- to accommodate T-bar and plasterboard ceilings. The installation of all these products is covered in the following pages. NOTE: The AIRDOR ELITE range must be installed at least 1.8 m above floor level. The maximum recommended mounting height is 3.5m.
Page 4
VISIBLE 1500 UNIT: VIEW ON BACK PLATE SHOWING MOUNTING DIMENSIONS (AND PIPE KNOCKOUT POSITIONS FOR CEILING MOUNTED (HORIZONTAL) INSTALLATIONS) WALL MOUNTED (VERTICAL) INSTALLATIONS: TOP, INLET PANEL VIEW FOR PIPE CONNECTION POSITIONS. VISIBLE 2000 UNIT: VIEW ON BACK PLATE SHOWING MOUNTING DIMENSIONS (AND PIPE KNOCKOUT POSITIONS FOR CEILING MOUNTED (HORIZONTAL) INSTALLATIONS) WALL MOUNTED (VERTICAL) INSTALLATIONS: TOP, INLET PANEL VIEW FOR PIPE CONNECTION POSITIONS.
3.1. VISIBLE INSTALLATION OPTIONS 3.1.1. HORIZONTAL INSTALLATION Installation requires a minimum of 4 suspension rods on 1000 units (6 on 1500 units) mounted securely to points in the roof space to match the mounting slot positions as in figure 1. The front access panel is held in place by tamper-proof fasteners and requires a suitably sized Allen key to un-latch (supplied).
3.2. CONCEALED INSTALLATION OPTIONS 3.2.1. T-BAR CONCEALED (VOID AND ROOM INLET INSTALLATION) Key sizes, dimensions and weight data is shown in Figure 3. Installation requires a minimum of 4 suspension rods mounted securely to points in the roof space to match the mounting slot positions as in figure 3.
Page 7
MOUNTING DIMENSIONS AND ROOM INLET PIPE CONNECTIONS: T-BAR: 1800 UNITS UNIT WEIGHT = 55Kg T-BAR: VOID INLET - SIDE PROFILE T-BAR: VOID INLET - 1200 (+ 2400) UNITS T-BAR: VOID INLET -1800 UNITS FIGURE 3. Continued QA/IOM/54 ISSUE 8...
3.2.2. PLASTERBOARD CONCEALED (VOID AND ROOM INLET INSTALLATION) Key sizes, dimensions and weight data is shown in Figure 4. Installation requires a minimum of 4 suspension rods mounted securely to points in the roof space to match the mounting slot positions as in figure 4. A single (for void inlet) or double cut-out (for room inlet) is required in the plasterboard ceiling for the inlet and outlet grilles.
Page 9
PLASTERBOARD: PLASTERBOARD: ROOM INLET - SIDE PROFILE VOID INLET - SIDE PROFILE PLASTERBOARD: VOID INLET - 1200 (+ 2400) UNITS PLASTERBOARD: VOID INLET -1800 UNITS PLASTERBOARD GRILLE APERTURE DIMENSIONS: FIGURE 4. Continued QA/IOM/54 ISSUE 8...
4. ELECTRICAL CONNECTIONS 4.1. LPHW UNITS All electrical work shall be carried out in accordance with current I.E.E. Regulations. Unit motors operate on single phase 230V/50Hz supply. Electrical connection is made to the mains terminal block located on the control plate between the fans (knock-outs in the back plate are present for cable entry – see figure 1).
5.4. CONTROL OPTIONS - ELECTRIC HEATED UNITS A high-temperature cutout and single, preset fan speed come as standard electric options. ELECTRIC OPTIONS ON/OFF thermostat with fascia dial (remote) RT 1 Energy saving thermostatic ON/OFF thermostat with tamper-proof dial (remote) TL X controls ON/OFF rocker switch (remote) RS 1R...