Table of Contents

Advertisement

!
USER MANUAL – Release 1.2 of 01/01/2010
Page 1 of 191
Version: 02/03/2010
PROGRAMMABLE CONTROLLERS
IPC400D SERIES
USER MANUAL
"#$%&

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the IPC400D SERIES and is the answer not in the manual?

Questions and answers

Essam
May 30, 2025

ماذا تعني هذة الرسالة

User image 6839fb526f921
1 comments:
Mr. Anderson
May 30, 2025

The message "AFr (network frequency alarm)" for the DIXEL IPC400D SERIES means that the network frequency is different from the value configured in parameter SP11. This triggers an alarm with the relay and buzzer activated, and other loads are turned off. The alarm resets automatically when the frequency returns to the set range or when network frequency control is disabled by setting SP11 = 2.

This answer is automatically generated

Essam
May 30, 2025

ماذا تعني هذة الرساله

User image 6839faf35a10c
1 comments:
Mr. Anderson
May 30, 2025

The message "NETWORK FREQUENCY ALARM" (display label AFr) for the DIXEL IPC400D SERIES means that the network frequency is different from the configured value in parameter SP11. This alarm activates the alarm relay and buzzer, and turns off other loads. It resets automatically when the frequency returns to the set range or when network frequency control is disabled by setting SP11 = 2.

This answer is automatically generated

Esam
June 18, 2025

when i set CF5 = 16 the Dixell 400d Automatic restart continuously ??

Esam
June 18, 2025

how can i reset the Dixell 400d ???

Summary of Contents for dIXEL IPC400D SERIES

  • Page 1 USER MANUAL – Release 1.2 of 01/01/2010 Page 1 of 191 Version: 02/03/2010 PROGRAMMABLE CONTROLLERS IPC400D SERIES USER MANUAL "#$%&...
  • Page 2: Table Of Contents

    INDEX GENERAL RECOMMENDATIONS SAFETY PRECAUTIONS GENERALITIES MAIN FUNCTIONS IPC400D SERIES FEATURES ANALOGUE - DIGITAL INPUTS/OUTPUTS CONFIGURATIONS ID1 – ID20 DIGITAL INPUTS CONFIGURATION RL1- RL15 DIGITAL OUTPUTS CONFIGURATION ANALOGUE INPUTS PB1 - PB10 CONFIGURATION CONFIGURATION OF THE OUT1 / OUT4 PROPORTIONAL OUTPUTS CONFIGURATION OF THE OUT5 / OUT6 PROPORTIONAL OUTPUTS HOW TO CONFIGURE THE INPUTS AND OUTPUTS (FILE IO.CONF)
  • Page 3 USER MANUAL – Release 1.2 of 01/01/2010 Page 3 of 191 Version: 02/03/2010 10.2 UNIPOLAR/BIPOLAR VALVES DRIVER CONNECTION MODE XEV20D ELECTRONIC THERMOSTATIC DRIVER WIRING DIAGRAMS 11.1 XEV20D DRIVER MODEL HARDWARE RESOURCES 11.2 XEV20D DRIVER MODULE CONNECTION TO THE PROGRAMMABLE UNIT 11.3 NTC / PTC / PT1000 PROBE ANALOGUE INPUTS 11.4...
  • Page 4 USER MANUAL – Release 1.2 of 01/01/2010 Page 4 of 191 Version: 02/03/2010 17.1 UNIT SWITCH-ON/OFF FROM THE KEYBOARD 17.2 UNIT SWITCH-ON/OFF FROM DIGITAL INPUT 17.3 SELECTING THE WORKING MODE: COOLING – HEATING 17.4 CHANGE OVER FUNCTION 17.5 COOLING – HEATING MODE SELECTION FROM KEYBOARD 17.6 COOLING –...
  • Page 5 USER MANUAL – Release 1.2 of 01/01/2010 Page 5 of 191 Version: 02/03/2010 26.9 SELECTION OF COMPRESSORS IN THE CIRCUIT ON THE BASIS OF "COMPRESSOR WEIGHT" 26.10 SELECTION OF THE CIRCUIT ON THE BASIS OF "COMPRESSOR WEIGHT" (NOT AVAILABLE FUNCTION) COMPRESSORS SWITCH-ON 27.1 DESCRIPTION OF DIRECT START-UP...
  • Page 6 USER MANUAL – Release 1.2 of 01/01/2010 Page 6 of 191 Version: 02/03/2010 38.1 SUPPLY FAN DURING DEFROST 38.2 HOT START FUNCTION FUNCTION OF SUPPLY FAN MAINTENANCE REQUEST CONDENSER WATER PUMP WORKING 40.1 ONLY ONE RELAY CONFIGURED AS CONDENSER WATER PUMP CONDENSER WATER PUMP ROTATION 41.1 2 RELAYS CONFIGURED AS CONDENSER WATER PUMP...
  • Page 7 USER MANUAL – Release 1.2 of 01/01/2010 Page 7 of 191 Version: 02/03/2010 47.3 TEMPERATURE CONTROL IN HEATING MODE 47.4 TEMPERATURE CONTROL OF THE AIR/AIR UNIT HEATERS 47.5 SUPPORT/ANTI-FREEZE/BOILER HEATERS WORKING GRAPHICS 47.6 TEMPERATURE CONTROL OF THE EVAPORATOR ANTI-FREEZE HEATERS 47.7 TEMPERATURE CONTROL OF THE CONDENSER ANTI-FREEZE HEATERS 47.8...
  • Page 8 USER MANUAL – Release 1.2 of 01/01/2010 Page 8 of 191 Version: 02/03/2010 54.4 WORKING 54.5 FREE-COOLING WORKING IN HEATING MODE 54.6 ANTI-FREEZE ALARM PREVENTION 54.7 FREE COOLING VENTILATION WORKING MODE 54.8 FRACTIONED BATTERY AUXILIARY RELAY FUNCTION 55.1 DIRECT ACTION WORKING ENABLED 55.2 REVERSE ACTION WORKING ENABLED WORKING OF THE AUXILIARY ANALOGUE OUTPUTS (0÷10...
  • Page 9 USER MANUAL – Release 1.2 of 01/01/2010 Page 9 of 191 Version: 02/03/2010 UNIT CONFIGURATION 57.39 57.40 REMOTE TERMINAL ALARM 57.41 NOTE: ALARM RELAY AND BUZZER NO VOLTAGE AUTOMATIC TO MANUAL RESRT ALARMS DIAGNOSTICS OUTPUTS BLOCK TABLE 60.1 CIRCUIT “A” OUTPUTS ALARM BLOCK TABLE 60.2 CIRCUIT “B”...
  • Page 10: General Recommendations

    USER MANUAL – Release 1.2 of 01/01/2010 Page 10 of 191 Version: 02/03/2010 1. GENERAL RECOMMENDATIONS To be read before further use of the unit. • This manual constitutes an integral part of the product and must be kept near to the appliance for easy and quick consultation.
  • Page 11: Generalities

    USER MANUAL – Release 1.2 of 01/01/2010 Page 11 of 191 Version: 02/03/2010 2. GENERALITIES iPro.CHILL is a programmable controller for application on Air Conditioning units up to 4 circuits and 4 compressors per circuit. It is possible to manage the following units: Air/air •...
  • Page 12 USER MANUAL – Release 1.2 of 01/01/2010 Page 12 of 191 Version: 02/03/2010 Allows maintenance of the circuit • Allows "partialised" working of the unit • Possibility of enabling/disabling the individual compressor Maintenance of the individual compressor • Malfunction • Complete management of pump down function: With dedicated pressure switch •...
  • Page 13: Ipc400D Series Features

