Eclipse 706GWR Operating Manual

Foundation fieldbus high performance, 4th generation guided wave radar level transmitter
Table of Contents

Advertisement

Quick Links

Eclipse
Model 706
®
F
fieldbus™
oundation
operating Manual
Software Version 1.x
High Performance, 4th Generation
Guided Wave Radar
Level Transmitter
2014/68/EU

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the 706GWR and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Eclipse 706GWR

  • Page 1 Eclipse Model 706 ® fieldbus™ oundation operating Manual Software Version 1.x High Performance, 4th Generation Guided Wave Radar Level Transmitter 2014/68/EU...
  • Page 2 Safety Messages MAGNETROL will repair or replace the control at no The ECLIPSE system is designed for use in Category II, cost to the purchaser (or owner) other than transportation. Pollution Degree 2 installations. Follow all standard...
  • Page 3: Table Of Contents

    3.1 Integrator Block (IT)..........24 6.4.2 Recommended Spare Parts......70 3.2 Arithmetic Block (AR)..........26 Appendix A................. 71 3.3 Input Selector Block (ISEL)........29 3.4 Signal Characterizer Block (SC)......30 57-646 ECLIPSE Guided Wave Radar Transmitter - F fieldbus ™ OUNDATION...
  • Page 4: Foundation Fieldbus

    FOUNDATION field- considers the two wires as a network. The network can ™ carry many process variables as well as other information. The ECLIPSE Model 706FF transmitter is a FOUNDA- TION fieldbus registered device that communicates with ™...
  • Page 5: Device Description (Dd)

    LAS in a field device such as the Eclipse Model 706 FF. ® NOTES: 1) The Eclipse Model 706 is normally shipped from the factory with Device Class set to Basic. 2) The operating class can be changed from Basic to L S using a fieldbus ™...
  • Page 6: Intrinsic Safety

    FISCO certifying agencies have limited the maximum seg- ment length to 1000 meters because the FISCO model does not rely on standardized ignition curves. The ECLIPSE Model 706 FF is available with entity IS, FISCO IS, FNICO non-incendive, or explosion proof approvals.
  • Page 7: Standard Function Blocks

    Fieldbus and there can be Model 706 PVs numerous function blocks in a single User Application. TB1 – Level The Enhanced ECLIPSE Model 706FF is a Guided Wave Level PV Status Radar (GWR) level transmitter with the following standard...
  • Page 8: Universal Fieldbus Block Parameters

    (hardware) enabling jumper is present and soft sim- ulation disable is set to NO. (See page 13 and refer to Section 2.4.5 for additional information). 57-646 ECLIPSE Guided Wave Radar Transmitter - F fieldbus ™ OUNDATION...
  • Page 9: Resource Block (Rb)

    OUNDATION manufacturer, and serial number. As it only contains data specific to the Eclipse Model 706 FF transmitter, it has no control function. 2.2.1 Resource Block Parameters MODE_BLK: Must be in AUTO in order for the remain- ing function blocks in the transmitter to operate.
  • Page 10 NOTE: After completing a download, allow several seconds before removing power from the ECLIPSE Model 706 FF transmitter to ensure that all data has been saved. FREE_SPACE: Shows the amount of available memory for further configuration.
  • Page 11: Additional Resource Block Parameters

    CHECK alarm category, this parame- ter reflects those that have been detected as active. FD_F IL_M P: Maps conditions to be detected as active for the FAIL alarm category. 57-646 ECLIPSE Guided Wave Radar Transmitter - F fieldbus ™ OUNDATION...
  • Page 12 FD_CHECK_PRI: Specifies the priority of the CHECK alarm category. FD_SIMUL TE: Diagnostic conditions can be manually supplied when simulation is enabled. FD_RECOMMEN_ CT: Describes what actions can be taken to address an active diagnostic condition. 57-646 Eclipse Guided Wave Radar Transmitter - F fieldbus OUNDATION...
  • Page 13: Transducer (Tb)

    “Hardware Version” in the Transducer Block. 2.3 Transducer Block The three TRANSDUCER blocks (TB) contained within the ECLIPSE Model 706 FF transmitter are custom blocks containing parameters that are pertinent to the transmitter itself. TRANSDUCER Block 1 (used for level and interface oper-...
  • Page 14: Tb Parameters

