BrookVent AS 90-0102-WIN-01 Installation, Maintenance And User Manual

Heat recovery ventilation

Advertisement

HIGH PERFORMANCE
IN A COMPACT PACKAGE
Heat Recovery Ventilation
Installation, maintenance
& user manual
Applicable to the following aircycle 1.2 models:
PRODUCT CODE
AS 90-0102-WIN-01
AS 90-0102-WINS-01
AS 90-0102-CIN-01
AS 90-0102-CINS-01
AS 90-0102-FIN-01
AS 90-0102-FINS-01
(Product codes above refer to 'standard' system set up. Add " V " to the end of each product code for an 'inverted' system set-up
DESCRIPTION
aircycle 1.2 c/w Integral Humidistat - Wall Mount
aircycle 1.2 c/w Integral Humidistat & Summer Bypass - Wall Mount
aircycle 1.2 c/w Integral Humidistat - Ceiling Mount
aircycle 1.2 c/w Integral Humidistat & Summer Bypass - Ceiling Mount
aircycle 1.2 c/w Integral Humidistat – Floor Mount
aircycle 1.2 c/w Integral Humidistat & Summer Bypass - Floor Mount
V. 1.2-14-03-17
brookvent.co.uk

Advertisement

Table of Contents
loading

Summary of Contents for BrookVent AS 90-0102-WIN-01

  • Page 1 Installation, maintenance & user manual Applicable to the following aircycle 1.2 models: PRODUCT CODE DESCRIPTION AS 90-0102-WIN-01 aircycle 1.2 c/w Integral Humidistat - Wall Mount AS 90-0102-WINS-01 aircycle 1.2 c/w Integral Humidistat & Summer Bypass - Wall Mount AS 90-0102-CIN-01 aircycle 1.2 c/w Integral Humidistat - Ceiling Mount...
  • Page 2: Table Of Contents

    Safety ..........................4 Specifications/ Dimensions (mm) ..................6 Installation ........................11 Electrical Connections/ Wiring ..................20 Controls and Settings ......................22 Maintenance ........................27 User Operation ........................29 Trouble Shooting ....................... 31 V. 1.2-14-03-17 brookvent.co.uk www.brookvent.co.uk T: +44 (0) 28 9061 6505...
  • Page 3: Introduction

    Introduction The Brookvent aircycle 1.2 is a compact and highly efficient Mechanical Heat Recovery Ventilation (HRV/MHRV) system, specifically designed for smaller dwellings and apartments with restricted space.
  • Page 4 4 years covering parts only. In the instance of a defect, Brookvent may repair the product, replace the product free of charge or refund the cost of the product at Brookvent’s own discretion. In terms of installation, operation and maintenance please follow all instructions provided.
  • Page 5: Safety

    Never touch the appliance with wet hands.  The unit is only suitable for 230 VAC/50Hz electric mains.  Never modify the fan or electronics, all repairs must be conducted by Brookvent.  Never connect the power if electronics cover is not fitted. ...
  • Page 6 In new build properties it may be prudent to check/ change your filters after the first 3 months of occupancy depending on the amount of residual ‘building dust’ present within the property. Failure to do so will affect your warranty. Filters can be purchased directly online from brookvent.co.uk V. 1.2-14-03-17 brookvent.co.uk www.brookvent.co.uk...
  • Page 7: Specifications/ Dimensions (Mm)

