Paul santos 570 DC Operating Manual

Heat recovery unit
Table of Contents

Advertisement

Heat Recovery Unit
santos (F) 570 DC
Status: 05.10
Design version:
R – Right (supply air)
L – Left (supply air)
Paul Wärmerückgewinnung GmbH
August-Horch-Straße 7
08141 Reinsdorf
Germany
Tel.: +49 (0)375 - 303505 - 0
Fax: +49 (0)375 - 303505 - 55

Advertisement

Table of Contents
loading

Summary of Contents for Paul santos 570 DC

  • Page 1 (F) 570 DC Status: 05.10 Design version: R – Right (supply air) L – Left (supply air) Paul Wärmerückgewinnung GmbH August-Horch-Straße 7 08141 Reinsdorf Germany Tel.: +49 (0)375 - 303505 - 0 Fax: +49 (0)375 - 303505 - 55...
  • Page 2 All rights reserved. This operating manual has been produced with the greatest care and attention. Nevertheless, the publisher accepts no liability for damage resulting from missing or incorrect information in this operating manual.
  • Page 3: Table Of Contents

    Table of Contents FOREWORD INTRODuCTION ............................. 1 CE Symbol ........................... 1 Warranty and Liability ......................... 1 1.2.1 General Information ......................1 1.2.2 Warranty Terms ......................... 1 1.2.3 Liability ..........................1 Safety 2 1.3.1 Safety Regulations ......................2 1.3.2 Safety Provisions and Safety Measures ................2 1.3.3 Symbols Used ........................
  • Page 4 3.10.2 Overview of Malfunctions ....................... 26 3.10.3 Malfunctions (or Problems) not Displayed ................30 3.11 Wiring Diagram: santos 570 DC – LEFT-HAND Version ..............31 3.12 Wiring Diagram: santos 570 DC – RIGHT-HAND Version............... 32 Commissioning and Acceptance Certificate .................. 34 Checklist A user/Owner Maintenance ....................
  • Page 5: Foreword

    Due to ongoing further development of work. Claims made under warranty shall only be ac- the unit it is possible that your santos 570 DC may cepted for material defects and/or manufacturing differ slightly from the unit described in this manual.
  • Page 6: Safety

    Safety 1.3.2 Safety Devices and Safety Measures • The santos cannot be opened without using tools. 1.3.1 Safety Regulations • It must not be possible to touch the fans with Observe the safety regulations given in this operat- your hand. For that reason air ducts must be ing manual at all times.
  • Page 7: Instructions For The User

    2 Instructions for the user This chapter describes how you should use the santos. Congratulations, you are now the own- er of a santos 570 DC, a heat recovery unit built by Paul Wärmerückgewinnung GmbH. We wish you the highest levels of com- fort.
  • Page 8: Input

    2.1.6 0-10 V Input Available Operating Aids The santos is equipped with four 0-10 V inputs. It It is possible to equip the santos with the following is possible to connect a variety of different controls operating aids: and sensors to these inputs. Several possible ex- •...
  • Page 9: 3-Position Switch

    Accessing menus Operating Display Description quence keys MENU Time delay values Status display Status display 2.2.3 Forced Ventilation with Bathroom Settings example Switch Deactivation delay bathroom setting A bathroom switch can be used to temporarily set the highest ventilation level available on the san- Operating Display Description...
  • Page 10: Touchscreen

    2.2.5 Touchscreen 2.2.6 Membrane Keypad The santos can be operated via a digital touch- The santos can also be operated via membrane screen that you are able to order separately. keypad that you are able to order separately. The The touchscreen is mounted on the wall in the living membrane keypad is mounted on the wall in the liv- room from where it communicates with the santos.
  • Page 11: P Menus For The User

    2.3 P Menus for the user Menu P1 Status of function control settings Status Sub- Description Activated menu Menu 21 currently active? Yes (1) / No (0) Menu 22 currently active? Yes (1) / No (0) Menu 23 currently active? Yes (1) / No (0) Menu 24 currently active? Yes (1) / No (0)
  • Page 12: Service By The User

    Time delay values Sub-menu Description Mini- Maxi- Stand- 1 Min. 20 Min. 10 Min. 1 Min. 120 Min. 30 Min. Forced ventilation time. 0 Min. 120 Min. 30 Min. • When is pressed for MORE " " than two seconds the santos switches to the highest ventilation level for 'n' minutes before switch- ing back automatically to the pre-...
  • Page 13: Cleaning Valves (In The Home)

    For replacement ... 2.4.2 Cleaning Valves (in the home) The valves must be cleaned (at least) twice a 1. Press OK (display on unit) or " " for at year. least four seconds (key on keypad), until Remove the valve from the wall or ceiling; the filter warning message is cleared.
  • Page 14: What To Do If A Malfunction Occurs

