  • Page 1 RAPID SHUTDOWN COMBINER Installation and Operation Guide Revision B © 2017, Yaskawa – Solectria Solar...
  • Page 2: Important Safety Instructions

    SAVE THESE INSTRUCTIONS 1. General Safety Information This manual contains important instructions for Solectria’s Rapid Shutdown (RSD) Combiner that should be followed during installation and maintenance of the combiner. To reduce the risk of electrical shock, and to ensure the safe installation and operation of the Solectria RSD Combiner, follow these instructions.
  • Page 3 Rapid Shutdown Combiner The Solectria RSD Combiner provides an automatic disconnect of 600 VDC residential or small commercial PV array systems, fully compliant with the Rapid Shutdown requirements of NEC 2014 article 690.12 when installed appropriately. It is compatible with Solectria’s single-phase residential inverters: PVI 3800TL, PVI 5200TL, PVI 6600TL, and PVI 7600TL.
  • Page 4 PVI 3800-7600TL Rapid Shutdown Combiner Installation and Operation Guide (Rev B) SOLECTRIA RAPID SHUTDOWN COMBINER ON ROOF WITHIN 10’ OF PV Example 1: 2 strings of 260W modules, 12 modules per string and a PVI 5200TL using both MPPT zones (1 string per RSD input).
  • Page 5 RSD Combiner, ensuring there is no high voltage DC between the inverter and the RSD Combiner. The PV system with rapid shutdown ability shall be properly labeled according to NEC 690.56 (C). The sign/label should be right at the service entrance and match the sample below (text and color scheme).
  • Page 6: Technical Specifications

    PVI 3800-7600TL Rapid Shutdown Combiner Installation and Operation Guide (Rev B) Technical Specifications INPUT RATINGS Max. system voltage 600V DC Max. Number of input circuits Rated input current per string 10A DC Fuse rating OUTPUT RATINGS Max. Number of output circuits...
  • Page 7: Quick Install Guide

    PVI 3800-7600TL Rapid Shutdown Combiner Installation and Operation Guide (Rev B) Dimensions of the RSD Combiner Fig.3 Dimensions of SOLECTRIA RSD Combiner Quick Install Guide  WARNING - Do not connect Solectria RSD Combiner to PV string before completing all installation and DC output connection. Once connected to PV string, the RSD Combiner will wake up immediately.
  • Page 8 PVI 3800-7600TL Rapid Shutdown Combiner Installation and Operation Guide (Rev B)  DANGER -To ensure maximum protection against hazardous voltages while assembling PV installations, both the positive and the negative conductors must be strictly isolated electrically from ground as well as each other.
  • Page 9 PVI 3800-7600TL Rapid Shutdown Combiner Installation and Operation Guide (Rev B)  NOTICE - Using a power screwdriver to tighten the mounting hardware is not recommended due to the risk of thread galling.  Check that the RSD Combiner is mounted securely on the PV racking.
  • Page 10  CAUTION - The rapid shutdown signal wire may be routed together with the DC output cables in the same conduit, but all the cables shall be listed and rated 600 V and use Class 1 wiring methods. Always check with the local AHJ.
  • Page 11 PVI 3800-7600TL Rapid Shutdown Combiner Installation and Operation Guide (Rev B) Connect DC wire to the DC wiring board And connect 5V signal wire to the AC wiring board of Solectria single-phase PV inverter Note: Redundant wiring is shown for 5V signal wire Fig.6 Terminal Wiring Diagram of Solectria RSD Combiner...
  • Page 12: Product Warranty And Rma Policy

    PVI 3800-7600TL Rapid Shutdown Combiner Installation and Operation Guide (Rev B) PV array string input connections  Finally, directly connect the PV strings to the inputs of the RSD Combiner via standard MC-4 style, Ampenol Helios H4 PV or equivalent connectors.
  • Page 13 PVI 3800-7600TL Rapid Shutdown Combiner Installation and Operation Guide (Rev B) Appendix A – Rapid Shutdown Combiner Data Sheet https://solectria.com/support/documentation/inverter-datasheets/rapid- shutdown-combiner-option-for-pvi-3800-7600tl/ Appendix B – String Sizing Tool https://solectria.com/support/string-sizing-tool/ Appendix C – Contact Information Yaskawa – Solectria Solar 360 Merrimack Street...
  • Page 14 PVI 3800-7600TL Rapid Shutdown Combiner Installation and Operation Guide (Rev B) Appendix E – UL1741/IEEE1547 Certification Letter DOCR-070566-B...
  • Page 15 PVI 3800-7600TL Rapid Shutdown Combiner Installation and Operation Guide (Rev B) DOCR-070566-B...