    H 583mm x W 600mm x D 337mm 3.02 CEILING MOUNT L 670mm x W 600mm x D 349mm 3.03 FLOOR MOUNT L 670mm x W 600mm x D 349mm V. 1.2-14-03-17 brookvent.co.uk www.brookvent.co.uk T: +44 (0) 28 9061 6505...
  • Page 8 Fresh from Outside Fresh to Home FRONT Inverted Configuration: (Factory Set: Must be specified at time of order) Fresh from Outside Fresh to Home Extract to Outside Extract from House Outside FRONT V. 1.2-14-03-17 brookvent.co.uk www.brookvent.co.uk T: +44 (0) 28 9061 6505...
  • Page 9 Installation: Wall, Ceiling or Floor Mount Standards: Fully complies with Building Regulations for UK & Ireland SAP Appendix Q Listed | Energy Savings Trust Best Practice | CE Guarantee Period: 5 Years V. 1.2-14-03-17 brookvent.co.uk www.brookvent.co.uk T: +44 (0) 28 9061 6505...
  • Page 10 Room Variable Kitchen + 4 Wet 100 % 1.20 Room Variable Kitchen + 5 Wet 100 % 1.46 Room Variable SAP 2012 (See SAP - PCDB for further details) http://www.ncm-pcdb.org.uk/sap/ V. 1.2-14-03-17 brookvent.co.uk www.brookvent.co.uk T: +44 (0) 28 9061 6505...
  • Page 11 35.1 Open Supply 43.6 47.6 60.4 66.2 63.4 54.2 45.7 Duct Speed Open Extract 40.5 56.1 58.8 43.2 41.7 39.2 (max) Duct Breakout 36.9 35.7 57.4 60.5 52.9 45.4 40.4 V. 1.2-14-03-17 brookvent.co.uk www.brookvent.co.uk T: +44 (0) 28 9061 6505...
  • Page 12: Installation

    A clear access space is required around the unit; this will ensure ease of installation relating to ductwork, wiring, and the connection of the condensate drain. It is important that filters to the system can also be accessed for replacement. V. 1.2-14-03-17 brookvent.co.uk www.brookvent.co.uk T: +44 (0) 28 9061 6505...
  • Page 13 Mounting 4.11 WALL MOUNT The aircycle 1.2 models AS 90-0102-WIN-01, AS 90-0102-WIN-01V, AS 90-0102-WINS-01, and AS 90-0102-WINS-01V are designed for Wall Mounting only. The unit should be attached the to the wall as shown using the wall bracket provided, please ensure the mounting surface can safely bear the load of the unit using suitable screw fixings.
  • Page 14 The unit should be attached to the Ceiling as shown (Fig.1) by first fixing the bracket to the unit using the fixings provided. Fig. 1 Fig. 2 Fig. 3 Brookvent supply drainage to this point. Dry Trap (Not Incl.) must be fitted with a 10 degree fall. Trap not included. V. 1.2-14-03-17 brookvent.co.uk...
  • Page 15 No.50 – M8 x 24 Washer (Quantity: 2)  Please ensure that this method of fixing is suitable for the mounting surface and that it can safely bear the load. V. 1.2-14-03-17 brookvent.co.uk www.brookvent.co.uk T: +44 (0) 28 9061 6505...
  • Page 16 Incl.) must be fitted with a 10 degree fall. Please ensure that this method of fixing is suitable for the mounting surface and that it can safely bear the load. V. 1.2-14-03-17 brookvent.co.uk www.brookvent.co.uk T: +44 (0) 28 9061 6505...
  • Page 17 300mm and kept taut as per the Domestic Compliance Guide (Part F: Eng and Wales 2010). The spigots on the Brookvent aircycle 1.2 systems are suitable for connection to 125mm diameter round pipe. The label on top of the unit clearly identifies which spigot should be connected to which ducting route within the dwelling.
  • Page 18 The aircycle 1.2 is supplied complete with a centralised drainage connection on the bottom of the unit. Brookvent recommend the use of a 32mm “Waterless Dry Trap” on HRV systems (as shown above) to prevent the back flow of air into the HRV unit from the waste discharge system.
  • Page 19 The aircycle 1.2 Ceiling mount drainage connection is 21.5mm. Brookvent recommend the use of a 32mm “Waterless Dry Trap” on HRV systems (as shown above) to prevent the back flow of air into the HRV unit from the waste discharge system.
  • Page 20 The aircycle 1.2 Floor mount drainage connection is 21.5mm. Brookvent recommend the use of a 32mm “Waterless Dry Trap” on HRV systems (as shown above) to prevent the back flow of air into the HRV unit from the waste discharge system.
  • Page 21: Electrical Connections/ Wiring

    Black = Neutral Grey = Switch The grey switch wire is used to boost the system. When a live 230v signal is applied, the Auto Boost function will be triggered. V. 1.2-14-03-17 brookvent.co.uk www.brookvent.co.uk T: +44 (0) 28 9061 6505...
  • Page 22 5.1 Wiring Schematic V. 1.2-14-03-17 brookvent.co.uk www.brookvent.co.uk T: +44 (0) 28 9061 6505...
  • Page 23: Controls And Settings