    USER MANUAL – Release 1.2 of 01/01/2010 Page 13 of 191 Version: 02/03/2010 Via RS485 slave output with ModBus protocol to Dixell XWEB300D / XWEB500D supervision systems • 3. IPC400D SERIES FEATURES FEATURES IPC410D IPC415D POWER SUPPLY 24 VAC/DC (± 10%)
  • Page 14: Analogue - Digital Inputs/Outputs Configurations

    USER MANUAL – Release 1.2 of 01/01/2010 Page 14 of 191 Version: 02/03/2010 4. ANALOGUE - DIGITAL INPUTS/OUTPUTS CONFIGURATIONS ID1 – ID20 DIGITAL INPUTS CONFIGURATION Disabled Remote ON/OFF Remote cooling/heating Evaporator flow switch Condenser flow switch Sanitary water flow switch Antifreeze alarm circuit 1 Antifreeze alarm circuit 2 Antifreeze alarm circuit 3...
  • Page 15 USER MANUAL – Release 1.2 of 01/01/2010 Page 15 of 191 Version: 02/03/2010 Evaporator support pump Overload Condenser main pump Overload Condenser support pump Overload Circuit 1 heat recovery request Circuit 2 heat recovery request Circuit 3 heat recovery request Circuit 4 heat recovery request End of circuit 1 defrost End of circuit 2 defrost...
  • Page 16: Rl1- Rl15 Digital Outputs Configuration

    USER MANUAL – Release 1.2 of 01/01/2010 Page 16 of 191 Version: 02/03/2010 RL1- RL15 DIGITAL OUTPUTS CONFIGURATION Disabled Alarm Evaporator main pump/supply fan Evaporator support pump Antifreeze heaters / support / boiler 1 step Antifreeze heaters / support / boiler 2 step Antifreeze heaters / support / boiler 3 step...
  • Page 17 USER MANUAL – Release 1.2 of 01/01/2010 Page 17 of 191 Version: 02/03/2010 Compressor 1 liquid injection solenoid valve Compressor 2 liquid injection solenoid valve Compressor 3 liquid injection solenoid valve Compressor 4 liquid injection solenoid valve Compressor 5 liquid injection solenoid valve Compressor 6 liquid injection solenoid valve Compressor 7 liquid injection solenoid valve Compressor 8 liquid injection solenoid valve...
  • Page 18 USER MANUAL – Release 1.2 of 01/01/2010 Page 18 of 191 Version: 02/03/2010 108. Compressor 5 Direct start-up Compressor 5 Winding 1 Part Winding start-up Compressor 5 Line 1 Star Delta start-up 109. Compressor 5 Winding 2 Part Winding start-up Compressor 5 Line 2 Star Delta start-up 110.
  • Page 19 USER MANUAL – Release 1.2 of 01/01/2010 Page 19 of 191 Version: 02/03/2010 158. LP1 Alarm (Low pressure circuit 1) 159. LP2 Alarm (Low pressure circuit 2) 160. LP3 Alarm (Low pressure circuit 3) 161. LP4 Alarm (Low pressure circuit 4) 162.
  • Page 20: Analogue Inputs Pb1 - Pb10 Configuration

    USER MANUAL – Release 1.2 of 01/01/2010 Page 20 of 191 Version: 02/03/2010 ANALOGUE INPUTS PB1 - PB10 CONFIGURATION 0. Disabled 1. Compressor 1 PTC discharge temperature probe 2. Compressor 2 PTC discharge temperature probe 3. Compressor 3 PTC discharge temperature probe 4.
  • Page 21: Configuration Of The Out1 / Out4 Proportional Outputs

    USER MANUAL – Release 1.2 of 01/01/2010 Page 21 of 191 Version: 02/03/2010 60. Auxiliary output n° 1 pressure probe (4÷20 mA / 0÷ 5 Volt) 61. Auxiliary output n° 2 pressure probe (4÷20 mA / 0÷ 5 Volt) 62. Auxiliary output n° 3 pressure probe (4÷20 mA / 0÷ 5 Volt) 63.
  • Page 22: How To Configure The Inputs And Outputs (File Io.conf)

    USER MANUAL – Release 1.2 of 01/01/2010 Page 22 of 191 Version: 02/03/2010 HOW TO CONFIGURE THE INPUTS AND OUTPUTS (FILE IO.CONF) To configure the digital inputs/outputs and analogue inputs/outputs it is necessary to generate a file called io.conf; This file is already available with default values. The file structure is thus composed: For the digital inputs: •...
  • Page 23: Further Connections

