UL BADF090 Installation Instruction

Single package convertible series dual fuel heat pumps

Advertisement

Quick Links

INSTALLATION
INSTRUCTION
208/230/460 VOLT
MODELS ONLY
SAFETY CONSIDERATIONS
Due to system pressure, moving parts and electrical components,
installation and servicing of air conditioning equipment can be hazardous.
Only qualified, trained, service personnel should install, repair, maintain
or service this equipment.
Observe all precautions in the literature, on labels and tags
accompanying the equipment whenever working on air conditioning
equipment. Be sure to follow all other safety precautions that apply.
Wear safety glasses and work gloves, and follow all safety
codes. Use a quenching cloth and have a fire extinguisher
available for all brazing operations.
GENERAL
Model BDF Dual Fuel Heat Pumps are single package units with gas
heat designed for outdoor installation on a rooftop or a slab.
The units are completely assembled on rigid, permanently
attached base rails. All piping, refrigerant charge, and electrical
wiring is factory installed and tested. The units require only
electric power and duct connections at the point of installation.
The gas-fired heaters have aluminized steel tubular heat
exchangers and spark ignition with proven pilot.
INSPECTION
As soon as a unit is received, it should be inspected for possible
damage during transit. If damage is evident, the extent of the
FOR YOUR SAFETY
If you smell gas:
1. Open windows.
2. Don't touch electrical switches; do not use
any phones in the area of the gas leak.
3. Extinguish any open flame.
4. Immediately call your gas supplier from another
location. Follow your gas supplier's instructions.
5. If you cannot reach your gas supplier, call the fire
department.
FOR YOUR SAFETY
Do not store or use gasoline or other flammable
vapors and liquids in the vicinity of this or any
other appliance
.
Installer should pay particular attention to the words: NOTE, CAUTION and WARNING . Notes are intended to clarify or make
the installation easier. Cautions are given to prevent equipment damage. Warnings are given to alert installer that personal in-
jury and/or equipment damage may result if installation procedure is not handled properly.
SINGLE PACKAGE
CONVERTIBLE SERIES
DUAL FUEL HEAT PUMPS
Supersedes: 511.17-N2W (293)
MODELS BADF090 & 120
(9.0 EER)
damage should be noted on the carrier's freight bill. A separate
request for inspection by the carrier's agent should be made in
writing. Refer to Form 50.15-NM for additional information.
REFERENCE
Additional information on the design, installation, operation and
service of this equipment is available in the following reference forms:
530.18-N3.2V
530.18-N3.8V
530.18-N3.9V
530.18-N3.10V - Manual Outdoor Air Damper 0-100%
530.18-N8.4V
530.18-N10.5V - Propane Conversion Accessory (USA)
530.18-N10.6V - High Altitude Accessory (Nat. Gas)
530.18-N10.7V - High Altitude Accessory (Propane)
690.15-N28V
Renewal Parts:
Refer to the Renewal Parts Manual for complete listing of
replacement parts on this equipment.
All forms referenced in this instruction may be ordered from:
APPROVALS
Design certified by U.L. as follows:
1. For use as a heat pump only unit or a heat pump unit with
a forced air furnace.
2. For outdoor installation only.
3. For installation on combustible material.
4. For use with natural gas or propane gas.
Not suitable for use with conventional venting systems.
LIMITATIONS
THIS PRODUCT MUST BE INSTALLED IN STRICT COMPLIANCE
WITH THE ENCLOSED INSTALLATION INSTRUCTIONS AND ANY
APPLICABLE LOCAL, STATE, AND NATIONAL CODES
INCLUDING, BUT NOT LIMITED TO, BUILDING, ELECTRICAL,
AND MECHANICAL CODES.
INCORRECT INSTALLATION MAY CREATE A CONDITION
WHERE THE OPERATION OF THE PRODUCT COULD CAUSE
PERSONAL INJURY OR PROPERTY DAMAGE
208/230/575 VOLT
MODELS ONLY
- Economizer Accessory
- Motorized Outdoor Air Damper Accy.
- Manual Outdoor Air Damper 0-35%
- Gas Piping Accessory
- Low Ambient Accessory
Publications Distribution Center
Unitary Products Group
P.O. Box 1592, York, Pa. 17405
CAUTION
WARNING
511.17-N2W (398)
035-15683

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the BADF090 and is the answer not in the manual?

