are used for additional cooling and/or heating. The actual scope of delivery may differ from the information in this manual for special constructions, additional order options or as a result of recent technical changes. Active chilled beams Type DID614...
Page 3
Danger due to incorrect use! Incorrect use of the unit can lead to dangerous situations. Never use the unit: – in areas with potentially explosive atmos- pheres – in humid rooms – in rooms with aggressive or dust-laden air Active chilled beams Type DID614...
Max. operating pressure, water side 6 bar Max. operating temperature 75 °C (55 °C when using flexible connecting hoses) Minimum operating temperature 6 °C Dimensions Fig. 2: Dimensional drawing of DID614 Ⓐ 4-pipe Ⓑ 2-pipe Active chilled beams Type DID614...
Page 5
L = total length (grille), B = total width (grille) Dimensions [mm] ∅D Weight [kg] Nominal size [mm] DID614 Contained water 600 × 600 1200 × 600 1250 × 625 900 × 900 1525 × 900 Active chilled beams Type DID614...
Use only lifting and transport gear designed for the required load. Always secure the load against tip- ping and falling. Upon delivery, carefully remove the packaging and check the unit for transport damage and complete- ness. Active chilled beams Type DID614...
Fig. 4: Ceiling installation, visible T-bars ① DID614 ② Ceiling tile 598 / 623 Fig. 5: Ceiling installation with clamping profile ① DID614 ② Ceiling tile 598 / 623 Fig. 6: Ceiling installation, concealed T-bars ① DID614 ② Ceiling tile Active chilled beams Type DID614...
Page 8
Danger of death from the fall of suspended loads! – Only use fixing materials designed for the required load. – Use all hanging brackets supplied. – Stand clear of suspended loads, unless properly secured. – Check secure fixing after installation. Active chilled beams Type DID614...
Incorrect assembly will damage the heat exchanger! Always use a suitable tool to counter the tight- ening force in order to prevent any damage. Fig. 8: DID614 with 4-pipe system 2-pipe system: 2 water connections 4-pipe system: 4 water connections ...
45° to the left or right. Three different air patterns can be set. NOTICE! Incorrect handling will damage the air control blades! To avoid any damage, always use both hands to move the air control blades. Active chilled beams Type DID614...
Page 11
Commissioning Adjusting the nozzles The DID614 is fitted with adjustable twin nozzles that allow for adapting the airflow velocity to changed operating conditions at a later stage, if required. CAUTION! Hot surface! Danger of burn injuries when working on the hot water system.
Page 12
After cleaning, re-attach the safety cables, and screw-fix and close the grille. CAUTION! Danger of head injuries from the fall of the induced air grille! Check that the induced air grille and safety cables are securely fixed! Active chilled beams Type DID614...