Graphic Operator Terminal Installation Manual Edition A, April 2017 AKI2G-CDB-MOD-12T-000 12.1” Touchscreen HMI Keep all manuals as a product component during the life span of the product. Pass all manuals to future users / owners of the product.
Page 2
Technical changes which improve the performance of the device may be made without prior notice! Printed in the United States of America. This document is the intellectual property of Kollmorgen™. All rights reserved. No part of this work may be reproduced in any form (by photocopying, microfilm or any other method) or stored, processed, copied or distributed by electronic means without the written permission of Kollmorgen™.
The Advanced Kollmorgen Interfaces works primarily in an object-oriented way, making it easy to understand and use. Configuration is carried out on a PC using the Kollmorgen Visualization Builder configuration tool. The project can then be transferred and stored in the operator panel itself.
AKI2G-CDB-MOD-12T-000 | SAFETY PRECAUTIONS SAFETY PRECAUTIONS Both the installer and the owner and/or operator of the operator panel must read and understand this installation manual. General • Read the safety precautions carefully. • Check the delivery for transportation damage. If damage is found, notify the supplier as soon as possible.
Page 6
AKI2G-CDB-MOD-12T-000 | SAFETY PRECAUTIONS • This equipment is suitable for use in Class 2 non-hazardous locations only. [Combinations of equipment in your system are subject to investigation by the local authority having jurisdiction at the time of installation]. • All devices have to be supplied by a Class 2 power supply.
AKI2G-CDB-MOD-12T-000 | SAFETY PRECAUTIONS Terminal Block Connector Wire Size AWG TQ Lb.In. 5–7 X1/X100 Phoenix connectors AWG 30–12 X1/X100 Anytek connectors AWG 24–12 X1/X100 DECA connectors AWG 24–12 • These devices are Class 2 supplied programmable controllers (industrial PCs) for the use in industrial control equipment and are intended to be (front) panel mounted (Type 12 and 4x for indoor use only).
AKI2G-CDB-MOD-12T-000 | SAFETY PRECAUTIONS • Replacing the battery incorrectly may result in explosion. Only use batteries recommended by the supplier. During the warranty period, the battery needs to be replaced by an authorized Kollmorgen service center. Dismantling and Scrapping •...
AKI2G-CDB-MOD-12T-000 | INSTALLATION INSTALLATION Space Requirements • Maximum installation plate thickness 12”: 8 mm • The following drawings show the space requirements in millimeters when installing the operator panel. The drawings are only illustrative and may be out of proportion.
AKI2G-CDB-MOD-12T-000 | INSTALLATION Installation Process The following is needed: • A Phillips/slot screwdriver 1. Unpack and check the delivery. If damage is found, notify the supplier. Note: Place the HMI panel on a stable surface during installation. Dropping the HMI panel or letting it fall may cause damage.
AKI2G-CDB-MOD-12T-000 | INSTALLATION 6. Connect the cables in the specified order, according to the drawing and steps below. Caution: • The HMI panel must be brought to ambient temperature before it is started up. If condensation forms, ensure that the HMI panel is dry before connecting it to the power outlet.
AKI2G-CDB-MOD-12T-000 | TECHNICAL DATA TECHNICAL DATA Parameter AKI2G-CDB-MOD-12T-000 Front panel, W x H x D 340 x 242 x 8 mm Cut out dimensions, W × H 324 x 226 mm Mounting depth 49 mm (149 mm including clearance) Standalone mounting VESA 75 x 75 Note: Maximum screw length for VESA mounting is 4 mm.
Page 13
AKI2G-CDB-MOD-12T-000 | TECHNICAL DATA Parameter AKI2G-CDB-MOD-12T-000 Power supply +24 V DC (18 to 32 V DC) CE: The power supply must conform with the requirements according to IEC 60950 and IEC 61558-2-4. UL and cUL: The power supply must conform with the requirements for class II power supplies.
AKI2G-CDB-MOD-12T-000 | CHEMICAL RESISTANCE CHEMICAL RESISTANCE Metal Casing The frame and casing material is powder-coated aluminum. This powder paint withstands exposure to the following chemicals without visible change: Acetic acid 10% Phosphoric acid 4% Citric acid 10% Phosphoric acid 10%...
AKI2G-CDB-MOD-12T-000 | CHEMICAL RESISTANCE Touch Screen and Overlay Material 5.2.1 Autoflex EBA 180L Autoflex EBA 180L covers the overlay surrounding the screen. Solvent Resistance Autoflex EBA 180L withstands exposure of more than 24 hours duration under DIN 42 115 Part 2 to...