    USER MANUAL – Release 1.2 of 01/01/2010 Page 23 of 191 Version: 02/03/2010 FURTHER CONNECTIONS 1 USB 1 Network 1 connecter for/GSM modem /XWEB modem 1 RS485 master 1 RS485 slave 1 CANbus 5. PARAMETERS IN TABLE FORM SUB-MENU SELECTION Label Meaning Display all parameters...
  • Page 24 USER MANUAL – Release 1.2 of 01/01/2010 Page 24 of 191 Version: 02/03/2010 Temperature control Parameter Description Resolution ST 1 Cooling set-point ST02 ST03 °C/°F Dec/int Defines the working set-point in cooling mode ST 2 Minimum Cooling set point -50.0 °C ST01 Minimum limit for the working set-point in cooling mode...
  • Page 25 USER MANUAL – Release 1.2 of 01/01/2010 Page 25 of 191 Version: 02/03/2010 ST 21 Defines the circuit 2 temperature control probe in cooling mode 0= Evaporator inlet NTC temperature probe 1= Evaporator n° 1 outlet NTC temperature probe 2= Evaporator n° 2 outlet NTC temperature probe 3= Evaporator n°...
  • Page 26 USER MANUAL – Release 1.2 of 01/01/2010 Page 26 of 191 Version: 02/03/2010 Unit CF 1 Defines the type of unit to control 0 = Air to air unit 1 = Air to water 2 = Water to water CF 2 Selection of unit working mode 1 = cooling only 2 = heating only...
  • Page 27 USER MANUAL – Release 1.2 of 01/01/2010 Page 27 of 191 Version: 02/03/2010 SP 4 Offset NTC probe remote terminal n° 1 -12.0 12.0 °C °F SP 5 Offset NTC probe remote terminal n° 2 -12.0 12.0 °C °F Working mode SP 6 Working mode cooling /...
  • Page 28 USER MANUAL – Release 1.2 of 01/01/2010 Page 28 of 191 Version: 02/03/2010 ES 12 Saturday energy saving time band definition ES 13 Sunday energy saving time band definition ES 14 Energy saving set increase in cooling mode -50.0 °C °F ES 15 Energy saving differential in cooling mode...
  • Page 29 USER MANUAL – Release 1.2 of 01/01/2010 Page 29 of 191 Version: 02/03/2010 Compressors rotation – balancing – temperature control CO 16 Selection criteria for compressors in the circuit 0 = Fixed sequence 1 = FIFO 2 = Balance 3 = Saturation 4 = Weight of the compressors CO 17 Criteria of selection for circuits...
  • Page 30 USER MANUAL – Release 1.2 of 01/01/2010 Page 30 of 191 Version: 02/03/2010 CO 56 Compressor 4 maintenance period 10 Hr 10 Hr CO 57 Compressor 5 maintenance period 10 Hr 10 Hr CO 58 Compressor 6 maintenance period 10 Hr 10 Hr CO 59 Compressor 7 maintenance period...
  • Page 31 USER MANUAL – Release 1.2 of 01/01/2010 Page 31 of 191 Version: 02/03/2010 PA 21 Pumps Enabling and Rotation: 0 = Single Pump – No Rotation; 1 = 2 Pumps – Manual Rotation; 2 = 2 Pumps – Rotation according to starts; 3 = 2 Pumps –Rotation according to running hours;...
  • Page 32 USER MANUAL – Release 1.2 of 01/01/2010 Page 32 of 191 Version: 02/03/2010 Un 1 High evaporator water inlet temperature unloading function set-point in -50.0 °C cooling mode °F Un 2 High evaporator water inlet temperature unloading function differential in 25.0 °C cooling mode...
  • Page 33 USER MANUAL – Release 1.2 of 01/01/2010 Page 33 of 191 Version: 02/03/2010 FA11 Proportional regulation Condensing pressure/temperature value corresponding to the maximum -50.0 °C outdoor fan speed defined at FA08 °F Step regulation 50.0 STEP Set: Condensing pressure/temperature value corresponding to the activation of the 2 outdoor fan step.
  • Page 34 USER MANUAL – Release 1.2 of 01/01/2010 Page 34 of 191 Version: 02/03/2010 FA26 STEP Set: Condensing pressure/temperature value corresponding to -50.0 °C the activation of the 4 outdoor fan step. °F 50.0 FA27 Condensing pressure/temperature differential between 25.0 °C °F activation and deactivation of the outdoor fan steps (ciruits 14.0...
  • Page 35 USER MANUAL – Release 1.2 of 01/01/2010 Page 35 of 191 Version: 02/03/2010 FA42 STEP Set: Evaporating pressure value corresponding to the activation of -50.0 °C the 4 outdoor fan step. °F 50.0 FA43 Evaporating pressure differential between activation and deactivation of the 25.0 °C outdoor fan steps (ciruits 1/2).
  • Page 36 USER MANUAL – Release 1.2 of 01/01/2010 Page 36 of 191 Version: 02/03/2010 Ar 16 Boiler function working set point and differential 0 = Heating mode set point (ST04) and differential (ST08) 1 = Boiler function set point (Ar13) and differential (Ar14) 2 = The Working set point is the Heating set point increased by the Boiler function set point (ST04+Ar17) and differential is the Boiler function one (Ar18)
  • Page 37 USER MANUAL – Release 1.2 of 01/01/2010 Page 37 of 191 Version: 02/03/2010 Defrost with condensation fans dF 25 External temperature level for enabling defrost with outdoor fans -50.0 °C The function defrost with outdoor fans is enabled if the external temperature is °F above the dF25 level.
  • Page 38 USER MANUAL – Release 1.2 of 01/01/2010 Page 38 of 191 Version: 02/03/2010 rC 10 Outdoor fans working in heat recovery mode 0 = Enabled 1 = Disabled rC 11 Heat recovery minimum set point -50.0 °C rC13 Defines the minimum limit for the working set-point in heat recovery mode °F rC 12 Heat recovery maximum set point...
  • Page 39 USER MANUAL – Release 1.2 of 01/01/2010 Page 39 of 191 Version: 02/03/2010 FS 20 Maximum antilegionella activation time The antilegionella cycle is disabled after the time FS20 even though the working set point is not achieved. FS 21 Heaters deactvation band for antilegionella function The electric heaters activated for the antilegionella function are disabled 25.0 °C...
  • Page 40 USER MANUAL – Release 1.2 of 01/01/2010 Page 40 of 191 Version: 02/03/2010 FS 48 Domestic hot water solenoid valves disabling in case of hot water production only (dedicated pipework). If the function is active during production of domestic hot water only (no cooling or heating demand) the solenoid valves remain in their standard position and only the domestic hot water pump is activated.
  • Page 41 USER MANUAL – Release 1.2 of 01/01/2010 Page 41 of 191 Version: 02/03/2010 FC 13 Condensing pressure/temperature 1 step coil split differential 25.0 °C °F 14.0 FC 14 Condensing pressure/temperature 2 step coil split set point -50.0 °C °F 50.0 FC 15 Condensing pressure/temperature 2 step coil split differential...
  • Page 42 USER MANUAL – Release 1.2 of 01/01/2010 Page 42 of 191 Version: 02/03/2010 US 15 Auxiliary relay n°4 set-point -50.0 °C °F 50.0 US 16 Auxiliary relay n°4 differential 25.0 °C °F 14.0 Auxiliary proportional output n°1 (0÷10V DC) US 17 Auxiliary proportional output n°1 working mode 0 = Disabled 1 = Always enabled with direct action...
  • Page 43 USER MANUAL – Release 1.2 of 01/01/2010 Page 43 of 191 Version: 02/03/2010 US 38 Auxiliary proportional output n°4 differential 25.0 °C °F 14.0 US 39 Auxiliary proportional output n°4 minimum value US40 US 40 Auxiliary proportional output n°4 maximum value US39 Alarms Parameter...
  • Page 44 USER MANUAL – Release 1.2 of 01/01/2010 Page 44 of 191 Version: 02/03/2010 Condenser flow alarm working mode AL 21 Condenser flow alarm working mode 0 = disabled 1 = enabled in cooling mode only 2 = enabled in heating mode only 3 = enabled both in cooling and heating mode AL 22 Delay on condenser flow alarm activation from water pump activation...
  • Page 45 USER MANUAL – Release 1.2 of 01/01/2010 Page 45 of 191 Version: 02/03/2010 AL 44 Delay on activation of antifreeze / low room air temperature / low outlet air temperature alarm from alarm condition occurrence during regular heating Secs mode. AL 45 Maximum number of antifreeze / low outlet air temperature alarms per hour in heating mode.
  • Page 46 USER MANUAL – Release 1.2 of 01/01/2010 Page 46 of 191 Version: 02/03/2010 AL 60 Maximum number of evaporator water inlet high temperature probe alarm occurrences per hour Reset is always manual if AL60 = 0 Reset is always automatic if AL60 = 60 Reset moves from automatic to manual if AL60 moves from 1 to 59 AL 61 Delay on activation of evaporator inlet high temperature alarm from...
  • Page 47 USER MANUAL – Release 1.2 of 01/01/2010 Page 47 of 191 Version: 02/03/2010 Et11 Connection between driver 1 valve 2 and relevant circuit 0 = circuit 1 1 = circuit 2 2 = circuit 3 3 = circuit 4 Et12 Connection between driver 2 valve 1 and relevant circuit 0 = circuit 1 1 = circuit 2...
  • Page 48 USER MANUAL – Release 1.2 of 01/01/2010 Page 48 of 191 Version: 02/03/2010 Et37 High superheating set point °C The alarm situation is notified after the high superheating alarm activation Et34 °F delay (Et29) Et38 Low superheating set point °C In this situation an additional integral time is added to normal regulation in Et34 °F...
  • Page 49: Ipro.chill Programmable Controller

    USER MANUAL – Release 1.2 of 01/01/2010 Page 49 of 191 Version: 02/03/2010 6. IPRO.CHILL PROGRAMMABLE CONTROLLER The programmable controllers of the iPro.CHILL family can be applied in all cooling, heating and condensing units with up to four circuits and 16 compressors. The completeness and user-friendliness make them suitable for any type of unit, even the most complex.
  • Page 50: Ipro.chill Wiring Diagrams