    DIN 1946-6 specifies that apart from rea- sons of maintenance and repairs ventila- tion systems must be operated continu- ally. When the home is unoccupied the system should be operated at the lowest ventilation level (level 1 set with 3-posi- tion switch, level "Absent"...
  • Page 15: Configuring The Santos

    3 Instructions for the Installer Observe the instructions contained in this chapter when installing the santos. Configuring the santos The standard version of the santos consists of the following components: • Outer casing (A) made of coated sheet steel; • Inner lining (B) made of high-quality expanded polypropylene (E)PP;...
  • Page 16: Technical Specifications

    Technical Specifications santos 570 DC nL (normal air volume) Level Ventilation rate Value 50 m3/h at 7 Pa 13 W bsent 150 m3/h at 23 Pa 27 W 250 m3/h at 77 Pa 68 W ediuM 450 m3/h at 323 Pa...
  • Page 17: Dimension Sketch

    Dimension Sketch System Functions...
  • Page 18: Conditions For Installation

    The scope of supply includes: • Santos 570 DC; ducting, use only air ducting material from Paul Check the identification plate to ensure it is the Wärmerückgewinnung GmbH. correct unit type. •...
  • Page 19: Connecting The Condensation Drain

    To prevent unnecessary temperature losses in both summer and winter we recommend you in- sulate the supply and exhaust air ductwork with thermal, vapour-tight insulation. Extract air santos 570 DC - RIGHT Exhaust air Supply air Intake air santos - left...
  • Page 20: Commissioning The Santos

    MENU MENU MENU Call up menu MENU MENU Ensure that the water seal connected to the Down domestic wastewater system is always filled Supply air off Exhaust air and with water. supply air on (LED green) (LED green) Ensure that the hose end terminates at least 60 mm below the water level.
  • Page 21 Menu P3 ¨ Set ventilation controls Values for ventilation controls Sub-menu Description Minimum Maximum Standard Power (in %) of the exhaust air fan 0% or 15% Normal / High for the "a ". 15% / 15% level bsent The power (in %) of the exhaust air Normal / High "l ".
  • Page 22: P Menus For The Installer

    3.7.2 P Menus for the Installer Menu P5 ¨ Setting additional control functions Values for additional control functions Sub-menu Description Minimum Maximum Standard Activating the 0 (= No) 1 (= Yes) fireplace control. Indicate presence of a 0 (= No) 1 (= Yes) frost protection device.
  • Page 23 Values for additional control functions Sub-menu Description Minimum Maximum Standard Indicate the presence of the en- 0 (= No) 2 (= Yes) thalpy exchanger. • 0; No enthalpy exchanger fitted • 1; Enthalpy exchanger with RH sensor • 2; Enthalpy exchanger without RH sensor Note: It is not possible to connect an RH sensor to the santos unit.
  • Page 24 Restore factory settings • Press " " for 5 seconds on the membrane keyboard to per- form a complete reset. This action will restore the original factory settings. Note: After a complete reset of the santos a message prompts you to re-enter the settings for "nL / HL" (see P56) and "Li / Re"...
  • Page 25 Values (malfunction) information Sub-menu Description Minimum Maximum Standard Min. setting analogue input 2 Highest setting analogue input 2 0=positive analogue input 2 1=negative setting analogue input 2 Read out analogue input 2 Analogue input 3 0=absent 1=present 0=Open loop 1 =Closed loop (analogue input 3) Setpoint analogue input 3 (closed loop)
  • Page 26: Setting Air Specifications

    Setting Air Specifications The santos unit must be set up following installation. These can be undertaken using santos air specifi- When in the setting mode the bypass valve cations shown above. damper and the frost protection device al- ways remain closed. The santos automati- The standard nL settings for the santos are as fol- cally switches off the setting mode after 30 lows:...
  • Page 27: Inspecting The Heat Exchanger And Fans

    deviations are in the plus range. If the majority 3.9.1 Inspecting the Heat Exchanger and Fans of the deviations are in the minus range, adapt all the deviations so that they are all in the mi- Check the condensation drain, the fans and nus range.
  • Page 28 7. Remove the heat exchanger (G) from the drain plate (H). There may still be water in the heat ex- Use a soft brush to clean the fan impel- changer! lers. 8. Clean the heat exchanger, if necessary. Remove dust using a vacuum cleaner. Cleaning the counter flow heat exchanger: –...
  • Page 29: Cleaning The Filters Of Units Equipped With A Frost Protection Device

