2
PARAMETER CODE (HEX)
<Common> Area accessible regardless of inverter models (Note 3)
Parameter
Address
0x0000
0x0001
0x0002
0x0003
0x0005
Frequency Reference
0x0006
0x0007
0x0008
0x0009
0x000A
0x000B
0x000C
0x000D
0x000E
Parameter Name
Drive model
Drive capacity
Drive Input Voltage
S/W Version
Run Command
Acceleration Time
Deceleration Time
Output Current
Output Frequency
Output Voltage
DC Link Voltage
Output Power
Sequence Monitor
Unit
Read/Write
-
R
-
R
-
R
-
R
0.01Hz
R/W
-
R/W
0.1 sec
R/W
0.1 sec
R/W
0.1 A
R
0.01 Hz
R
0.1 V
R
0.1 V
R
0.1 kW
R
-
R
6
Data Value (Hex)
4: SV-iS5
0: 0.75 1:1.5 2:2.2 3: 3.7
4: 5.5
5: 7.5 6: 11 7: 15
8: 18.5
9: 22 A: 30
C:45
D: 55 E: 75 F: 90
10: 110
11: 132 12: 160
13: 200
14:220
16:375 (Unit : kW)
0: 220V 1: 440V
0100: Ver. 1.00,
0101: Ver 1.01
Bit 0: Stop
Bit 1: Forward Run
Bit 2: Reverse Run
Bit 3: Fault Reset
Bit 4: Emergency Stop
BIT 0 : Stop
BIT 1 : Forward Run
BIT 2 : Reverse Run
BIT 3 : Fault (Trip)
BIT 4 : Accelerating
BIT 5 : Decelerating
BIT 6 : Output Frequency
Arrival
modbus-rtu iS5 manual.doc
B:37
15:280

Hide quick links: