Option board

Advertisement

Quick Links

L
Thank you for purchasing
ON
Always follow safety instructions to prevent accidents and potential hazards from occurring.
Safety precautions are classified into "WARNING" and "CAUTION" and their meanings are as follows:
WARNING
CAUTION
The indicated illustrations on the product and in the manual have the following meanings.
Danger may be present. Read the message and follow the instructions carefully.
Particular attention should be paid because danger of an electric shock may be present.
 Keep operating instructions handy for quick reference.
Read the operating instructions carefully to fully understand the functions of the H100 series and to use it properly
 Be cautious, when handling the CMOS components of the Option Board.
Static may lead to malfunctioning of the product.
 Turn off the inverter power, when changing the communication cable.
Otherwise, you may damage the board or a communication error may occur.
 Make sure to insert the Option Board connector to the inverter precisely.
Otherwise, you may damage the board or a communication error may occur.
 Check the parameter unit before setting up the parameter.
Otherwise, a communication error may occur.
W
Option Board.
ORKS

SAFETY PRECAUTIONS

Improper operation may result in serious personal injury or death.
Improper operation may result in slight to medium personal
injury or property damage.
CAUTION
H100LonWorksManual
.
1

Advertisement

loading

Summary of Contents for Lonworks H100

  • Page 1: Safety Precautions

     Keep operating instructions handy for quick reference.  Read the operating instructions carefully to fully understand the functions of the H100 series and to use it properly CAUTION  Be cautious, when handling the CMOS components of the Option Board.
  • Page 2: Included Items

    1.1 About the LonWorks (Local Operating Network) Platform The LonWorks is a networking platform created by Echelon Corporation, which is widely utilized in the field of building automation. On a LonWorks network, all the devices connected to the network nodes can freely communicate with each other using the LoneTalk protocol.
  • Page 3: Technical Data

    H100LonWorksManual 2. About The H100 Lon Works Communication Module 2.1 Technical Data Items Description Power supply to the H100 LonWorks Power Power is supplied by the inverter(s) communication module Free Topology Network Topology (Bus, Star, Loop, or any combination of these 3 types)
  • Page 4 H100LonWorksManual 2.2 Device Layout Connector to Connector the Inverter (to Inverter) -CPU Operation -Error -Service -COM DIP Switch Communication Terminal resistance Connector (A, B, S) -Service Pin Configuration...
  • Page 5 Turn off the power to the inverter before installation and network connection. Installing or removing the communication module while the power is on may damage the inverter or the LonWorks communication module. Make sure that the inverter is fully discharged before installing or removing the H100 LonWorks communication Module.
  • Page 6 H100LonWorksManual ■ Install the H100 LonWorks communication module (4) into the connector on the I/O board. ■ Secure the communication module with the 2 screws supplied with the device.
  • Page 7 H100LonWorksManual ■ Replace the top cover (5), then the keypad (6). ■ Replace the power terminal block cover (7). The inverter is now ready for use.
  • Page 8: Configuring A Network

    Appropriate network termination is required to guarantee data reliability and to reduce noise. The H100 LonWorks communication module has built-in terminal resistance. Therefore, network termination can be made by simply turning on the termination switch. For a bus network, turn on the termination switch of the H100 LonWorks communication modules at both ends.
  • Page 9 For use with a bus topology 100Ω terminal resistance Terminate two modules at the ends of the network. ③ BUS ① NO ② FT Bus Topology Free Topology Ω Ω (100 <Termination Switch Configuration for the H100 LonWorks communication module>...
  • Page 10: Installation Guidelines

    11. Turn off the power to the H100 inverter and wait for 5 minutes until the DC link voltage discharges. Replace the inverter covers. The installation process is finished. Turn the power on to the H100 inverter, and then configure the device using the network tool.
  • Page 11 H100LonWorksManual 2.7 Maximum Ranges for Different Network Cables As shown in the following table, the maximum ranges of a network are limited based on the topology and the type of cables used. Reliable network communication cannot be guaranteed beyond the maximum ranges listed in the table. BUS Topology Cable Type Maximum Bus Length...
  • Page 12: Inverter Parameters