AKI2G-CDB-MOD-12T-000 | CHEMICAL RESISTANCE 5.2.3 Touch Screen Protector For harsh environments and exposure to outdoor conditions, it is recommended to use a protective film to guard the touch screen from damage. This optional part can be ordered from Kollmorgen. Kollmorgen | April 2017...
AKI2G-CDB-MOD-12T-000 | OPERATOR PANEL DRAWINGS OPERATOR PANEL DRAWINGS Connectors Figure 6-1: AKI2G-CDB-MOD-12T-000 Pos. Connector Description Power supply +24 V DC (18-32 V DC) USB Host 2.0, max output current 500 mA LAN A 10/100 Base-T (shielded RJ45) LAN B 10/100 Base-T (shielded RJ45)
AKI2G-CDB-MOD-12T-000 | ADDITIONAL INSTALLATION TIPS ADDITIONAL INSTALLATION TIPS When experiencing communication problems in noisy environments or when operating close to temperature limits, the following recommendations are to be noticed. Grounding the HMI panel Door Mounting plate in the cabinet Operator panel...
AKI2G-CDB-MOD-12T-000 | ADDITIONAL INSTALLATION TIPS Ethernet Connection in the Operator Panel Industrial Ethernet RJ45 RJ45 RJ45 RJ45 Operator panel RJ45 Operator panel RJ45 Short and Operator panel unshielded Shielded RJ45 Operator panel RJ45 0.1 μF 250 V In some industrial units for Ethernet, the RJ45 contact’s shield is connected to the chassis via a capacitor, see 1 in drawing above.
AKI2G-CDB-MOD-12T-000 | ADDITIONAL INSTALLATION TIPS To Achieve Better EMC Protection • Initially, use the original cabling from Kollmorgen primarily. • Use shielded cables for RS232 communication. Use twisted pair and shielded cabling for RS422 and RS485. • • Use the cabling intended for the bus type; Ethernet, Profibus, CC-Link, CAN, Device Net etc.
AKI2G-CDB-MOD-12T-000 | ADDITIONAL INSTALLATION TIPS Ambient Temperature The maximum ambient temperature for the operator panel is provided in the specifications. The ambient temperature refers to the temperature in the device cabinet which cools the operator panel’s electronics. 50 °C inside...
AKI2G-CDB-MOD-12T-000 | ADDITIONAL INSTALLATION TIPS Safety Most of the operator panels are fed with 24 V DC. Power supply 230 V AC to 24 V DC Operator panel +24 V Power supply 230 V AC to 24 V DC Operator panel...
AKI2G-CDB-MOD-12T-000 | ADDITIONAL INSTALLATION TIPS Galvanic Isolation Internal electronics Ethernet DC/DC galvanic isolation Filter DC/AC +24 V DC 0 V (GND) 1.5 m RS422/485 RS232 The operator panel has galvanic isolation against the 24 V DC feed but no galvanic isolation between the communication ports for RS232, RS422/485 and USB.
AKI2G-CDB-MOD-12T-000 | ADDITIONAL INSTALLATION TIPS Cable and Bus Termination RS485 • If maximum transfer distance and maximum transfer speed is needed, shielded and twisted pair cable should be used. The mutual capacitance may not exceed 52.5 pF/m, and the cable area should be at least 0.25 mm...
Page 28
5. Press finger on screen again to enter the service menu. The Service Menu displays: Note: Additional information about the Service Menu options are available in the Kollmorgen Visualization Builder (KVB) online help: HMI Panel System Software/Service Menu KVB Installation Programming the AKI panels requires the KVB software to be install on a PC work station.
Page 29
If both software packages are installed on your computer, use the KAS IDE by right-clicking on the System option in the Project Explorer and select “Add HMI Device” to display a list of HMI panels that are available. Kollmorgen | April 2017...
Page 30
Additionally, the PxMM’s IP address is also transferred into the KVB project when it is opened from within the KAS IDE. To open KVB from inside the KAS IDE, double-click on the project to launch KVB. Kollmorgen | April 2017...
Page 31
Double-clicking on it will also launch KVB. In this scenario tags and the target IP address are imported into KVB but the AKI Panel selection is not made in the IDE and must be configured in KVB: Kollmorgen | April 2017...
Page 32
About KOLLMORGEN Kollmorgen is a leading provider of motion systems and components for machine builders. Through worldclass knowledge in motion, industry-leading quality and deep expertise in linking and integrating standard and custom products, Kollmorgen delivers breakthrough solutions that are unmatched in performance, reliability and ease-of-use, giving machine builders an irrefutable marketplace advantage.