    USER MANUAL – Release 1.2 of 01/01/2010 Page 50 of 191 Version: 02/03/2010 7. IPRO.CHILL WIRING DIAGRAMS IPC410D MODEL HARDWARE RESOURCES Power supply 24V AC/DC Digital inputs 20 opto-insulated with 10mA AC current on the contact Analogue inputs 10 configurables: 0÷5V, 4÷20mA, NTC, PTC, digital input Analogue outputs 2 configurable: 0÷10V, external relay driving, PWM signal 4 configurables: 0÷10V signal, external relay driving...
  • Page 51: Ipc415D Model Hardware Resources

    USER MANUAL – Release 1.2 of 01/01/2010 Page 51 of 191 Version: 02/03/2010 IPC415D MODEL HARDWARE RESOURCES Power supply 24V AC/DC Digital inputs 20 opto-insulated with 10mA AC current on the contact Analogue inputs 10 configurables: 0÷5V, 4÷20mA, NTC, PTC, digital input Analogue outputs 2 configurable: 0÷10V, external relay driving, PWM signal 4 configurables: 0÷10V signal, external relay driving...
  • Page 52: Ntc/Ptc Probes Analogue Inputs

    USER MANUAL – Release 1.2 of 01/01/2010 Page 52 of 191 Version: 02/03/2010 NTC/PTC PROBES ANALOGUE INPUTS PbC = Probes common terminal DIGITAL INPUTS GND = common inputs (terminals n° 50 and n° 61 are connected internally) 4÷20MA PRESSURE TRANSDUCERS ANALOGUE INPUTS...
  • Page 53: V Ratiometric Pressure Transducers Analogue Inputs

    USER MANUAL – Release 1.2 of 01/01/2010 Page 53 of 191 Version: 02/03/2010 0÷5V RATIOMETRIC PRESSURE TRANSDUCERS ANALOGUE INPUTS OUTDOOR FAN SPEED CONTROL PWM OUTPUTS Phase-cut modules are available with PWM input signal for proportional regulation only for 1-phase fans. WARNING: the PWM signal is compatible only with Dixell modules Phase cut module for outdoor fan speed control...
  • Page 54: Servomotors Control 0÷10V / 4÷20Ma Proportional Outputs

    USER MANUAL – Release 1.2 of 01/01/2010 Page 54 of 191 Version: 02/03/2010 Phase cut module for outdoor fan speed control SERVOMOTORS CONTROL 0÷10V / 4÷20MA PROPORTIONAL OUTPUTS GND = common OUT1 – OUT6 outputs configurable with 0÷10V signal OUT5 - OUT6 outputs also configurable with 4÷20mA signal...
  • Page 55: Proportional Outputs Configured For Piloting An External Relay

    USER MANUAL – Release 1.2 of 01/01/2010 Page 55 of 191 Version: 02/03/2010 7.10 PROPORTIONAL OUTPUTS CONFIGURED FOR PILOTING AN EXTERNAL RELAY GND = common It is possible to connect a relay with a 12 volt coil in continuous current with maximum absorption of 40 mA. 7.11 VGIPC REMOTE TERMINAL COLLECTION It is possible to connect up to two remote terminals in parallel, each with an NTC probe on board.
  • Page 56: Iproex60D Expansion Module

    USER MANUAL – Release 1.2 of 01/01/2010 Page 56 of 191 Version: 02/03/2010 8. IPROEX60D EXPANSION MODULE The following can be connected to the programmable devices of the iPro.CHILL range: the IPROEX60D expansion module to ease the increase of I/O available to the user. Up to 4 expansion modules IPROEX60D can be connected to the iPro.CHILL for increasing the I/O number.
  • Page 57: Iproex60D Expansion Module Wiring Diagrams

    USER MANUAL – Release 1.2 of 01/01/2010 Page 57 of 191 Version: 02/03/2010 9. IPROEX60D EXPANSION MODULE WIRING DIAGRAMS IPROEX60D EXPANSION MODEL HARDWARE RESOURCES Power supply 24V Ac/dc Digital inputs 3 opto-isolated with 10mA alternating current on the contact Analogue inputs 7 configurables 0÷1V, 0÷5V, 0÷10V, 2÷20 mA, 4÷20mA, NTC, PTC, digital input Analogue outputs 3 configurables with 0÷10V signal/external relay piloting...
  • Page 58: Expansion Module Connection To The Programmable Unit

    USER MANUAL – Release 1.2 of 01/01/2010 Page 58 of 191 Version: 02/03/2010 EXPANSION MODULE CONNECTION TO THE PROGRAMMABLE UNIT Using the CANBus serial output it is possible to connect up to a maximum of 4 expansion modules. Use the relevant DIP switch to determine an unmistakable address between the connected modules. Only use the connection between the GND terminals if there are communication problems between the modules.
  • Page 59: Electronic Thermostatic Valve Management Driver

    USER MANUAL – Release 1.2 of 01/01/2010 Page 59 of 191 Version: 02/03/2010 10. ELECTRONIC THERMOSTATIC VALVE MANAGEMENT DRIVER The XEV20D module is a driver for motorised electronic thermostatic valves (Stepper) of both the bipolar and unipolar type. Up to 4 driver modules XEV20D can be connected to the iPro.CHILL for driving up to 8 electronic expansion valves.
  • Page 60: Unipolar/Bipolar Valves Driver Connection Mode

    USER MANUAL – Release 1.2 of 01/01/2010 Page 60 of 191 Version: 02/03/2010 XEV20D can manage a large variety of motorised valves. The table below gives the maximum current values that the valve windings can absorb. Select the transformer suitable for the application on the basis of that stated in the table.
  • Page 61: Xev20D Electronic Thermostatic Driver Wiring Diagrams

    USER MANUAL – Release 1.2 of 01/01/2010 Page 61 of 191 Version: 02/03/2010 11. XEV20D ELECTRONIC THERMOSTATIC DRIVER WIRING DIAGRAMS 11.1 XEV20D DRIVER MODEL HARDWARE RESOURCES Power supply 24V Ac/dc Analogue inputs PB1 / PB2 configurable analogue inputs: NTC, PTC, Pt1000 PB3 / PB4 configurable analogue inputs: NTC, PTC, Pt1000,4÷20mA, 0÷5V Unipolar/bipolar model motorised valve motor piloting outputs Up to 2 (see product order code)
  • Page 62: Xev20D Driver Module Connection To The Programmable Unit

    USER MANUAL – Release 1.2 of 01/01/2010 Page 62 of 191 Version: 02/03/2010 11.2 XEV20D DRIVER MODULE CONNECTION TO THE PROGRAMMABLE UNIT Using the CANBus serial output it is possible to connect up to a maximum of 4 driver modules. Use the relevant DIP switch to determine an unmistakable address between the connected modules.
  • Page 63: Ntc / Ptc / Pt1000 Probe Analogue Inputs

    USER MANUAL – Release 1.2 of 01/01/2010 Page 63 of 191 Version: 02/03/2010 11.3 NTC / PTC / PT1000 PROBE ANALOGUE INPUTS PbC = common probes 11.4 0÷5V RATIOMETRIC PRESSURE TRANSDUCERS ANALOGUE INPUTS 11.5 4÷20MA PRESSURE TRANSDUCERS ANALOGUE INPUTS...
  • Page 64: Rs485 Serial Communication Peripherals Connection

    USER MANUAL – Release 1.2 of 01/01/2010 Page 64 of 191 Version: 02/03/2010 12. RS485 SERIAL COMMUNICATION PERIPHERALS CONNECTION 12.1 RS485 SERIAL LINE All compatible Modbus devices have an RS485 output. The devices with RS485 serial do not require any external module or any connection cable.
  • Page 65: Rs485 Master Serial Output Connection With Modbus Protocol