    H100LonWorksManual 3. Inverter Parameters 3.1 Table of Parameters Code Parameter Name Default Value Settings CNF-30 Option-1 Type 0. Keypad 1. Fx/Rx-1 2. Fx/Rx-2 DRV-06 Cmd Source 1.Fx/Rx-1 3. Int 485 4. FieldBus 5.Time Event 0. Keypad-1 1. Keypad-2 2. V1 4.
  • Page 13 H100LonWorksManual Code Parameter Name Default Value Settings IN-65–71 P1–P7 Define 17. 2ndSource COM-06 FBus S/W Ver COM-09 FBus LED COM-10 Opt Parameter1 COM-11 Opt Parameter2 COM-12 Opt Parameter3 COM-13 Opt Parameter4 COM-14 Opt Parameter5 COM-31 Para Status-1 0x000A 0–0xFFFF COM-32 Para Status-2 0x000E 0–0xFFFF...
  • Page 14 Freq Ref Src This parameter is used to select a frequency reference. To provide a frequency reference using the LonWorks communication, set DRV-07 Freq Ref Src to ‘7.Fieldbus.’ 3.2.4 Secondary Command Source Options (for switching between two different command sources)
  • Page 15 H100LonWorksManual This parameter is used to display the version information about the Lon Works communication module that is installed in the inverter. 3.2.6 Communication Module LED Status Display– FbusLED (COM-9) This parameter is used to display the status of the four LEDs (CPU, Error, Service, and COM) of the communication module on the inverter keypad.
  • Page 16 Opt Parameter5 This parameter is used to enable the service pin feature without using the service pin switch on the LonWorks communication module. Set COM-14 Service Pin Enable to ‘1’ to enable the service pin feature. This allows the Lon Works communication module to send its Neuron ID and Program ID to the network.
  • Page 17 Dec Time DRV-18 Base Frequency DRV-19 Start Frequency DRV-20 Max Frequency BAS-11 Pole Number Note After commissioning the H100 Lon Works communication module, COM-94 Comm Update must be set to ‘Yes’ to apply the inverter’s configuration properties configured using the keypad.
  • Page 18 H100LonWorksManual 3.2.13 Operation Options for a Lost Command– Lost Cmd Mode (PRT-12) DRV-06 Cmd Source DRV-07 Freq Ref Src PRT-12 Lost Cmd Mode PRT-13 Lost Cmd Time PRT-14 Lost Preset F This parameter is used to select an operation mode to be used when the command is lost. When remote command via network is lost for the ‘lost command decision time’, the inverter decides that the command is lost.
  • Page 19 H100LonWorksManual 3.2.14 Lost Command Decision Time– Lost Cmd Time (PRT-13) DRV-06 Cmd Source DRV-07 Freq Ref Src PRT-12 Lost Cmd Mode PRT-13 Lost Cmd Time This parameter is used to set the time the inverter takes to decide that the command is lost. When the remote command via network is lost for the lost command decision time (PRT-13 Lost Cmd Time + the time set at nciRdvHrtBt), the inverter decides that the command is lost.
  • Page 20: Functional Profile