    RHS as shown. Inverted Supply configuration systems have their Boost controls located on the LHS and are clearly labelled. Boost Over-run 0 – 15mins V. 1.2-14-03-17 brookvent.co.uk www.brookvent.co.uk T: +44 (0) 28 9061 6505...
  • Page 24 For the required airflow rates refer to the design specification for the property and or refer to Building Regulations (Part F: Means of Ventilation, England and Wales) or relevant equivalent dependent upon local guidelines. If further guidance is required on the commissioning process, please contact Brookvent directly. V. 1.2-14-03-17 brookvent.co.uk...
  • Page 25 Turn the boost switch on. Turn the Supply Boost up until the whole dwelling Boost rate i.e. 29l/s is achieved through the Supply valves. Do not adjust the valves, only adjust the control on the unit. Turn the boost switch off. V. 1.2-14-03-17 brookvent.co.uk www.brookvent.co.uk T: +44 (0) 28 9061 6505...
  • Page 26 6.4 Boost Over-Run Timer All Brookvent aircycle systems come complete with an automatic boost over-run timer of 15mins (factory set). The grey ‘switch wire’ on the aircycle 3.1 systems (See section ‘5.0 Electrical Connections/ Wiring’) is used to boost the system.
  • Page 27 6.6 Tempering Summer Bypass Feature available on selected models only (AS 90-0301-WINS-01). The Tempering Summer Bypass feature, unique to Brookvent aircycle systems, functions via thermostatically responsive solenoid which operates on a linear scale between 20 Degrees Celsius (No Summer Bypass) and 27 Degrees Celsius (Full Summer Bypass);...
  • Page 28: Maintenance

    It is recommended that the filters are checked every 6 months. Replacement filters can be purchased online at brookvent.co.uk To change the filters, simply remove the filter covers from the front of the unit, replace the filters, and replace the filter covers firmly.
  • Page 29 Fixings: Ensure that all of the unit fixings and the mounting fixings have not  become loose over time and are kept sufficiently tight. V. 1.2-14-03-17 brookvent.co.uk www.brookvent.co.uk T: +44 (0) 28 9061 6505...
  • Page 30: User Operation

    User Operation The Brookvent aircycle 1.2 is an extremely compact and highly efficient Mechanical Heat Recovery Ventilation (HRV/MHRV) system, specifically designed for smaller dwellings and apartments with restricted space. The system should be run continuously 24 hours a day, and should only be disconnected by a competent person during service or maintenance.
  • Page 31 This is typically used in sanitary accommodation and bathrooms. *The items detailed above are examples of the types of Automatic Control Options that are typically used in conjunction with the Brookvent aircycle 1.2* V. 1.2-14-03-17 brookvent.co.uk www.brookvent.co.uk...
  • Page 32: Www.brookvent.co.uk

    (Please note that the aircycle 1.2 system has a minimum boost overrun time of 15mins). *The items detailed above are examples of the types of Manual Control Options that are typically used in conjunction with the Brookvent aircycle 1.2 * V. 1.2-14-03-17 brookvent.co.uk www.brookvent.co.uk...
  • Page 33: Trouble Shooting

    Check whether the system is designed to boost from a light switch relay, if so, have any of these been left on while commissioning process is being carried out. V. 1.2-14-03-17 brookvent.co.uk www.brookvent.co.uk T: +44 (0) 28 9061 6505...
  • Page 34: Www.brookvent.co.uk

    Notes V. 1.2-14-03-17 brookvent.co.uk www.brookvent.co.uk T: +44 (0) 28 9061 6505...
  • Page 35: Www.brookvent.co.uk

    Notes V. 1.2-14-03-17 brookvent.co.uk www.brookvent.co.uk T: +44 (0) 28 9061 6505...
  • Page 36: Www.brookvent.co.uk

    Customer Support At Brookvent we pride ourselves on providing Gold Standard after sales and support to all customers. Please feel free to contact one of our specialist team about any query you may have and we will be more than happy to assist you.