product : Renovent Sky 200 The product described above complies with following directives: 2014/35/EU (low voltage directive) 2014/30/EU (EMC directive)
  • Page 46: Erp Values

    Internet address for Assembly instructions: http://www.brinkclimatesystems.nl/installateurs/kenniscentrum/Documentatie.aspx Bypass: Yes; 100% Bypass * Measurements executed by TZWL according to the EN 13141-7 standard (TZWL-report M.84.03.215.AD, June 2016) SEC Class („Average climate“) SEC in kWh/m²/a SEC < -42 Renovent Sky 200 Rev. C...