    USER MANUAL – Release 1.2 of 01/01/2010 Page 65 of 191 Version: 02/03/2010 12.2 RS485 MASTER SERIAL OUTPUT CONNECTION WITH MODBUS PROTOCOL Using the RS485 MASTER serial output it is possible to connect up to a maximum of 100 devices...
  • Page 66: Rs485 Slave Serial Output Connection With Modbus Protocol

    USER MANUAL – Release 1.2 of 01/01/2010 Page 66 of 191 Version: 02/03/2010 12.3 RS485 SLAVE SERIAL OUTPUT CONNECTION WITH MODBUS PROTOCOL Using the RS485 SLAVE serial output, it is possible to connect the iPro.CHILL programmable controller to the Dixell XWEB supervising systems or to applications developed by third party system integrators for complete control and supervision from local or remote.
  • Page 67: Remote Connection Via Modem

    USER MANUAL – Release 1.2 of 01/01/2010 Page 67 of 191 Version: 02/03/2010 13. REMOTE CONNECTION VIA MODEM 13.1 PC CONNECTION FROM REMOTE VIA SERIAL OR EXTERNAL GSM MODEM The iPro.CHILL series has a RS232 serial output on board (OPTIONAL) through which a serial cable can be used for connection to a GSM or external Dixell serial XWEB modem.
  • Page 68: Pc Connection From Remote Via Internal Serial Modem

    USER MANUAL – Release 1.2 of 01/01/2010 Page 68 of 191 Version: 02/03/2010 13.2 PC CONNECTION FROM REMOTE VIA INTERNAL SERIAL MODEM The iPro.CHILL range has an internal serial modem (OPTIONAL) through which it is possible to reach the programmable controller by means of a remote connection. Modem Connection (“or point to point connection”) It is the most used method where a LAN network connection is not available, (Intranet or Internet).
  • Page 69: Connection Via Intranet

    USER MANUAL – Release 1.2 of 01/01/2010 Page 69 of 191 Version: 02/03/2010 14.2 CONNECTION VIA INTRANET This type of connection will allow you to access the programmable controller from any PC connected to the network. Enter the address of the server into the Browser bar, memorise this address in favourites. The connection to the local network must be managed by qualified staff and the network administrator, who must firstly assign an IP number to the iPro.CHILL (an example could be http://192.168.000.111) WARNING: An automatic procedure will guide you through configuration.
  • Page 70: Using The Usb Port

    USER MANUAL – Release 1.2 of 01/01/2010 Page 70 of 191 Version: 02/03/2010 15. USING THE USB PORT 15.1 USB PORT (HOST) The iPro.CHILL range always has a USB port on board, through which the following can be performed using a standard pen drive: Download applications...
  • Page 71: User Interface

    USER MANUAL – Release 1.2 of 01/01/2010 Page 71 of 191 Version: 02/03/2010 16. USER INTERFACE Using the VISOGRAPH LCD graphic keyboard, it is possible to monitor and modify the status of the unit. On unit switch-on, the main screen will be the following If the unit is managed from remote or during switch-off from time period, the screen will be: If the unit has been configured as AIR-AIR, during clock off, it is possible to decide whether to enable ventilation or not, in this case the screen will be:...
  • Page 72: How To Modify The Information Present In The Main Screen

    USER MANUAL – Release 1.2 of 01/01/2010 Page 72 of 191 Version: 02/03/2010 16.1 HOW TO MODIFY THE INFORMATION PRESENT IN THE MAIN SCREEN To set the time and date, press the SERVICE key. Use the UP and DOWN keys to select the TIME/TIME PERIOD icon and press ENTER. To modify a element, position the cursor on the same and use the UP and DOWN cursors and press SET: The element starts to flash.
  • Page 73: Set Key

    USER MANUAL – Release 1.2 of 01/01/2010 Page 73 of 191 Version: 02/03/2010 to indicate that the condenser fans are working • (in the case of AIR-AIR or AIR-WATER unit configuration) If the alarms occur or particular working modes sub-enter, the following icons will be shown on the main screens: flashing to indicate that an alarm is active •...
  • Page 74: Probes Key

    USER MANUAL – Release 1.2 of 01/01/2010 Page 74 of 191 Version: 02/03/2010 The cursor will automatically position itself on the next element, to modify it repeat the operation just described. In this screen it is also possible to verify (but not modify) whether the energy saving mode and dynamic set are active;...
  • Page 75 USER MANUAL – Release 1.2 of 01/01/2010 Page 75 of 191 Version: 02/03/2010 Warning that the probes displayed are only those configured. In order to display the variables relative to the individual circuit, press the relative key. For example, if the variable of circuit 1 is to be displayed, press By pressing the key, all of the other variables of the circuit selected can be seen.
  • Page 76: Alarm Key

    USER MANUAL – Release 1.2 of 01/01/2010 Page 76 of 191 Version: 02/03/2010 16.5 ALARM KEY When an alarm occurs, the display shows the flashing icon and the buzzer starts to operate. Press any key to silence the buzzer. Moreover, the alarms key starts to flash alternately with the icons By pressing the key, pass to the alarms in progress screen: Three types of alarms can be present: Resettable...
  • Page 77 USER MANUAL – Release 1.2 of 01/01/2010 Page 77 of 191 Version: 02/03/2010 Via keys , set the password. • Press ENTER to confirm. • If the password is correct, the following message will be displayed: • If the password introduced is incorrect, the following message will be displayed: •...
  • Page 78: Circ Key

    USER MANUAL – Release 1.2 of 01/01/2010 Page 78 of 191 Version: 02/03/2010 16.6 CIRC KEY Using the CIRC key it is possible to monitor the situation of the unit. The information refers to: Circuits compressors status; the screen shows the compressors present for each circuit and the •...
  • Page 79 USER MANUAL – Release 1.2 of 01/01/2010 Page 79 of 191 Version: 02/03/2010 Status of the evaporator pump (or evaporator pumps if the support is present) • Status of the condenser pump (or of the pumps if the WATER-WATER support is present) •...
  • Page 80: Service Key

    USER MANUAL – Release 1.2 of 01/01/2010 Page 80 of 191 Version: 02/03/2010 16.7 SERVICE KEY By pressing the SERVICE key, enter the configuration of: Parameters Programming • Time/Time periods Programming • Compressors • Water pump • Alarms display • Historical alarms •...
  • Page 81 USER MANUAL – Release 1.2 of 01/01/2010 Page 81 of 191 Version: 02/03/2010 Pushing the key it’s possible to enter the Level 1 (Pr1) parameters without typing any password. To enter the Level 2 (Pr2) or Level 3 (Pr3) parameters the relevant password must be typed in level parameters –...
  • Page 82: Time/Time Bands

    USER MANUAL – Release 1.2 of 01/01/2010 Page 82 of 191 Version: 02/03/2010 16.7.2 Time/Time bands We have already seen previously that this menu is used for the time and date set. It is also possible to enable or disable the Energy Saving and/or automatic switch off of the time bands. By pressing the key, pass to the screen for the configuration of the three time bands.
  • Page 83: Compressors

    USER MANUAL – Release 1.2 of 01/01/2010 Page 83 of 191 Version: 02/03/2010 For every day of the week and for both functions, it is possible to manage: No time band • Band 1 • Band 2 • Band 1 and 2 •...
  • Page 84: Alarms Display

