Installation Instructions

for use by heating contractor
Replacement of Control Console
for Vitodens 100-WB1A
Safety and Installation Requirements
Please ensure that these instructions are read and understood before commencing installation. Failure to comply with the
instructions listed below can cause product/property damage, severe personal injury, and/or loss of life.
Working on the equipment
The installation, adjustment, service,
and maintenance of this product must
be done by a licensed professional
heating contractor who is qualified and
experienced in the installation, service,
and maintenance of hot water boilers.
There are no user serviceable parts on
the boiler, burner, or control.
Remove front cover panel and expose control
C
7826 988 II CA 03/2009
Ensure main power supply to
equipment, the heating system, and all
external controls has been deactivated.
Close main gas supply valve. Take
precautions in both instances to avoid
accidental activation of power during
service work.
A
B
, Part No. 7826 987, 7826 988
D
It is not permissible to perform service
work on any component parts ensuring
safe operation of the heating system.
When replacing parts, use original
Viessmann or Viessmann approved
replacement parts.
Ensure that theVitodens 100
Service Instructions are
referenced.
1. Remove the screw at the top of
boiler
.
2. Press down on springs at bottom
of boiler
and remove the front
enclosure panel
.
3. Flip control console down
.

Advertisement

loading

Summary of Contents for Viessmann 7826 987

  • Page 1: Installation Instructions

    Installation Instructions for use by heating contractor Replacement of Control Console , Part No. 7826 987, 7826 988 for Vitodens 100-WB1A Safety and Installation Requirements Please ensure that these instructions are read and understood before commencing installation. Failure to comply with the instructions listed below can cause product/property damage, severe personal injury, and/or loss of life.
  • Page 2 Removing the control unit 1. Flip control unit down and out towards you. The control unit is held in place with a spring loaded clip A. 2. Slide unit to the left to remove. IMPORTANT The control unit has labels and stickers containing important information.
  • Page 3 Removing the control unit (continued) 6. Remove connectors. 7. Cut cable tie from the base. 8. Remove complete control console from the base (left side first).
  • Page 4 Installation 1. Install new control (starting from right side). 2. Reconnect all wiring harnesses (connectors are numbered which correspond to the numbers printed on the circuit board). 3. Use two cable ties (field supplied) to secure the harness to the control base.
  • Page 5 Installation (continued) 5. Reinstall front cover panel. 6. Verify DIP switch settings. DIP switch settings - S1 Dip switch Setting Explanation number OFF Pump is ON during call for heat. After call for heat (RT-Terminal) is satisfied pump post-purges for 12 minutes.
  • Page 6 3. Fasten with screw at the top part of the boiler. IMPORTANT Read and follow, where applicable, the safety instructions of all labels and stickers attached to boiler surfaces. Do not remove any of these instructions. Contact Viessmann if any replacement labels are required.
  • Page 7 Wiring diagram External Connections (Field Wiring)
  • Page 8 Viessmann Manufacturing Company (U.S.) Inc. Viessmann Manufacturing Company Inc. 45 Access Road 750 McMurray Road Warwick, Rhode Island • 02886 • USA Waterloo, Ontario • N2V 2G5 • Canada 1-800-288-0667 • Fax (401) 732-0590 1-800-387-7373 • Fax (519) 885-0887 www.viessmann-us.com • info@viessmann-us.com...

This manual is also suitable for:

7826 988