Summary of Contents for Boston gear Ratiotrol P-3026-BG
Page 1
Boston Gear ® Ratiotrol ® DC Motor Speed Control Installation and Operation P-3026-BG Doc. No. 60881 VEL Series 1/6 – 1 HP VEH Series 1 – 3 HP An Altra Industrial Motion Company...
VEL100 – 1 HP 2. VEH100 – VEH500: 230VAC VEH100 – 1 HP VEH150 – 1-1/2 HP VEH200 – 2 HP VEH300 – 3 HP P-3026 • Doc. No. 60881 • Boston Gear Ratiotrol DC Motor Speed Control ® ®...
6. Speed Regulation (see Table 2) – Regulation Performance Characteristics percentages are of motor base speed under steady-state conditions. 1. Speed Range (controlled) – 0 to motor base speed P-3026 • Doc. No. 60881 • Boston Gear Ratiotrol DC Motor Speed Control ® ®...
Form C, 2 ampere (120 VAC – 28 UDC) contacts which can be used to signal audible or visual alarms, or auxiliary control devices, e.g., lubrication pumps, fans, valves. P-3026 • Doc. No. 60881 • Boston Gear Ratiotrol DC Motor Speed Control ®...
However, to prevent problems from high-energy transients and large surges, observe the following: 1. Place the controller on a feeder line separate P-3026 • Doc. No. 60881 • Boston Gear Ratiotrol DC Motor Speed Control ® ®...
See the option selection table on the controller speed. data label. 10. Turn the MOTOR SPEED potentiometer fully counterclockwise to zero and depress the STOP button. P-3026 • Doc. No. 60881 • Boston Gear Ratiotrol DC Motor Speed Control ® ®...
This center position causes a Stop function, and an antiplug circuit prevents the motor from being restarted while the motor is braking until a safe speed for reversing is attained. P-3026 • Doc. No. 60881 • Boston Gear Ratiotrol DC Motor Speed Control ®...
Overvoltage and resulting overspeed can to the Troubleshooting Table (Table 5). damage the motor. Refer to Figure 4 for the location of the internal adjustment potentiometers. P-3026 • Doc. No. 60881 • Boston Gear Ratiotrol DC Motor Speed Control ® ®...
Page 11
To obtain a particular percentage of rated output torque, set the armature current at a percentage of rated armature current; e.g., 50% torque is obtained with 50% rated armature current. P-3026 • Doc. No. 60881 • Boston Gear Ratiotrol DC Motor Speed Control ® ®...
SCR and/or diode breaking down Replace BR1. (intermittently shorting) in Power Bridge BR1 Control board failure causing SCR Replace control board. false firing or misfiring P-3026 • Doc. No. 60881 • Boston Gear Ratiotrol DC Motor Speed Control ® ®...
Page 13
Correct condition accordingly. the motor Turning IR COMP potentiometer (R9) counterclockwise may minimize condition. Motor failure Check motor brushes, replace if needed. Repair or replace motor. P-3026 • Doc. No. 60881 • Boston Gear Ratiotrol DC Motor Speed Control ® ®...
Page 14
Correct accordingly. Motor fields should be connected for low voltage. Motor overheating from friction Check for misalignment. Realign motor. Shorted motor windings or Repair motor. faulty bearings P-3026 • Doc. No. 60881 • Boston Gear Ratiotrol DC Motor Speed Control ® ®...
Remote Operator’s Station 10-Turn Speed Pot NEMA 3, 4, 12, & 13 Kit * Includes Option D, Dyn. Braking ** Includes Option D and Option9, Jog P-3026 • Doc. No. 60881 • Boston Gear Ratiotrol DC Motor Speed Control ® ®...
No employee, agent, distributor, or other person is authorized to give additional warranties on behalf of Boston Gear, nor to assume for Boston Gear any other liability in connection with any of its products, except an officer of Boston Gear by a signed writing.