Do you have a question about the GridManager and is the answer not in the manual?
Questions and answers
Summary of Contents for Solutronic Energy GridManager
Page 1
User Manual GridManager with FEED-IN function User manual GridManager with FEED-IN function MoS/MM/JK 2016-11-23 Version: A8, Subject to change without prior notice...
9 Operating status........................... 9.1 LED power.......................... 9.2 LED L1, L2, L3......................9.3 LED error......................... 10 Data connection to GridManager using SOLPLUS+............11 Parameter settings GridManager.................... 11.1 IP-address GridManager....................11.2 Total AC power of connected inverters................11.3 Minimum withdrawal from grid / Maximum feed in to the grid......
Dear Customer, Thank you for buying a GridManager with FEED-IN function designed and manufac- tured by Solutronic Energy. This manual describes how to use your GridManager with FEED-IN function. Please keep it somewhere where you have ready access to it whenever you need to.
Page 4
"Warning!" denotes a warning that, if not observed, can result in death or serious injury! Danger! "Danger!" denotes a warning that, if not observed, will result in death or serious injury! Note Useful information and tips to help you operate the GridManager to best effect. Description of the Nameplate 2/28 GM_User Manual_A8_EN...
Alternating current (alternating voltage): electrical value on the output side of the inverter Photovoltaic = Solar generator: interconnection of several solar modules to Generator form a string or a number of parallel strings GridManager with FEED-IN function GM_User Manual_A8_EN 3/28...
If you are not able to understand the language used in this documentation sufficiently, please contact and inform the supplier of the situation. Do not try to attempt to install or put the GridManager with FEED-IN function into service until you have read through all the documentation supplied thoroughly.
Prerequisites 4 Prerequisites The inverters and the GridManager should be connected in one Ethernet using a dedicated switch for this setup. Using RS485 for regulation is not possible. Abbildung Bezeichnung Beschreibung V 2.7.4 Laptop or PC death. For setting up the with SOLPLUS+ GridManager.
Mode of Operation 5 Mode of Operation The GridManager covers the power management of the inverter as a function of local consumption. It’s located between the SOLPLUS inverters and appliances; and the power meter. The typical reaction time for power regulation is 4 Milliseconds.
PV-inverter You may install either a GridManager or a PowerReductionCard, installing both at the same installation will not work. Connect appliances to the same phase as the inverter, especially if only one inverter is used.
Page 10
Installation GridManager 63 Ethemet-connection Grid-connection SLS* of building one or more 1-phase N L1 L2 L3 House distribution,fuses etc. or 3-phase inverter N L1 L2 L3 Light etc. Appliance 1-Phase *If available/required Appliance 1-Phase Note PE connections not shown! Stove...
It shall be installed between the meter (reference counter when feed in is zero or bidirectional meter when grid-feed is limited) and the local distribution for appliances and PV-inverter You may install either a GridManager or a PowerReductionCard, installing both at the same installation will not work. Installation...
Page 12
Installation GridManager 250 View from top: Connector for current transformers Ethernet 10/28 GM_User Manual_A8_EN...
8 Connecting GridManager, inverters and PC All devices are connected using a standard ethernet-switch and -cables. The GridManager itself has no display. In the first 60 seconds after starting up the GridManager uses always the IP-address 192.168.0.98. If a connection to this address is established, the GridManager will continue to use this IP-address, otherwise it will switch to the set IP-address after these 60 seconds.
Operating status 9 Operating status The operating status of GridManager is shown by LEDs. 9.1 LED power State Meaning No power or not yet initialized Everything okay Flashing slowly Internal error found or Default-communication Flashing fast Operation with default communication parameters 9.2 LED L1, L2, L3...
SOLPLUS+ and it’s manuals are available on our homepage www.solutronic-en- ergy.de. Please use the latest version available, at least the version stated in chapter 4. To setup the GridManager you’ll need the professional version of SOLPLUS+. If you need a professional key, please contact our service.
11.1 IP-address GridManager Note GridManager uses the same password mechanics as a inverter. You will need your individual password level 3 to setup the parameters. Please see the manual for password level 3 on how to get and enter a password level 3.
The 4th segment of the IP address using the format xxx.xxx.xxx. 98 To use DHCP enter 0 (zero) in all 4 parameters 110-113. The GridManager will receive a IP-address from the DHCP server. If no DHCP server is present the default IP-address 192.168.0.98 is used.
Parameter settings GridManager Parameter 392: AC total power inverter L3 Menu: Options Unit: Accuracy: Default value: 5000 W Password level: 11.3 Minimum withdrawal from grid / Maximum feed in to the grid These parameters define how much power per phase should be either...
Page 19
Parameter settings GridManager Parameter 398: Minimum removal of grid-total L2 Menu: Options Unit: Accuracy: Default setting: 100 W Password level: Parameter 399: Minimum removal of grid-total L3 Menu: Options Unit: Accuracy: Default setting: 100 W Password level: 11.3.2 Limited allowed feed in into the grid (single phases) These parameters define how much power is allowed to be fed into the grid.
Page 20
Parameter settings GridManager Parameter 397: Minimum removal of grid-total L1 Menu: Options Unit: Accuracy: Default setting: 100 W Password level: Parameter 398: Minimum removal of grid-total L2 Menu: Options Unit: Accuracy: Default setting: 100 W Password level: Parameter 399: Minimum removal of grid-total L3...
11.4.2 Defining power class for GridManager 63A and 250A This setting is usually not necessary to change, as it’s already set according to the power class of the GridManager. The value 80 or 81 defines the internal scaling of GridManager either to 63 A or 250 A.
Page 22
Parameter settings GridManager Sets the interval at which the UDP packets are sent. All (P402 + 1) * 20ms a packet is sent. That is, With the default setting of "4" a packet is sent every 100ms, with the setting "0" a packet is sent every 20ms.
12.1 Activating FEED-IN mode This parameter enables the inverter to receive regulation packets from the GridManager. This overrules the power output settings of the inverter and uses the regulation sent by GridManager Set this parameter to 64. Parameter FEED-IN operating mode...
Default value: 33010 Password-level: This port is used for receiving the control signal from the GridManager. If you change this parameter, you need to change the parameter “network port for UDP packages” on the GridManager also. Parameter: is inactive...
Parameter settings Inverter 12.4 Fallback Should the inverters not be able to recive regulation packets from the GridManager they will use this parameter to limit their output. This prevents violation of rules but reduces effectiveness. This parameter is ignored as long the inverter receives regulation packets.
3 seconds Resolution: 0,1 seconds Password level: This parameter defines the time after the last receipt of a packet from a GridManager to switch the inverter to the Power Limitation parameter. Parameter: GM UDP Timeout SE 40S2 - SE 60S2:...
Menu: yield control Unit: Resolution: This parameter indicates the number of packets received. Depending on the transmis- sion frequency of the packets from the Gridmanager, the value should be correspond- ingly increased. Parameter: performance specification SOLPLUS 25 - 55: Parameter 42...
Measurement readings GridManager 13 Measurement readings GridManager These parameters store the actual values of the GridManager. Use SOLPLUS+ to display this data.Positive values show retrieval from grid, negative values show feed in to the grid. Parameter 13: Actual value grid voltage L1...
Attachment 14 Attachment 14.1 Example GridManager active Parameterization of P466 --> SP120 Parameterization of P310 -->L1=1 Parameterization of P311 -->L2=2 Parameterization of P312 -->L3=3 L1 L2 L3 Parameterization of P318 -->FIS active SP 25-55 Parameterization of P310 -->L1=1 L1 N Parameterization of P318 -->FIS active...