Cabling Requirement; Card Reader And Io Connections - Keyprocessor Orion Installation Manual

Table of Contents

Advertisement

Picture RS485
connection
Note!
The Polyx must always be at the beginning of the communication line.
Remark:
When using a shielded wire (conductive), the shield should be attached
on one side to earth
Note!
The last Orion on the communication line must be provided of an EOL
jumper.
6.1.3

Cabling requirement

The required cable between the Polyx™ Network controller and the Orion(s) is displayed
below:
Cable
CAT5/6 UTP four twisted pairs of 24AWG
copper conductors
Minimal 24AWG twisted pairs of 24AWG
copper conductors, shielded
6.1.4

Card reader and IO connections

In the table below the labels-, connections- and the defaults are defined.
Reader & IO 1:
Label
Description
C
GND (digital ground)
T1
Digital input (Reader tamper)
LD
LED control
D0
D0 / Data or Digital input*
D1
D1 / Clock or Digital input*
O1
Digital output
C
GND (digital ground)
+V
Reader power
A1
ADC input 1 **
A2
ADC input 2 **
A3
ADC input 3 **
C
GND (digital ground)
H1
High Power output
C
GND
O2
Digital output
O3
Digital output
17
Connection: Orion <> Orion
Orion (I)
TIA/EIA-568-B
A B C S
Cable color
RS485
B
White/Orange
A
Orange
B
White/green
-
Blue
-
White/blue
A
Green
C
White/brown
C
Brown
(⏚) of the installation
Communication
type
RS485
iProtect default
Door in latch mode
Loop
Push button
Door status
Door control
Alarm
Orion (I)
A B C S
RS485
B
A
B
-
-
A
C
C
housing.
Total bus length (meter)
600