Questions and answers

Summary of Contents for UL BADF090

  • Page 1: Installation Instruction

    INSTALLATION CONVERTIBLE SERIES INSTRUCTION DUAL FUEL HEAT PUMPS Supersedes: 511.17-N2W (293) 511.17-N2W (398) 035-15683 MODELS BADF090 & 120 (9.0 EER) 208/230/575 VOLT MODELS ONLY 208/230/460 VOLT MODELS ONLY SAFETY CONSIDERATIONS damage should be noted on the carrier’s freight bill. A separate Due to system pressure, moving parts and electrical components, request for inspection by the carrier’s agent should be made in...
  • Page 2: Table Of Contents

    511.17-N2W TABLE OF CONTENTS Safety Considerations............1 MAINTENANCE & TROUBLESHOOTING General ................1 Normal Maintenance............17 Inspection................1 Cleaning Flue Passages and Heating Elements ....17 Reference ................1 Troubleshooting ..............18 Approvals ................1 Replacement Parts ............19 Nomenclature............... 2 TABLES INSTALLATION Description...
  • Page 3: Installation

    511.17-N2W INSTALLATION These units must be installed in accordance with the following OUTDOOR COIL CONDENSATE DRAINAGE national and local safety codes: PRECAUTION 1. National Electrical Code ANSI/NFPA No. 70. Condensate will drain from the outdoor coil during the heating and defrost cycles. Normally this condensate may be allowed 2.
  • Page 4: Condensate Drain

    The internal wiring harness furnished with this unit is an integral COMPRESSORS part of a UL and C.G.A. design certified unit. Field alteration to comply with electrical codes should not be required. The compressors are mounted on springs which have been tightened down for shipment only.
  • Page 5: Gas Connection

    511.17-N2W FIG. 3 - TYPICAL FIELD WIRING TABLE 3 - PIPE SIZING CHART TABLE 2 - GAS HEAT APPLICATION DATA Nominal Iron Pipe Size Temp. Rise °F Input Output Length in Feet Available on Gas Rate 1/2 in. 3/4 in. 1 in.
  • Page 6: L.p. Units, Tanks And Piping

    511.17-N2W FIG. 5 - BOTTOM SUPPLY CONNECTION FIG. 4 - EXTERNAL SUPPLY CONNECTION EXTERNAL SHUT-OFF EXTERNAL SHUT-OFF Check all connections for leaks when piping is completed, soap solution or other material suitable for the purpose. NEVER USE A FLAME. using a soap solution. NEVER USE A FLAME. 6.
  • Page 7: Utilities Entry Data

    511.17-N2W VENT AIR BLOWER OUTLET HOOD COMPRESSOR ACCESS FIELD-SUPPLIED ACCESS CONTROL WIRING DISCONNECT SWITCH (See Detail "X") ENTRY LOCATION CONDENSER 33-7/8" COIL (090) 39-7/8" DOT PLUG FOR PRESSURE (120) CHECK 47-7/8" (150) COMBUSTION DOT PLUG FOR PRESSURE CHECK INLET HOOD RETURN AIR 1-1/4"...
  • Page 8 511.17-N2W DETAIL "Y" (UNIT WITH ECONOMIZER RAIN HOOD) CLEARANCES Locate unit so that the vent air outlet hood is at least: Front 24" • Three (3) feet above any forced air inlet located within 10 12" (Less Economizer) Back 36" (With Economizer/ horizontal feet (excluding those integral to the unit).
  • Page 9: Physical Data

    511.17-N2W TABLE 4 - PHYSICAL DATA WEIGHTS (LBS) MODEL 130 Mbh 1140 7-1/2 165 Mbh 1160 CENTRIFUGAL BLOWER (Dia. x Wd. in.) 12 x 12 15 X 12 SUPPLY AIR BASIC UNIT BLOWER FAN MOTOR HP (STANDARD) 165 Mbh 1515 200 Mbh 1535 ROWS DEEP...
  • Page 10: Accessory Static Resistances