    H100LonWorksManual 4. Functional Profile 4.1 Node Object Input Network Output Network Variable Variable Node Object Mandatory nviRequest nvoStatus Network SNVT_obj_request SNVT_obj_state Variables Network Input Variables Function Variable Name SNVT Type Node Object Request nviRequest SNVT_obj_request 4.1.1 ‘nviRequest’ Variable The ‘nviRequest’input variable enables or updates the command inputs from a network. This input variable supports RQ_ENABLE, RQ_DISABLE, RQ_CLEAR_ALARM, RQ_NORMAL, RQ_CLEAR_STATUS, RQ_UPDATE_STATUS, RQ_REPORT_MASK.
  • Page 21 H100LonWorksManual 4.2 Drive Object Input Network Output Network Variable Speed Motor Variable Variable Drive (6010) Mandatory nviDrvSpeedStpt nvoDrvSpeed Network SNVT_switch SNVT_lev_percent Variables nvoDrvCurrent SNVT_amp nviDrvSpeedScale nvoDrvVolt Optional SNVT_lev_percent SNVT_volt Network Variables nvoDrvPwr SNVT_power_kilo nvoDrvRunHours SNVT_time_hour Configuration Properties nc17 nciLocation (Optional) nc50 nciMaxSpeed (Mandatory) nc53 nciMinSpeed (Mandatory) nc48 nciRcvHrtBt (Optional)
  • Page 22 H100LonWorksManual Network Input Variables Function Variable Name SNVT Type Drive Speed Setpoint nviDrvSpeedStpt SNVT_switch Drive Speed SetpointScaling nviDrvSpeedScale SNVT_lev_percent -163.840% 163.830% 4.2.1 ‘nviDrvSpeedStpt’ and ‘nviDrvSpeedScale’ Variables Definition Network input SNVT_switch nviDrivSpeedStpt Network input SNVT_lev_percent nviDrvSpeedScale Description Variables ‘nviDrvSpeedStpt’ and ‘nviDrvSpeedScale’ are used for run commands and speed references. The state variable value for ‘nviDrvSpeedStpt’...
  • Page 23 In the communication (COMM) group, set DRV-06 Cmd Source to ‘FieldBus’ and DRV-07 Freq Ref Src to ‘FieldBus’ using the keypad. These settings configure the inverter to receive run commands and frequency references from the LonWorks communication. Code Number/ Code Description...
  • Page 24 H100LonWorksManual Inverter Parameters Related to the ‘nviDrvSpeedStpt’ and ‘nviDrvSpeedScale’ Variables Code Number/ Code Description Default Range Common Area Address 0x0005 Frequency Command 0.00 Hz 0.00 – 400.00 0x0006 Run Command Refer to the ‘Common Area’ section. DRV-18 Base Frequency 60.00 Hz 30.00–400.00 Note Network variables ‘nviDrivSpeedStpt’...
  • Page 25 H100LonWorksManual Inverter Parameters Related to the ‘nvoDrvSpeed’ Variable Code Number/ Code Description Default Range Common Area Address 0x000A Output Frequency 0x000E Status of Inverter(FWD, REV) DRV-18 Base Frequency 60.00 Hz 30.00–400.00 4.2.4 ‘nvoDrvCurnt’ Variable Definition Network output SNVT_amp nvoDrvCurnt Description The ‘nvoDrvCurnt’...
  • Page 26 H100LonWorksManual Inverter Parameters Related to the ‘nvoDrvVoltCurnt’ Variable Code Number/ Code Description Common Area Address 0x000B Output Voltage 4.2.6’nvoDrvPwr’ Variable Definition Network output SNVT_power_kilo nvoDrvPwr Description The ‘nvoDrvPwrNetWork’ variable is used to output the inverter’s power output in kilowatts (kW). Typical Range 0.0 –...
  • Page 27 H100LonWorksManual Optional/ Function Variable Name SNVT Type Mandatory Location Label nciLocation Optional SCPTlocation Maximum Motor Speed nciMaxSpeed Mandatory SCPTmaxSetpoint Minimum Motor Speed nciMinSpeed Mandatory SCPTminSetpoint Receive Heartbeat Time nciRcvHrtBt Optional SCPTmaxRcvTime Send Heartbeat Time nciSndHrtBt Mandatory SCPTmaxSndTime Minimum Send Time nciMinOutTm Optional SCPTMinOutTime...
  • Page 28 H100LonWorksManual 4.2.8 Location Label (Optional) Definition Network config input SNVT_str_asc nciLocation Description The ‘nciLocation’ variable is used to obtain the physical location information (6 byte location string) from the neuron chip. Default Empty spaces 4.2.9 Maximum Motor Speed (Mandatory) Definition Network config input SNVT_lev_percent nciMaxSpeed Description...
  • Page 29 H100LonWorksManual Inverter Parameters Related to the ‘nciMaxSpeed’ VariableI Code Number/ Code Description Default Range Common Area Address DRV-18 Base Frequency 60.00 Hz 30.00 – 400.00 DRV-20 Max Frequency 60.00 Hz 40.00 – 400.00 4.2.10 Minimum Motor Speed (Mandatory) Definition Network config input SNVT_lev_percent nciMinSpeed Description The ‘nciMinSpeed’...
  • Page 30 H100LonWorksManual Inverter Parameters Related to the ‘nciMaxSpeed’ Variable Code Number/ Code Description Default Range Common Area Address DRV-18 Base Frequency 60.00 Hz 30.00 – 400.00 DRV-20 Start Frequency 0.50 Hz 0.01–10.00 4.2.11 Receive Heart Beat Time (Optional) Definition Network config input SNVT_time_sec nciRcvHrtBt Description The ‘nciRcvHrtBt’...
  • Page 31 0.1–120.0sec Caution When the LonWorks network is used as a command source, the inverter’s lost command time becomes the time set at ‘nciRcvHrtBt’ and PRT-13Lost Cmd Time added together. However, if the ‘nciRcvHrBt’ variable is set to 0.0 sec, the...
