Test
IEC 61000-4-17
IEC 60255-5
IEC 60255-5
Section 7.4.2

IEEE 1613 Type Tests

Table: IEEE 1613 Type Tests
IEEE Test
C37.90.3
C37.90.2
C37.90.1
C37.90.1
C37.90
C37.90
NOTE
• If the unit contains copper ports, the IEEE 1613 conformance is Class 1 (During disturbance, errors
may occur but recovery is automatic).
• If the unit contains all fiber ports, the IEEE 1613 conformance is Class 2 (During disturbance, no
errors will occur).
IEEE 1613 Type Tests
Description
Ripple on D.C.
Power Supply
Dielectric Strength
H.V. Impulse
IEEE 1613 Clause
9
8
Radiated RFI
7
Fast Transient
7
Oscillatory
6
H.V. Impulse
6
Dielectric Strength
D.C. Power ports
Signal ports
D.C. Power ports
A.C. Power ports
Signal ports
D.C. Power ports
A.C. Power ports
Description
ESD
Enclosure Contact
Enclosure Air
Enclosure ports
Signal ports
D.C. Power ports
A.C. Power ports
Earth ground ports
Signal ports
D.C. Power ports
A.C. Power ports
Signal ports
D.C. Power ports
A.C. Power ports
Signal ports
D.C. Power ports
A.C. Power ports
Test Levels
10%
2 kVAC (Fail-Safe Relay output)
1.5kVDC
2 kVAC
5kV (Fail-Safe Relay output)
5kV
5kV
Test Levels
+/- 8kV
+/- 15kV
35 V/m
+/- 4kV @ 2.5kHz
+/- 4kV
+/- 4kV
+/- 4kV
2.5kV common mode @ 1MHz
2.5kV common & differential mode @ 1MHz
2.5kV common & differential mode @ 1MHz
5 kV (Failsafe Relay)
5 kV
5 kV
2kVAC (Failsafe Relay)
1.5 kVDC
2 kVAC
Chapter 7
Certification
Severity
Levels
3
N/A
N/A
N/A
N/A
N/A
N/A