    511.17-N2W TABLE 6 - ACCESSORY STATIC RESISTANCES* EXTERNAL STATIC PRESSURE DROP - RESISTANCE, IWG DESCRIPTION 2250 3000 4000 5000 Economizer 0.02 0.02 0.03 0.05 *Deduct these resistance values from the available external static pressure shown in the respective Blower Performance Table. TABLE 7 - BLOWER MOTOR AND DRIVE DATA ADJUSTABLE FIXED...
  • Page 11: Operation

    511.17-N2W OPERATION COOLING SYSTEM HEATING MODE - AMBIENT TEMPERATURE ABOVE BALANCE POINT: The unit will operate in the mechanical The cooling section is a complete factory package utilizing an heating mode with both compressors energized through the air-cooled condenser. The system is factory-charged with heat relay for stage 1 heating (W1).
  • Page 12: Defrost Sequence Of Operation

    511.17-N2W DEFROST SEQUENCE OF OPERATION LOCKOUT CONTROL: Any one of four conditions will put the system into a lock-out condition during the heating or cooling These heat pumps have a unique “ambient modified” mode: time-temperature defrost control that automatically adjusts to changes in the outdoor temperature.
  • Page 13: Heating System (Gas Heat)

    511.17-N2W HEATING SYSTEM (GAS HEAT) SAFETY CONTROLS The control circuit includes the following safety controls: The following sequence describes the operation of the gas heat 1. Limit Control (LS). This control is located inside the heat section. exchanger compartment and is set to open at the temperature indicated in Table 9.
  • Page 14: Start-Up

    511.17-N2W START-UP OPERATING INSTRUCTIONS 1. Remove the cap on the regulator. It’s located next to the push-on electrical terminals. CAUTION: This furnace is equipped with an intermittent pilot and automatic re-ignition system. DO NOT attempt 2. To decrease the gas pressure, turn the adjusting screw to manually light the pilot.
  • Page 15: Checking Supply Air Cfm

    511.17-N2W Adjust burner shutters so no yellow flame is observed in the 2. Insert at least 8" of 1/4 inch tubing into each of these holes heat exchanger tubes. Refer to Figure 14. for sufficient penetration into the air flow on both sides of the evaporator (or indoor) coil.
  • Page 16: Adjustment Of Temperature Rise

    511.17-N2W ADJUSTMENT OF TEMPERATURE RISE NOTE To find the Btu input, multiply the number of cubic feet of gas consumed per hour by the Btu content of the gas in The temperature rise (or temperature difference between the your particular locality (contact your gas company for this return air and the heated air from the furnace) must lie within information - it varies widely from city to city.) the range shown on the U.L.
  • Page 17: Normal Maintenance

    511.17-N2W MAINTENANCE NORMAL MAINTENANCE CLEANING FLUE PASSAGES AND HEATING ELEMENTS CAUTION: Prior to any of the following maintenance proce- dures, shut off all power to the unit to prevent With proper combustion adjustment the heating element of a personal injury. gas fired furnace will seldom need cleaning.
  • Page 18: Troubleshooting

    511.17-N2W TROUBLESHOOTING WARNING: Troubleshooting of components necessarily re- b. If the motor shell is cold with the room thermostat calling quires opening the electrical control box with the for heat, check for line voltage at the motor’s Mate-N- power connected to the unit. Use extreme care Lok connector attached to the evaporator partition.
  • Page 19: Replacement Parts

    511.17-N2W d. If 24 volts is present, remove the pilot burner and the high tension wire for good electrical connection. If remove the pilot orifice from the pilot burner. The orifice all are intact, replace the ignitor module. is removed in the direction opposite the flow of gas. 7.
  • Page 20 Subject to change without notice. Printed in U.S.A. Copyright © by Unitary Products Group 19958 All rights reserved. Code: EBL, F 511.17-N2W Post Office York Unitary Box 1592 Pennsylvania Products Group 17405-1592...