    3.9.2 Cleaning the Filters of units 3.10.1 Malfunction messages displayed Equipped with a Frost Protection There follows an overview of the malfunction messages that are shown on the display of the Device digital control panel. The filter of the frost protection device Code Description (if installed) must be cleaned every 4...
  • Page 30: Overview Of Malfunctions

    3.10.2 Overview of Malfunctions The graphic below offers an overview of the messages described above that can be viewed on the display of the digital control panel in the event of a malfunction. ’FiL‘ ’tEr’ on the display and/or FilterI on the keypad display Press OK until no longer displayed...
  • Page 31 WARNING! santos turned off Danger of death from via an external contact live components – do not touch the PCB! Cause lies with unit connected to santos: check the connected unit. A1 / A2 / A3 / A4 Temperature WARNING! Malfunction temperature sensor Resistance [KΩ] Danger of death from...
  • Page 32 A5 / A6 WARNING! Danger of death from Malfunction bypass motor / frost live components – protection device do not touch the PCB! Remove filters, plastic front and sealing plate Activate self-test (P76 to 1) Motor running? Isolate from mains supply Check connection on PCB;...
  • Page 33 Check frost protection device Check PCB fuse; in conjunction with cable replace cable WARNING! Malfunction Danger of death from Frost protection device too hot live components – do not touch the PCB! Remove filters, plastic front and seal Bypass damper functioning correctly in relation to frost protection device? (check with P76 to 1)
  • Page 34: Malfunctions (Or Problems) Not Displayed

    3.10.3 Malfunctions (or Problems) not Displayed This section gives an overview of the malfunctions (or problems) that are not displayed. Problem / Malfunc- Cause Check / Remedy tion All OFF Supply voltage Check the fuse on the control PCB. • If the fuse is OK the PCB is defective. No supply voltage Mains power supply has failed.
  • Page 35: Wiring Diagram: Santos 570 Dc - Left-Hand Version

    3.11 Wiring Diagram: santos 570 DC – LEFT-HAND Version Supply air BYP/PIE T1/T3 T2/T4 VENT. (N) Blue (L3) Brown (L2) Black (L1) Gray Display BYP/PIE T1/T3 T2/T4 VENT. RJ45 RS232 Bathroom switch Exhaust air Comm. Basis RS232 - PC RS232 - KFB...
  • Page 36: Wiring Diagram: Santos 570 Dc - Right-Hand Version

    3.12 Wiring Diagram: santos 570 DC – RIGHT-HAND Version Exhaust air BYP/PIE T1/T3 T2/T4 VENT. (N) Blue (L3) Brown (L2) Black (L1) Gray Display BYP/PIE T1/T3 T2/T4 VENT. RJ45 RS232 Bathroom switch Supply air Comm. Basis RS232 - PC RS232 - KFB...
  • Page 37 08141 Reinsdorf Tel.: +49(0)375 - 303505 - 0 Fax: +49(0)375 - 303505 - 55 EC Declaration of Conformity Designation of the appliance : Heat Recovery units: santos 570 DC series Conforms to the directives : Machinery Directive (2006/42/EC)) Low Voltage Directive...
  • Page 38: Commissioning And Acceptance Certificate

    Remedial action required Yes/no Confirmation note Date: ........Signature/Stamp ..................Commissioning personnel / Installer © Paul Wärmerückgewinnung GmbH • August-Horch-Straße 7 • 08141 Reinsdorf • Deutschland Tel: +49(0)375-303505-0 • Fax: +49(0)375-303505-55 • E-Mail: info@paul-lueftung.de • Internet: www.paul-lueftung.de 34 System Functions...
  • Page 39: Checklist A User/Owner Maintenance

    - Supply air temperature as specified in DIN EN 308! © Paul Wärmerückgewinnung GmbH • August-Horch-Straße 7 • 08141 Reinsdorf • Deutschland Tel: +49(0)375-303505-0 • Fax: +49(0)375-303505-55 • E-Mail: info@paul-lueftung.de • Internet: www.paul-lueftung.de System Functions...
  • Page 40: Checklist B Professional Maintenance

    Open cross-section Yes/no available? Excess air openings No structure or air-borne Yes/no noise transmission? © Paul Wärmerückgewinnung GmbH • August-Horch-Straße 7 • 08141 Reinsdorf • Deutschland Tel: +49(0)375-303505-0 • Fax: +49(0)375-303505-55 • E-Mail: info@paul-lueftung.de • Internet: www.paul-lueftung.de 36 System Functions...
  • Page 41: Air Volume Protocol

    Owner/user informed about the effect on indoor air humidity of winter and summer modes Under the Terms and Conditions of Warranty original PAUL spare parts only (e.g. filters) must be used The period of warranty begins on the date of dispatch ex works.

This manual is also suitable for:

Santos f 570 dc

Table of Contents