    Host system. 2.3.3 Eclipse Model 706 FF Configuration Parameters One of the main advantages of the Eclipse Model 706 FF GWR transmitter is that the device can be delivered pre- configured to the user.
  • Page 15: Configuration Parameters

    The Fieldbus™ concept allows a user to make adjustments if deemed necessary. 2.3.4 Eclipse Model 706 FF device-Specific Configuration Parameters Please refer to ECLIPSE Model 706 I/O Manual 57-606 for detailed information on the Model 706 device-specific configuration parameters. nalog Input Block...
  • Page 16 IO_OPTS: Option which the user may select to alter input and output block processing. STATUS_OPTS: Options which the user may select in the block processing of status. 57-646 ECLIPSE Guided Wave Radar Transmitter - F fieldbus ™ OUNDATION...
  • Page 17 HI_HI_ALM: The status for high high alarm and its associ- ated time stamp. HI_ALM: Status for high alarm and associated time stamp. LO_ALM: Status for low alarm and associated time stamp. 57-646 ECLIPSE Guided Wave Radar Transmitter - F fieldbus ™ OUNDATION...
  • Page 18: Ai Block Diagnostics

    OUT parameter for out of bound conditions. 2.4.3 Local display of analog input transducer Block output The ECLIPSE Model 706FF transmitter incorporates a use- ful feature that allows the Analog Input (AI) block Out val- ues to be displayed on the local LCD.
  • Page 19: Ai Out Display Screens

    Any or all (or none) of the AI block Out values can be selected for display on the LCD. NOTE: In the photo at left, status is shown as “Bad out of Service”. This message would be shown prior to commissioning. 57-646 ECLIPSE Guided Wave Radar Transmitter - F fieldbus ™ OUNDATION...
  • Page 20: Ai Block Configuration

    Out Scale EU at 0% Out Scale EU at 100% 81.3 Probe Length Out Scale Units 111 cm L Type Direct 0 cm 0 cm Offset = –15.5 cm 57-646 ECLIPSE Guided Wave Radar Transmitter - F fieldbus ™ OUNDATION...
  • Page 21: Simulation Feature

    This feature cannot be activated without the placement of a hardware jumper. This jumper is installed as standard on the ECLIPSE Model 706, and is placed under the display module to avoid inadvertent disabling of this feature. Refer to figure at left for jumper location.
  • Page 22 HI_HI_PRI: The priority of the HI HI Alarm. HI_LIM: The setting for the alarm limit used to detect the HI alarm condition. HI_PRI: The priority of the HI alarm. 57-646 ECLIPSE Guided Wave Radar Transmitter - F fieldbus ™ OUNDATION...
  • Page 23 SP: The target block setpoint value. SP_HI_LIM: The highest SP value allowed. SP_LO_LIM: The lowest SP value allowed. SP_RATE_DN: Ramp rate for downward SP changes. SP_RATE_UP: Ramp rate for upward SP changes. 57-646 ECLIPSE Guided Wave Radar Transmitter - F fieldbus ™ OUNDATION...
  • Page 24: Advanced Function Blocks

    • Normal: Most common mode for target BLOCK_ERR: The summary of active error conditions associated with the block. The block error for the Integrator function block is Out of service. 57-646 ECLIPSE Guided Wave Radar Transmitter - F fieldbus ™ OUNDATION...
  • Page 25 SRTOTAL: The snapshot of RTOTAL just before a reset SSP: The snapshot of TOTAL_SP INTEG_TYPE: Defines the type of counting (up or down) and the type of resetting (demand or periodic) 57-646 ECLIPSE Guided Wave Radar Transmitter - F fieldbus ™ OUNDATION...
  • Page 26: Arithmetic Block (Ar)

    The Arithmetic function block provides the ability to con- figure a range extension function for a primary input and applies the nine (9) different arithmetic types as compensa- tion to or augmentation of the range extended input. 57-646 ECLIPSE Guided Wave Radar Transmitter - F fieldbus ™ OUNDATION...
  • Page 27 PV_SCALE: Associated with the PV. OUT_RANGE: The high and low scale values, engineering units code, and number of digits to the right of the decimal point associated with OUT. 57-646 ECLIPSE Guided Wave Radar Transmitter - F fieldbus ™ OUNDATION...
  • Page 28 OUT_LO_LIM: The minimum output value allowed. UPDATE_EVT: This alert is generated by any changes to the static data. BLOCK_ALM: Used for all configuration, hardware, con- nection failure, or system problem in the block. 57-646 ECLIPSE Guided Wave Radar Transmitter - F fieldbus ™ OUNDATION...
  • Page 29: Input Selector Block (Isel)

    The supported status options for the input selector block are: “Use Uncertain as Good,” “Uncertain if Man mode.” IN_1: The block input value and status. 57-646 ECLIPSE Guided Wave Radar Transmitter - F fieldbus ™ OUNDATION...
  • Page 30: Signal Characterizer Block (Sc)

    ST_REV: The revision level of the static data associated with the function block. The revision value will be incre- mented in each time a static parameter value in the block is changed. 57-646 ECLIPSE Guided Wave Radar Transmitter - F fieldbus ™ OUNDATION...
  • Page 31 BLOCK_ALM: The block alarm is used for all configura- tion, hardware, connection failure, or system problems in the block. BLOCK_ERR_DESC: Reports more specific details regard- ing some errors reported through BLOCK_ERR. 57-646 ECLIPSE Guided Wave Radar Transmitter - F fieldbus ™ OUNDATION...
  • Page 32: Model 706 Transmitter Configuration

    4.0 Model 706 Transmitter Configuration Although the ECLIPSE Model 706 transmitter can be delivered pre-configured from the factory, it can also be eas- ily reconfigured in the shop or at the installation using the local LCD/Keypad. Bench configuration provides a conve- nient and efficient way to set up the transmitter before going to the tank site to complete the installation.
  • Page 33: Menu Transversal And Data Entry

    DOWN to choose new data selection ➪ ENTER to confirm selection B CK (Escape) key at any time to abort the proce- dure and escape to previous branch item. 57-646 ECLIPSE Guided Wave Radar Transmitter - F fieldbus ™ OUNDATION...
  • Page 34: Entering Numeric Data Using Digit Entry

    10 after the value has been decremented 10 times. Returns to the previous menu without changing Back the original value, which is immediately redis- played. Accepts the displayed value and returns to the Enter previous menu. 57-646 ECLIPSE Guided Wave Radar Transmitter - F fieldbus ™ OUNDATION...
  • Page 35: Enter Character Data

    4.3 Password Protection The ECLIPSE Model 706 transmitter has three levels of password protection to restrict access to certain portions of the menu structure that affect the operation of the system.
  • Page 36: Model 706 Menu: Step-By-Step Procedure

    Factory Password. 4.4 Model 706 Menu: Step-By-Step Procedure The following tables provide a complete explanation of the software menus displayed by the ECLIPSE transmitter. The menu layout is similar between the local Keypad/LCD interface, the DD, and the DTM.
  • Page 37 DI GNOSTICS Refer to Section 3.3.4 ME SURED V LUES Allows the user to scroll through all of the available measured values for the measurement type chosen. device Setup Screen 57-646 ECLIPSE Guided Wave Radar Transmitter - F fieldbus ™ OUNDATION...
  • Page 38: Model 706 Configuration Menu: Device Setup

    (-7.6 m to 22.9 m) 7Y7 Twin Flex Clad Dielectric Range: Probe Coating: (7yF only) Below 1.7 None (Bare) 1.7 to 3.0 PFA Coated 3.0 to 10 Above 10 57-646 ECLIPSE Guided Wave Radar Transmitter - F fieldbus ™ OUNDATION...
  • Page 39 Custom Table Type: Horizontal/Ellipse Linear Horizontal/Spherical Spline Spherical Level Input Source: Vertical/Flat Keypad Vertical/Ellipse Sensor Vertical/Spherical Vertical/Conical CUSTOM TABLE VALUES: Custom Table Up to 30 Pairs of Level/Volume Data 57-646 ECLIPSE Guided Wave Radar Transmitter - F fieldbus ™ OUNDATION...
  • Page 40 12 inches 1,000 18 inches 10,000 24 inches 100,000 36 inches Value (read only) 48 inches RunTime (read only) 60 inches 72 inches Reset 96 inches 120 inches 144 inches 57-646 ECLIPSE Guided Wave Radar Transmitter - F fieldbus ™ OUNDATION...
  • Page 41 View Ifc Echo Strength: Volume: (Interface and level mode only) (Volume and Level mode only) Hide Hide View View Elec Temp: Flow: Hide (Flow mode only) View Hide View 57-646 ECLIPSE Guided Wave Radar Transmitter - F fieldbus ™ OUNDATION...
  • Page 42 Reset Parameters: 0 to 100 echo strength units Reject Curve State: Sloped Start Value (used when Lvl Thresh Mode is Disabled Sloped) [Enabled] 0 to 100 echo strength units 57-646 ECLIPSE Guided Wave Radar Transmitter - F fieldbus ™ OUNDATION...
  • Page 43 Probe Target Mode Calibrate Targ Calib Ticks Target Ticks Elec Temp Offset Ifc Boundary Offset NAP Value Factory Reset FACTORY CALIB (Factory password required) Window Fiducial Ticks Conversion Factor Scale Offset 57-646 ECLIPSE Guided Wave Radar Transmitter - F fieldbus ™ OUNDATION...
  • Page 44: Troubleshooting And Diagnostics

    5.0 Troubleshooting and Diagnostics The ECLIPSE Model 706 transmitter is designed and engi- neered for trouble-free operation over a wide range of oper- ating conditions. The transmitter continuously runs a series of internal self-tests and displays helpful messages on the large graphic liquid crystal display (LCD) when attention is required.
  • Page 45: Diagnostics (Namur Ne 107)

    LIMIT attribute is “Constant.” Refer to Section 5.2 for additional information. 5.1.1 diagnostics (namur nE 107) The ECLIPSE Model 706 transmitter includes an exhaus- tive list of Diagnostic Indicators which follow the NAMUR NE 107 guidelines. NAMUR is an international user association of automation...
  • Page 46 Required A default mapping of all diagnostic indicators will be applied initially, and can be re-applied through use of a restart with NE-107 Diagnostic Indicators defaults operation. Status Signals 57-646 ECLIPSE Guided Wave Radar Transmitter - F fieldbus ™ OUNDATION...
  • Page 47: Diagnostic Indication Simulation

    Clean gold pin on transmitter and socket on probe. No Fiducial Check settings: Failure Reference signal too weak to detect. Fiducial Gain HF Cable Length Window Increase Fid Gain. Contact MAGNETROLTechnical Support. 57-646 ECLIPSE Guided Wave Radar Transmitter - F fieldbus ™ OUNDATION...
  • Page 48 10 seconds. TB Config Changed Function A transducer block parameter has been If desired, reset Config Changed Check modified from the User Interface. indicator in ADVANCED CONFIG menu. 57-646 ECLIPSE Guided Wave Radar Transmitter - F fieldbus ™ OUNDATION...
  • Page 49 The ECLIPSE Model 706 offers the ability to do Trending and Echo Curve analysis via the local graphical LCD or by using PACTware and the Model 706 DTM. The Model 706 DTM is an advanced troubleshooting tool that can aid in the resolution of some of the Diagnostic Indicators shown above.
  • Page 50: Diagnostic Help

    F or C. ECHO CURVES – This menu allows the user to display the live Echo Curve and Echo Rejection on the LCD. 57-646 ECLIPSE Guided Wave Radar Transmitter - F fieldbus ™ OUNDATION...
  • Page 51: Diagnostic Parameters

    Not Limited Nr Toalizer R Toalizer All PVs except Analog Board Error Sensor Failure Constant limited Elec Temperature All PVs except No Probe Sensor Failure Constant limited Elec Temperature 57-646 ECLIPSE Guided Wave Radar Transmitter - F fieldbus ™ OUNDATION...
  • Page 52 High Volume Alarm Volume Config Error High limited Flow High Flow Alarm Non-Specific High limited Head Level Ifc Level Upper Thick Safety Zone Alarm Distance Non-Specific Not limited Volume Head Flow 57-646 ECLIPSE Guided Wave Radar Transmitter - F fieldbus ™ OUNDATION...
  • Page 53 Not limited Low Echo Strength All PVs Good Non-Specific Not limited Low Ifc Echo Strength All PVs Good Non-Specific Not limited Sequence Record All PVs Good Non-Specific Not limited 57-646 ECLIPSE Guided Wave Radar Transmitter - F fieldbus ™ OUNDATION...
  • Page 54: Foundation

    • Ensure that the Resource Block, then the Transducer Block, and lastly the Function Block(s) are in“Auto” mode rather than Out of Service (OOS). If all of these requirements are met, stable communication should be established. 57-646 ECLIPSE Guided Wave Radar Transmitter - F fieldbus ™ OUNDATION...
  • Page 55: Reference Information

    Factory Sealed: No Explosion Proof conduit fitting (EY seal) is required within 18" of the transmitter. However, an Explosion Proof conduit fitting (EY seal) is required between the hazardous and safe areas. 57-646 ECLIPSE Guided Wave Radar Transmitter - F fieldbus ™...
  • Page 56: Agency Installation Drawing

    Any approved termination on with R = 90 ... 100 C = 0 ... 2.2µF AGENCY LISTED DRAWING ALL REVISIONS TO THIS DRAWING REQUIRE QA APPROVAL 099-5072 SHEET 3 OF 3 57-646 ECLIPSE Guided Wave Radar Transmitter - F fieldbus ™ OUNDATION...
  • Page 57: Model Number

    6 . 3 . 1 T R A N S M I T T E R 1 2 3 BASIC MODEL NUMBER 7 0 6 ECLIPSE 4th Generation Guided Wave Radar (GWR) Level Transmitter 4 POWER 24 VDC, Two-Wire 5 SIGNAL OUTPUT 4 –20 mA with HART...
  • Page 58: Probes

    600# Masoneilan flange in carbon steel 600# Masoneilan flange in stainless steel ¿ Confirm mounting conditions/nozzle diameter to ensure sufficient clearance. ¡ Always check dimensions if ANSI/EN flanges are not used. 57-646 ECLIPSE Guided Wave Radar Transmitter - F fieldbus ™ OUNDATION...
  • Page 59 4-piece Enlarged Segmented Probe OD=2.5"(64mm) 13 14 15 INSERTION LENGTH inches (012 – 396) X X X cm (030 – 999) unit of measure determined by 2nd digit of model number 57-646 ECLIPSE Guided Wave Radar Transmitter - F fieldbus ™ OUNDATION...
  • Page 60 600# Masoneilan flange in stainless steel ¿ Confirm mounting conditions/nozzle diameter to ensure sufficient clearance. ¡ Always check dimensions if ANSI/EN flanges are not used. ¬ Not available with 3rd digit ‘D’ 57-646 ECLIPSE Guided Wave Radar Transmitter - F fieldbus ™ OUNDATION...
  • Page 61 Single Length Probe (Non-Segmented) 13 14 15 INSERTION LENGTH inches (012 – 240) X X X cm (030 – 610) unit of measure determined by 2nd digit of model number 57-646 ECLIPSE Guided Wave Radar Transmitter - F fieldbus ™ OUNDATION...
  • Page 62: Measurement System

    600# Masoneilan flange in stainless steel – as per dimensions on page 18 ¿ Confirm mounting conditions/nozzle diameter to ensure sufficient clearance. ¡ Always check dimensions if ANSI/EN flanges are not used. 57-646 ECLIPSE Guided Wave Radar Transmitter - F fieldbus ™...
  • Page 63 4-piece Segmented Probe 13 14 15 INSERTION LENGTH inches (012 – 288) X X X cm (030 – 732) unit of measure determined by 2nd digit of model number 57-646 ECLIPSE Guided Wave Radar Transmitter - F fieldbus ™ OUNDATION...
  • Page 64 EN 1092-1 TYPE B2 DN 80, PN 25/40 EN 1092-1 TYPE A DN 100, PN 400 EN 1092-1 TYPE B2 ¿ Confirm mounting conditions/nozzle diameter to ensure sufficient clearance. 57-646 ECLIPSE Guided Wave Radar Transmitter - F fieldbus ™ OUNDATION...
  • Page 65 Probes(8th Digit F or P) 13 14 15 INSERTION LENGTH inches (012 – 288) X X X cm (030 – 732) unit of measure determined by 2nd digit of model number 57-646 ECLIPSE Guided Wave Radar Transmitter - F fieldbus ™ OUNDATION...
  • Page 66 DN 100, PN 16 EN 1092-1 TYPE A DN 100, PN 25/40 EN 1092-1 TYPE A DN 100, PN 63 EN 1092-1 TYPE B2 DN 100, PN 100 EN 1092-1 TYPE B2 57-646 ECLIPSE Guided Wave Radar Transmitter - F fieldbus ™ OUNDATION...
  • Page 67 (for use with 3rd digit '1' only) 13 14 15 INSERTION LENGTH feet (003 – 100) X X X meters (001 – 030) unit of measure determined by 2nd digit of model number 57-646 ECLIPSE Guided Wave Radar Transmitter - F fieldbus ™ OUNDATION...
  • Page 68 EN 1092-1 TYPE A DN 100, PN 63 EN 1092-1 TYPE B2 DN 100, PN 100 EN 1092-1 TYPE B2 ¿ Confirm mounting conditions/nozzle diameter to ensure sufficient clearance. 57-646 ECLIPSE Guided Wave Radar Transmitter - F fieldbus ™ OUNDATION...
  • Page 69 12 SPECIAL OPTIONS None 13 14 15 INSERTION LENGTH feet (003 – 100) X X X meters (001 – 030) unit of measure determined by 2nd digit of model number 57-646 ECLIPSE Guided Wave Radar Transmitter - F fieldbus ™ OUNDATION...
  • Page 70: Replacement Parts

    6.4.2 Recommended Spare Parts item description Part number ¿ Electronic module Display Module Z31-2850-001 Potted Bezel Assembly Z31-2849-002 ¡ Terminal board General Purpose (GP), Intrinsically Safe (IS), Explosion Proof (XP) Z30-9166-001 57-646 ECLIPSE Guided Wave Radar Transmitter - F fieldbus ™ OUNDATION...
  • Page 71 GET CONNECTED Simply connect the HART/RS232 or HART/USB serial inter- face from the PC to the two-wire loop. Echo Curve Screen 57-646 ECLIPSE Guided Wave Radar Transmitter - F fieldbus ™ OUNDATION...
  • Page 72 Safety Zone Height RESET_SAFETY_ZONE_LATCH Reset SZ Latch ALARM_DELAY Failure Alarm Delay LEVEL_TRIM Level Trim LEVEL_THRESHOLD_MODE Level Threshold Mode LEVEL_THRESHOLD_VALUE Level Threshold Value SLOPED_START_VALUE Sloped Start Value SLOPED_END_DISTANCE Sloped End Distance 57-646 ECLIPSE Guided Wave Radar Transmitter - F fieldbus OUNDATION...
  • Page 73 Target Ticks TARGET_ECHO_STRENGTH Target Echo Strength VAPOR_MEASURED_DIELECTRIC Vapor Measured Dielectric EOP_TICKS EoP Ticks EOP_ECHO_STRENGTH EoP Echo Strength EOP_DISTANCE EoP Distance EOP_ MEASURED_DIELECTRIC EoP Measured Dielectric ELECTRONICS_TEMPERATURE Electronics Temp TEMPERATURE_UNIT Temperature Unit 57-646 ECLIPSE Guided Wave Radar Transmitter - F fieldbus OUNDATION...
  • Page 74 New User Password LOCAL_DISP_MEAS_VALUES Local Disp Meas Values LOCAL_DISP_LANGUAGE Local Disp Language LOCAL_DISP_PHYS_DEV_TAG Local Disp Phys Dev Tag FIRMWARE_VERSION Firmware Version HARDWARE_VERSION Hardware Version PRESENT_STATUS Present Status STATUS_INDICATORS_1 Status Indicators 57-646 ECLIPSE Guided Wave Radar Transmitter - F fieldbus OUNDATION...
  • Page 75 Echo Reference ECHO_HISTORY_LOG1 Echo History 1 ECHO_HISTORY_LOG2 Echo History 2 ECHO_HISTORY_LOG3 Echo History 3 ECHO_HISTORY_LOG4 Echo History 4 ECHO_HISTORY_LOG5 Echo History 5 ECHO_HISTORY_LOG6 Echo History 6 ECHO_HISTORY_LOG7 Echo History 7 57-646 ECLIPSE Guided Wave Radar Transmitter - F fieldbus OUNDATION...
  • Page 76 XD_ERROR Transducer Error COLLECTION_DIRECTORY Collection Directory MEAS_TYPE Measurement Type VOLUME Volume VOLUME_UNIT Volume Unit LEVEL_VALUE Level LEVEL_UNIT Level Unit VESSEL TYPE Vessel Type VESSEL_RADIUS Vessel Radius VESSEL_ELLIPSE_DEPTH Vessel Ellipse Depth 57-646 ECLIPSE Guided Wave Radar Transmitter - F fieldbus OUNDATION...
  • Page 77 Volume Table Pt 26 VOLUME_TABLE_PT_27 Volume Table Pt 27 VOLUME_TABLE_PT_28 Volume Table Pt 28 VOLUME_TABLE_PT_29 Volume Table Pt 29 VOLUME_TABLE_PT_30 Volume Table Pt 30 VOLUME_HIGH_LIMIT Volume High Limit LEVEL_LOW_LIMIT Level Low Limit 57-646 ECLIPSE Guided Wave Radar Transmitter - F fieldbus OUNDATION...
  • Page 78 FLOW Flow FLOW_UNIT Flow Unit HEAD Head HEAD_UNIT Head Unit DISTANCE_VALUE Distance DISTANCE_UNIT Distance Unit NR_TOTALIZER_MULTIPLIER NR Totalizer Multiplier NR_TOTALIZER NR Totalizer NR_TOTALIZER_UNIT NR Totalizer Unit NR_TOTALIZER_TIME NR Totalizer Time 57-646 ECLIPSE Guided Wave Radar Transmitter - F fieldbus OUNDATION...
  • Page 79 FLOW_TABLE_PT_12 Flow Table Pt 12 FLOW_TABLE_PT_13 Flow Table Pt 13 FLOW_TABLE_PT_14 Flow Table Pt 14 FLOW_TABLE_PT_15 Flow Table Pt 15 FLOW_TABLE_PT_16 Flow Table Pt 16 FLOW_TABLE_PT_17 Flow Table Pt 17 57-646 ECLIPSE Guided Wave Radar Transmitter - F fieldbus OUNDATION...
  • Page 80 PRESENT_STATUS Present Status STATUS_INDICATORS_1 Status Indicators STATUS_INDICATORS _2 Status Indicators STATUS_INDICATORS _3 Status Indicators STATUS_INDICATORS _4 Status Indicators STATUS_INDICATORS _5 Status Indicators STATUS_INDICATORS _6 Status Indicators TREND_FLOW_VALUE Flow TREND_HEAD_VALUE Head 57-646 ECLIPSE Guided Wave Radar Transmitter - F fieldbus OUNDATION...
  • Page 81 NOTES 57-646 ECLIPSE Guided Wave Radar Transmitter - F fieldbus OUNDATION...
  • Page 82 NOTES 57-646 ECLIPSE Guided Wave Radar Transmitter - F fieldbus OUNDATION...
  • Page 83 NOTES 57-646 ECLIPSE Guided Wave Radar Transmitter - F fieldbus OUNDATION...
  • Page 84 Eclipse Guided Wave Radar transmitters may be protected by one or more of the following U.S. Patent Nos. US 6,062,095; US 6,247,362; US 6,588,272; US 6,626,038; US 6,640,629; US 6,642,807; US 6,690,320; US 6,750,808; US 6,801,157. May depend on model.