    USER MANUAL – Release 1.2 of 01/01/2010 Page 84 of 191 Version: 02/03/2010 To reset the working hours • To disable the pump (e.g. perform maintenance) • To reset working hours or disable/enable the pumps, follow the procedure described for the compressors. 16.7.5 Alarms display This menu contains the same information described in paragraph 16.5.
  • Page 85 USER MANUAL – Release 1.2 of 01/01/2010 Page 85 of 191 Version: 02/03/2010 Via keys ,set the password. • Press ENTER to confirm. • If the password is correct, the following message will be displayed: • If the password introduced is incorrect, the following message will be displayed: •...
  • Page 86: Defrost

    USER MANUAL – Release 1.2 of 01/01/2010 Page 86 of 191 Version: 02/03/2010 16.7.7 Defrost In this screen it is possible to check the status of the defrost cycle for every circuit present: By selecting the circuit affected and pressing ENTER, pass to the following screen. key allows forcing of the defrost cycle.
  • Page 87: I/O Status

    USER MANUAL – Release 1.2 of 01/01/2010 Page 87 of 191 Version: 02/03/2010 16.7.9 I/O status This menu allows to display the status of all inputs and outputs that have been defined. The I/O units have been divided by groups, as in the screen below: By pressing the ENTER key, it is possible to enter every I/O unit.
  • Page 88: Heat Recovery

    USER MANUAL – Release 1.2 of 01/01/2010 Page 88 of 191 Version: 02/03/2010 16.7.11 Heat recovery Using this menu it is possible to verify the recovery working status. key enables the recovery working. The following information may be available: Status of the recovery function: •...
  • Page 89: Free-Cooling

    USER MANUAL – Release 1.2 of 01/01/2010 Page 89 of 191 Version: 02/03/2010 16.7.13 Free-cooling Using this menu it is possible to verify the free cooling working status. key enables the free cooling working. The following information may be available: Status of the free cooling function: •...
  • Page 90: Screw Compressor

    USER MANUAL – Release 1.2 of 01/01/2010 Page 90 of 191 Version: 02/03/2010 16.7.14 Screw compressor This menu can be used to monitor the working status of the screw compressor in the various circuits. The Set and Differential values can be modified. By selecting the desired circuit and pressing ENTER, the following information can be displayed: 16.7.15 Control panel Your own LCD keyboard can be customised in this menu.
  • Page 91: Unit Switch Off

    USER MANUAL – Release 1.2 of 01/01/2010 Page 91 of 191 Version: 02/03/2010 17. SELECTION – WORKING MODE – ENABLING – SWITCH-ON – UNIT SWITCH UNIT SWITCH-ON AND SWITCH-OFF CAN TAKE PLACE: From the keyboard • By time bands (see switch-on/off with time bands) •...
  • Page 92: Change Over Function

    USER MANUAL – Release 1.2 of 01/01/2010 Page 92 of 191 Version: 02/03/2010 AUTOMATIC WORKING SELECTION IN COOLING-HEATING MODE FROM DIGITAL INPUT Par. SP07 = 1 The switch-on selection of a unit configured for cooling and heating takes place from digital inputs configured as remote Heat/Cool request.
  • Page 93: Cooling – Heating Mode Selection From Keyboard

    USER MANUAL – Release 1.2 of 01/01/2010 Page 93 of 191 Version: 02/03/2010 COOLING – HEATING MODE SELECTION FROM KEYBOARD 17.5 SP06 = 0 By pressing the key, the unit is switched-on in cooling mode, pressing the key, the unit is switched-on in heating mode.
  • Page 94: Working With Digital Input Configured As Temperature Control Request

    USER MANUAL – Release 1.2 of 01/01/2010 Page 94 of 191 Version: 02/03/2010 19.1 WORKING WITH DIGITAL INPUT CONFIGURED AS TEMPERATURE CONTROL REQUEST Unit configured as motor-condensing CF04 = 1. Temperature control request digital input (motor-condensing) With contact NOT ACTIVE unit in OFF •...
  • Page 95: Compressor Temperature Control In Heating Mode

    USER MANUAL – Release 1.2 of 01/01/2010 Page 95 of 191 Version: 02/03/2010 20.2 COMPRESSOR TEMPERATURE CONTROL IN HEATING MODE The Par. ST10 defines the probe for unit temperature control (if ST12= 1 just of circuit n° 1) in heating working mode 0= Evaporator inlet NTC temperature probe 1= Evaporator n°...
  • Page 96: Compressors Proportional Temperature Control Graphics (Unit)

    USER MANUAL – Release 1.2 of 01/01/2010 Page 96 of 191 Version: 02/03/2010 21.1 COMPRESSORS PROPORTIONAL TEMPERATURE CONTROL GRAPHICS (UNIT) Compressors regulator working in cooling mode graphics (if ST12 = 1 just of circuit n° 1) Compressors regulator function in heating mode graphics (if ST12 = 1 just in circuit n° 1)
  • Page 97: Circuit N° 2 Compressors Proportional Temperature Control Graphics

    USER MANUAL – Release 1.2 of 01/01/2010 Page 97 of 191 Version: 02/03/2010 21.2 CIRCUIT N° 2 COMPRESSORS PROPORTIONAL TEMPERATURE CONTROL GRAPHICS Compressors regulator working in cooling mode graphics with ST12 = 1 Compressors regulator working in heating mode graphics with ST12 = 1...
  • Page 98: Compressors Neutral Zone Temperature Control Graphics

    USER MANUAL – Release 1.2 of 01/01/2010 Page 98 of 191 Version: 02/03/2010 21.3 COMPRESSORS NEUTRAL ZONE TEMPERATURE CONTROL GRAPHICS Compressors regulator function in cooling mode graphics If ST12 = 1 the working set point of the second circuit is ST13 and the band is ST19 Compressors regulator working in heating mode graphics If ST12 = 1 the working set point of the second circuit is ST16 and the band is ST20...
  • Page 99: Working Description

    USER MANUAL – Release 1.2 of 01/01/2010 Page 99 of 191 Version: 02/03/2010 21.4 WORKING DESCRIPTION While the controlled variable (defined on parameter ST09 for cooling mode and ST10 for heating mode) remains inside the neutral zone nothing happens in terms of activation or disabling of compressors/capacity steps.
  • Page 100: Dynamic Set-Point Working Graphics

    USER MANUAL – Release 1.2 of 01/01/2010 Page 100 of 191 Version: 02/03/2010 23.1 DYNAMIC SET-POINT WORKING GRAPHICS 4÷20 ma probe configured as 4..20 mA input NTC probe with positive differential NTC probe with negative differential 24. ENERGY SAVING FROM ID FUNCTION The ES request is active: If one of the digital inputs configured as ES is active 25.
  • Page 101: Compressors Temperature Control Rotation Control

    USER MANUAL – Release 1.2 of 01/01/2010 Page 101 of 191 Version: 02/03/2010 26. COMPRESSORS TEMPERATURE CONTROL ROTATION CONTROL Manages working of the compressors in cooling and heating unit in up to 4 circuits with a maximum of 4 compressors per circuit. Notes The function manages the rotations and the switch-on/off times of the compressors of a unit with 4 circuits and 4 compressors per circuit.
  • Page 102: Selection Of The Circuit For Saturation

    USER MANUAL – Release 1.2 of 01/01/2010 Page 102 of 191 Version: 02/03/2010 26.7 SELECTION OF THE CIRCUIT FOR SATURATION Before switching a new circuit on all resources of the circuits already on are activated. Switch-on: the circuit is selected which in that moment has the greatest number of resources engaged. If the resources used are the same, the circuit is selected that can switch the compressor on with the least "n°...
  • Page 103: Compressors Switch-On