  • Page 32 H100LonWorksManual 4.2.12 Send Heart Beat Time (Mandatory) Definition Network config input SNVT_time_sec nciSndHrtBt Description The ‘nciSndHrtBt’ variable is used to configure the time it takes to perform a data update on the network, regardless of the presence of changes in the data. The ‘nciSndHrtBt’...
  • Page 33 H100LonWorksManual converted back to Hertz (Hz) is reflected in DRV-18 Base Freq. The following formula converts an RPM value into Hertz (Hz). In this formula, the number of motor poles is set at M2- 10 Pole Num. The motor pole number must be configured correctly to ensure proper operation. ...
  • Page 34 H100LonWorksManual Valid Range 30.0–400.0 (0.1 Hz) Default 60.0 Hz Inverter Parameters Related to the ‘nciNmlFreq’ Variable Code Number/ Code Description Default Range Common Area Address DRV-18 Base Frequency 60.00 Hz 30.00 – 400.00 4.2.16 Minimum Ramp Up Time (Mandatory) Definition Network config input SNVT_time_sec nciRampUpTm Description...
  • Page 35 H100LonWorksManual Inverter Parameters Related to the ‘nciRampDownTm’ Variable Code Number/ Code Description Default Range Common Area Address 0x0008 Dec Time (Deceleration time) 30.0 sec 0.0 – 600.0 DRV-04 4.2.18 Default for nviDrvSpeedScale (Optional) Definition Network config input SNVT_lev_percentnciDrvSpeedScale Description The ‘nciDrvSpeedScale’ value is used as the default value of the network output variable ‘nviDrvSpeedScale.’ Valid Range -163.840–...
  • Page 36 H100LonWorksManual place, and the ‘nciNmlFreq’ value is 50 Hz. 49.99 1,500RPM (1,499.7) 60.0 120.000% 0 50.0 10.0 20.00% 0 50.0 The ‘nciNmlFreq’ values must be used in the formula for the base frequency values. The maximum frequency (MaxFreq) value cannot be set higher than 163.830% of the base frequency (Base Freq). Therefore, the maximum value of the ‘nciMaxSpeed’...
  • Page 37 H100LonWorksManual 4.2 User Object (User Function Profile Type) Input Network User Object(20001) Output Network Variable Variable nvoUsrParaState1 nviUsrParaCtrl1 SNVT_count SNVT_count nvoUsrParaState2 nviUsrParaCtrl2 nv10 SNVT_count SNVT_count nvoUsrParaState3 nviUsrParaCtrl3 nv11 SNVT_count SNVT_count nviUsrParaCtrl4 nvoUsrParaState4 nv12 SNVT_count SNVT_count Mandatory Network Variables nviUsrParaCtrl5 nvoUsrParaState5 nv13 SNVT_count SNVT_count...
  • Page 38 H100LonWorksManual Network Input Variables Function Variable Name SNVT Type Min. Max. User Parameter Control1 nviUsrParaCtrl1 SNVT_count 65535 User Parameter Control2 nviUsrParaCtrl2 SNVT_count 65535 User Parameter Control3 nviUsrParaCtrl3 SNVT_count 65535 User Parameter Control4 nviUsrParaCtrl4 SNVT_count 65535 User Parameter Control5 nviUsrParaCtrl5 SNVT_count 65535 User Parameter Control6 nviUsrParaCtrl6...
  • Page 39 H100LonWorksManual Inverter Parameters Related to the ‘nviUsrParaCtrl1– nviUsrParaCtrl8’ Variables Code Number/ Code Description Default Range Common Area Address COM-50 User Parameter Control Number 0–8 COM-51 User Parameter Control 1 0x0005 0–0xFFFF COM-52 User Parameter Control 2 0x0006 0–0xFFFF COM-53 User Parameter Control 3 0x0000 0–0xFFFF COM-54...
  • Page 40 0x0000 0–0xFFFF Note When the inverter is used on a LonWorks network, COM-30 User Parameter Control Number is automatically set to ‘8’. If the user sets COM-30 to any other value from the Keypad, it automatically reverts back to ‘8.’...
  • Page 41 H100LonWorksManual Network Configuration Variable Optional/ Feature Variable Name SNVT Type Mandatory Receive Heartbeat Time for User Object nciUsrRcvHrtBt Optional SCPTmaxRcvTime Send Heartbeat Time for User Object nciUsrSndHrtBt Optional SCPTmaxSndTime Minimum Send Time for User Object nciUsrMinOutTm Optional SCPTMinOutTime 4.3.3 Receive Heart Beat Time for User Object (Mandatory) Definition Network config input SNVT_time_sec nciUsrRcvHrtBt...
  • Page 42 0.1–120.0sec Note When the LonWorks network is used as a command source, the inverter’s lost command time becomes the time set for the ‘nciUsrRcvHrtBt’ and PRT-13 Lost Cmd Time added together. However, if the ‘nciRcvHrBt’ variable is set to 0.0 sec, the lost command protection feature is disabled.
  • Page 43 H100LonWorksManual 4.3.5 Minimum Out Time for User Object (Mandatory) Definition Network config input SNVT_time_sec nciUsrMinOUtTm Description The ‘nciUsrMinOUtTm’ variable is used to configure the minimum wait time before the network output variables ‘nvoUsrParaState1–nvoUsrParaState8’ are sent to the network. Rather than reflecting the changes in the variables each time they are made, a network update is performed when a set period of ‘nciUsrMinOutTm’...
  • Page 44: Led Information

    H100LonWorksManual 5. LED Information The H100LonWorkscommunication module has four LEDs that indicate the current operation status of the communication module. The following list shows the LED indicators on the H100 LonWorks communication module. CPU (Green) ERROR (Red) Service (Green) COMM (Green)