...5 MODBUS Functions
5.2 Read Holding Register – Function Code 03
5.2.1 Read Holding Register Query
The Read Holding Register Query obtains the contents of up to eight holding registers
in the addressed slave.
Note. The data start register must contain the offset address of the first
register to be accessed, e.g. to start at register 1 the data start register
must contain 00 (00H).
Broadcast mode is not supported by Function Code 03.
Example. Read three holding registers from slave (01) starting at holding address 01
(process variable input).
Address Function
01
03
5.2.2 Read Holding Register Response
The addressed slave responds with its address and function code, followed by the
information field. The information field contains one byte describing the quantity of
data bytes to be returned. Two bytes are used to return each register requested, the
first byte containing the high order bits and the second the low order bits.
Example
PV input (two registers)
PV decimal places
Address Function Count Register 01
01
03
10
Register
Register Data No. of
Start
Start
Offset High Offset Low
00
00
270
Byte
Holding
High Low
00
00
00
Registers
High
00
1
Holding
Register 02
Register 03
High Low
High Low
01
09
Data No. of
Error
Registers
Check ( C R C - 1 6 )
Low
Field
03
05
Holding
Error
Check ( C R C - 1 6 )
Field
00
01
49
CB
75