    USER MANUAL – Release 1.2 of 01/01/2010 Page 103 of 191 Version: 02/03/2010 If a N° of peaks set in the parameter is reached by a compressor in 1 working hour (maximum n° of compressor peaks per hour), in the case of other available steps the next temperature control request is turned to the latter.
  • Page 104: Description Of Part Winding Start-Up

    USER MANUAL – Release 1.2 of 01/01/2010 Page 104 of 191 Version: 02/03/2010 27.4 DESCRIPTION OF PART WINDING START-UP This type of start-up allows to drastically reduce the peak current on compressor start-up. It is used with alternative hermetic, semi-hermetic or screw compressors with medium-large dimensions. Two relay outputs must be configured for every compressor: One as compressor 1 PW start-up n°...
  • Page 105: Star Delta Start-Up Of A Partialised Compressor

    USER MANUAL – Release 1.2 of 01/01/2010 Page 105 of 191 Version: 02/03/2010 Fig. 3 27.9 STAR DELTA START-UP OF A PARTIALISED COMPRESSOR The start-up procedure is the same as that stated above (par. 14.8). If compressor/s with partialisations have been configured, if switch-on is requested at full compressor load, first the partialisation solenoid is excited (always the step with the lowest index, the part.
  • Page 106 USER MANUAL – Release 1.2 of 01/01/2010 Page 106 of 191 Version: 02/03/2010 Par CO08=2 continuous insertion with reverse action steps 2= continuous insertion the partialisation steps are all inserted/removed on the basis of the polarity chosen. In the case of partialisation request due to temperature control, only the requested step is inserted/removed. The others all remain inserted/removed on the basis of the polarity chosen.
  • Page 107: Start-Up With Partialised Compressor / Idle Start-Up

    USER MANUAL – Release 1.2 of 01/01/2010 Page 107 of 191 Version: 02/03/2010 WARNING If a configuration is used of the continuous insertion partialisations management with direct or reverse action, in the case of 50% or 75% or 100% call, the 25% valve is forced to allow working of the other partialisation steps.
  • Page 108: Compressor Liquid Injection Solenoid Valve Function

    USER MANUAL – Release 1.2 of 01/01/2010 Page 108 of 191 Version: 02/03/2010 29. COMPRESSOR LIQUID INJECTION SOLENOID VALVE FUNCTION Four relay outputs are available for the management of a liquid injection solenoid valve for the compressor n° 1 / 2 / 3 / 4 The function is active for the compressor if: If a relay output is configured as a compressor liquid injection solenoid valve and an analogue output as a compressor discharge temperature PTC probe.
  • Page 109 USER MANUAL – Release 1.2 of 01/01/2010 Page 109 of 191 Version: 02/03/2010 Working example in heating mode Fig. 1 0 – 100% regulation of a modulating compressor Fig. 2 compressor multi-unit regulation equipped with a 2-step modulating compressor Fig. 3 compressor multi-unit regulation equipped with a 3-step modulating compressor Circuit n°1 Circuit n°...
  • Page 110: Compressors In Tandem

    USER MANUAL – Release 1.2 of 01/01/2010 Page 110 of 191 Version: 02/03/2010 If a N° of peaks set in the parameter is reached by a compressor in 15 working minutes (maximum n° of compressor peaks), in the case of other available steps the next temperature control request is turned to the latter. 32.
  • Page 111: Evaporator Water Pump Rotation

    USER MANUAL – Release 1.2 of 01/01/2010 Page 111 of 191 Version: 02/03/2010 35. EVAPORATOR WATER PUMP ROTATION 35.1 2 RELAYS CONFIGURED AS EVAPORATOR WATER PUMP If 2 relays are configured on as evaporator water pump and one as evaporator support water pump, pumping unit management is enabled.
  • Page 112: Water Pump Maintenance Request Function

    USER MANUAL – Release 1.2 of 01/01/2010 Page 112 of 191 Version: 02/03/2010 5= regulates on 1 / 2 / 3 / 4 evaporator outlet and common outlet 6= regulates on external air temperature Par. PA11 = Pump activation set-point in anti-freeze working mode on temperature control probe Par.
  • Page 113: Hot Start Function

    USER MANUAL – Release 1.2 of 01/01/2010 Page 113 of 191 Version: 02/03/2010 dF31 Supply fan block during defrost 0= Not enabled 1= Enabled 38.2 HOT START FUNCTION This function is only active with air/air units configured as heatings. It allows start-up of the supply fan only if the temperature of the condensing coil is sufficiently hot.
  • Page 114: Condenser Water Pump Rotation

    USER MANUAL – Release 1.2 of 01/01/2010 Page 114 of 191 Version: 02/03/2010 (in defrost mode in the periods in which the compressor is in OFF mode for dripping, the pump remains on) If only one pump is configured, the pump keeps working; if two pumps are configured, there is the rotation.
  • Page 115: Water Pump Maintenance Request Function

    USER MANUAL – Release 1.2 of 01/01/2010 Page 115 of 191 Version: 02/03/2010 1= regulates common condenser water inlet probe 2= regulates common condenser water inlet probe and 1 / 2 condenser input 3= regulates common condenser water inlet probe and 3 / 4 condenser input 4= regulates 1 / 2 condenser water outlet probe 5= regulates 3 / 4 condenser water outlet probe 6= regulates on 1 / 2 / 3 / 4 condenser outlet...
  • Page 116: Pump-Down Function With Circuit Low Pressure Pressure Switch

    USER MANUAL – Release 1.2 of 01/01/2010 Page 116 of 191 Version: 02/03/2010 Exceeding (upwards) the threshold set in parameter PD02 added to the hysterisis set in parameter • PD03 by the pressure detected by the circuit LP transducer. Exceeding the maximum duration of the pump-down cycle defined at parameter PD04. In this case, a •...
  • Page 117: Working Examples

    USER MANUAL – Release 1.2 of 01/01/2010 Page 117 of 191 Version: 02/03/2010 WARNING: In the case of pump-down from dedicated pressure switch or analogue input, it is possible that the pressure at which compressor/step switch-off is allowed is lower than the activation threshold of the LP pressure switch.
  • Page 118: Pump-Down Active In Shut-Down And In Re-Start, Based On The Analogue Input Relative To The Evaporation Pressure

    USER MANUAL – Release 1.2 of 01/01/2010 Page 118 of 191 Version: 02/03/2010 2.1. The deactivation pressure of the pump-down pressure switch is higher than the deactivation pressure of the LP pressure switch: in this case, the rising pressure will deactivate the LP pressure switch before the pump-down pressure switch, therefore there is no risk of LP alarms on re-start.
  • Page 119: Circuits Unloading

    USER MANUAL – Release 1.2 of 01/01/2010 Page 119 of 191 Version: 02/03/2010 0= remains at automatic reset even if the number of interventions/hour are reached 1=enables manual reset on reaching the number of interventions/hour 45. CIRCUITS UNLOADING It manages the forced partialisation of the cooling circuits when the unit is working in critical working conditions.
  • Page 120: Unloading From Condensation High Temperature Transducer

    USER MANUAL – Release 1.2 of 01/01/2010 Page 120 of 191 Version: 02/03/2010 When the temperature measured is less than or equal to the Set - Diff. The unloading function is deactivated or however, to prevent prolonged working in unloading with temperature conditions between activation set and deactivation differential, when the condensation temperature is below the set, the time set is counted.
  • Page 121: Unloading By Low Pressure Transducer

