Introduction In the event of oil leaking out due to any accidental cause at an industrial lot where a large volume of oil is handled, the most important matter is to detect its occurrence without delay and to dispose of it quickly and adequately. "Apolarm-C"...
Functional theory of “Apolarm-C” ■Detector (Fig.4-1) (a) Way of detection When all of the detecting electrodes come in contact with oil at an oil depth from 3 to 5 mm, this device functions to detect the presence of oil there. When any of the electrodes, even only one electrode, is in contact with water, no detection signal is sent out from the device.
Page 6
■ Principle and structure (Fig.4-2) Model CSR-3005E is an intrinsic safety type explosion-proof transducer. Floater has three electrodes, and high frequency current provided from its detector circuit checks the electrostatic capacity at the electrode section. When oil flows out onto water surface, the electrodes have to contact water through the oil layer, which causes their electrostatic capacity to vary largely.
Components 5-1. Detector Apolarm-C (1) Structure of Apolarm-C CSR-3005E Water-weathering structure Floater is composed of three resin moldings and their jointing faces are welded. The section through which cable is led out is double-sealed by means of grand packing and bonding agent.
Page 8
Dielectric constants and specific gravity of main oils: Table 5-1 Petroleum items Items Dielectric constant Specific gravity Crude oil 2.2 - 2.5 Naphtha Gasoline 0.76 Jet engine fuel 0.83 Kerosene 0.78 Xylene 0.87 Benzene 0.87 Toluene 0.87 A heavy oil 0.85 B heavy oil 0.89...
Table 5-2 Water Detected Spec. Viscosity Kind of oil temperature temperature oil layer Gravity (CP) (℃) (℃) (mm) Kerosene 13.5 14.0 0.796 Turbine oil 13.5 13.5 0.877 A-Heavy oil 13.5 13.5 0.846 B-Heavy oil 13.5 13.5 0.91 ― C-Heavy oil 0.925 (c) Change of detectable oil layer thickness Detectable oil layer thickness can be changed by changing electrode length (max.
Page 10
(2) Restriction on wiring length The cable that connects detector and transducer works as a kind of condenser and coil. Electric energy may accumulate in this cable and such energy may work to impair the intrinsic safety of the device. For this reason, the maximum wiring cable length is restricted under the explosion-proofing principles.
Page 11
2. Length of cable usable 2km at max with 2 mm core cable 3. Power consumption 2 VA with rated voltage (Model CSR-3005E) 4. Delay time 1~10 sec (adjustable) Fig. 5-2 Dimensions of Transducer Intrinsic safety circuit side terminal holder 3P...
5-3. Dry pit attachment In case there is no water ordinarily or there is a fear of water being emptied, dry pit attachment is used. When the water level drops, the electrode points come in contact with the contact plate of the attachment and cease to further go down. Therefore, the electrodes are earthed as are when floating on water.
Wiring and operation 6-1. Wire connection diagram "Apolarm-C" can function in 2-combined state of 1. Detector (Model CSR-3005E) and 2.Transducer (Model AS- 40E) In connecting Apolarm-C and transducer, do it correctly in accordance with Fig.6-1 Note: As regards intrinsic safety terminals PN between detector and transducer, connect the white color cable attached to detector to P and the black color cable to N.
(4) Operation Table 6-1 System trouble (APOLARM Cable Normal Oil detect short or open) APOLARM-C Pilot Lamp Model (Green) CSR-3005E Lamp Pilot Lamp Transducer (Green) Model AS-40E Pilot Lamp (Red) Oil ALARM OPEN CLOSE OPEN Contact A1-C1 Oil ALARM CLOSE...
Installation of Apolarm-C 7-1. Determination of place for installation The thickness of oil layer produced by leaked oil gets the thinner the wider the dispersed area of the oil. Therefore, it is important how to gather the leaked oil in a limited area. Gathering of oil in a small area makes easier the work of oil recovering, which leads to thwarting the mishap from expanding further.
Page 16
b) An installation example in oil separation pit ■Oil separation pit Junction box APOLARM-C Oil separation pit ① As generally the oil separation pit is filled with water. Therefore, it is unnecessary to set dry pit attachment there. When the oil pit is emptied, warning signal is send forth. ②...
Page 17
d) An installation example in large capacity pit (excessively large pit). In case of large capacities pit that usually holds water in it; prepare a detecting-use separator as shown in the bellow figure. The appropriate length & width measurements of separator is ordinarily 400 ~ 600 mm. Separator Apolarm Separator...
7-3. Cautions for installation work (1) Relation between oil layer thickness detectable and out flowing amount of oil The amount the leaked-out oil is required to reach after oil begins to leak out for the detector to start giving out oil detection signal is indicated by the following formula: Amount of leaked-out oil = (oil layer thickness detectable by detector) ×...
Page 19
A high frequency (around 1 MHz) is used inside this detector, which, therefore, may issue false signal if a transceiver or other high frequency source is nearby. Though this new Apolarm (CSR-3005E) has enhanced its immunity against external interference, do not use, as much as possible, such a transceiver, etc. near the Apolarm.
How to install Explosion-proof wiring Fig.8-1 below “recommended wiring” shows a general outline of Apolarm-C wiring. For details, please see ”User’s Guide for the Installation of Explosion-proof Electrical Equipment” Here is excerpts form the guideline which will help customer install Apolarm-C wiring. 8-1.
8-2. Wiring of intrinsically safe circuit (Guide for the Installation of Explosion-proofed Electrical Equipment 9.6) (1) When Aploarm-C cable needs to be installed near other cables, Apolarm cable must be wired independently by using metal pipe or metal duct in order to prevent power cross, static induction and electromagnetic induction.
8-6. Panel wiring at non-hazardous area (Guide for the Installation of Explosion-proofed Electrical Equipment 9.6.6.7) In the event of wiring intrinsically safe circuit inside the instrument panel in non-hazardous area, be sure to follow the instructions below. In general, the panel must have a relay box for external wiring of this relay box should be installed inside the panel.
Installation of Explosion-proofed Electrical Equipment”. Do not use any transducer other than AS-40E with Apolarm-C (CSR-3005E). *If Apolarm-C and transducer (AS-40E) do not have same registration number of the Type Certificate; please contact our dealership or ASAHI KASEI TECHNOSYSTEM CO., LTD.