Outdoor unit quiet operation

z
Low noise mode (Optional parts: UTY-XWZXZ2)
Introduction of a low outdoor noise operation mode allow the outdoor unit to have two quiet mode
operation settings.
* Performance may drop depending on the outside air temperature condition, etc.
1) Level1 (Rated noise value -3dB)
2) Level2 (Rated noise value -5dB)
Peak cut operation
z
Peak cut mode (Optional parts: UTY-XWZXZ2)
The introduction of a peak power consumption mode control a 4 step outdoor operation control to
cut down energy usage at peak energy usage times.
* Performance drops by reducing the power consumption preferentially.
Level 1 ... Performs operation which suppresses the power consumption to almost 0% by stopping
the compressor.
Level 2 ... Performs operation which suppresses the power consumption to 50% of the rated
power consumption value.
Level 3 ... Performs operation which suppresses the power consumption to 75% of the rated
power consumption value.
Level 4 ... Performs operation which suppresses the power consumption to the rated power
consumption value (100%).