    USER MANUAL – Release 1.2 of 01/01/2010 Page 121 of 191 Version: 02/03/2010 45.3 UNLOADING BY LOW PRESSURE TRANSDUCER The low pressure unloading function is only active with unit working in heating mode. The function is managed by means of the analogue input configured as circuit evaporation pressure probe FUNCTION ACTIVATED: If the pressure measured by the evaporation probe is equal to or exceeds the set for a time that can be set, the unloading function of the circuit to which the probe belongs is activated.
  • Page 122: Working In Unloading Mode Notes

    USER MANUAL – Release 1.2 of 01/01/2010 Page 122 of 191 Version: 02/03/2010 Manages the unloading on unit water side. The function is always active and enabled in any working mode: Example of working Unit with just 1 compressor per circuit and 3 circuits configured, steps available 3 and the Par. Un16 •...
  • Page 123: If The Pwm/ 0÷10V Signal Triac Output Is Used

    USER MANUAL – Release 1.2 of 01/01/2010 Page 123 of 191 Version: 02/03/2010 Par. FA02 fan working mode 0 = depends on the compressor, fans only active if compressor is active 1 = independent from the active fans compressor with selected working mode off in stand-by/OFF FA01 –...
  • Page 124: Unique Or Separate Condensation

    USER MANUAL – Release 1.2 of 01/01/2010 Page 124 of 191 Version: 02/03/2010 Step n°2 relay out Step N° 2 OFF Step N° 2 ON Step N° 2 OFF Step N° 2 OFF Step n°3 relay out Step N° 3 OFF Step N°...
  • Page 125: Proportional Fan Regulator Graphics

    USER MANUAL – Release 1.2 of 01/01/2010 Page 125 of 191 Version: 02/03/2010 46.4 PROPORTIONAL FAN REGULATOR GRAPHICS 46.5 CONDENSATION FAN REGULATOR ON / OFF IN COOLING MODE GRAPHICS 46.6 CONDENSATION FAN REGULATOR ON / OFF IN HEATING MODE GRAPHICS...
  • Page 126: Anti-Freeze/Support Heaters Regulator

    USER MANUAL – Release 1.2 of 01/01/2010 Page 126 of 191 Version: 02/03/2010 47. ANTI-FREEZE/SUPPORT HEATERS REGULATOR 47.1 HEATER OUTPUT WORKING IN COOLING OR HEATING MODE Par. Ar10 Determines the working of the anti-freeze heaters when the device is in cooling or heating working mode.
  • Page 127: Support/Anti-Freeze/Boiler Heaters Working Graphics

    USER MANUAL – Release 1.2 of 01/01/2010 Page 127 of 191 Version: 02/03/2010 47.5 SUPPORT/ANTI-FREEZE/BOILER HEATERS WORKING GRAPHICS 47.6 TEMPERATURE CONTROL OF THE EVAPORATOR ANTI-FREEZE HEATERS It depends on the configuration of the relay outputs configured as circuit heater and by the choice of the NTC probe/s prepared for their control.
  • Page 128: Temperature Control Of The Boiler Heaters (Anti-Freeze) Boiler Function

    USER MANUAL – Release 1.2 of 01/01/2010 Page 128 of 191 Version: 02/03/2010 WARNING It is not possible to command the circuit n° 1 heaters relay output with the circuit n° 2 condenser water outlet probe and vice versa, the same for the remaining circuits. 47.8 TEMPERATURE CONTROL OF THE BOILER HEATERS (ANTI-FREEZE) BOILER FUNCTION Check electric heaters in cooling heating working mode.
  • Page 129: Anti-Freeze Heaters Working From Digital Input

    USER MANUAL – Release 1.2 of 01/01/2010 Page 129 of 191 Version: 02/03/2010 WORKING OF THE BOILER HEATERS DURING THE DEFROST CYCLE The parameter Ar05 establishes working of the boiler heaters (anti-freeze) during the defrost cycle. If the value is 0 during the defrost cycle the heaters are only activated by their temperature control. If the value is 1, the heaters are always on during the defrost cycle: they switch on when the reversing valve converts working from heating to cooling and they switch off when the dripping time has ended and the compressor re-starts.
  • Page 130 USER MANUAL – Release 1.2 of 01/01/2010 Page 130 of 191 Version: 02/03/2010 if the temperature measured by the condensation or evaporation probe < dF10 for circuit n° 1,< dF11 • for circuit n° 2,< dF12 for circuit n° 3,< dF13 for circuit n° 4 go to phase 3 otherwise wait to satisfy the dF10/dF14 set •...
  • Page 131 USER MANUAL – Release 1.2 of 01/01/2010 Page 131 of 191 Version: 02/03/2010 PHASE 4: defrost This phase must always be performed In this phase: If dF23=0 the condensation fans are always off If dF23=1 the condensation fans start if the condensation pressure/temperature > dF24 and their normal regulation follows with the cooling set.
  • Page 132: Description Of Defrost Parameters

    USER MANUAL – Release 1.2 of 01/01/2010 Page 132 of 191 Version: 02/03/2010 49.1 DESCRIPTION OF DEFROST PARAMETERS dF01 Determines the type of defrost mode 0 = Defrost disabled 1 = Defrost in temperature/pressure. The dF09 defrost interval count takes place when the temperature drops below the dF02 set.
  • Page 133 USER MANUAL – Release 1.2 of 01/01/2010 Page 133 of 191 Version: 02/03/2010 At the end of the dF09 time count the device sees the temperature of the circuit n° 3 combined defrost NTC probe. If the temperature is below the dF12 set, the defrost procedure is performed otherwise it continues to function in heating mode.
  • Page 134: Defrost With Condensation Fans

    USER MANUAL – Release 1.2 of 01/01/2010 Page 134 of 191 Version: 02/03/2010 2= start with condensation temperature/pressure probe end with evaporation pressure probe 3= start and end due to evaporation pressure dF29 minimum stand-by time before forced defrost allows to set a delay when inserting the forced defrost function dF30 forced defrost temperature/pressure set Allows to set a temperature/pressure set below which the dF29 count starts.
  • Page 135: Heat Recovery Working From Digital Input

    USER MANUAL – Release 1.2 of 01/01/2010 Page 135 of 191 Version: 02/03/2010 Resources necessary for circuit working in heat recovery mode On the basis of the circuits enabled, the respective outputs configured as circuit n° recovery valve Analogue input configured as: condenser water common inlet NTC temperature probe •...
  • Page 136: Unit With Two Parallel Hydraulic Circuits

    USER MANUAL – Release 1.2 of 01/01/2010 Page 136 of 191 Version: 02/03/2010 Circuit n° configured with more than one power step (e.g. circuit configured with 3 compressors). When the time set in the par. rC04= minimum working time in heat recovery mode has passed, the insertion of other steps is prevented for the time cR02 if the recovery request expires.
  • Page 137 USER MANUAL – Release 1.2 of 01/01/2010 Page 137 of 191 Version: 02/03/2010 ENTRY - EXIT FROM HEAT RECOVERY MODE OF THE CIRCUITS CONFIGURED WITH A POWER STEP Both on entry and exit from recovery mode, the delay times rC02 and rC03 are not considered and the recovery valve is activated or deactivated immediately.
  • Page 138: Heat Recovery Working By Means Of Temperature Probe

    USER MANUAL – Release 1.2 of 01/01/2010 Page 138 of 191 Version: 02/03/2010 52. HEAT RECOVERY WORKING BY MEANS OF TEMPERATURE PROBE The heat recovery requests can be managed by the temperature probe positioned on the heat recovery units. Thermostating is proportional, as described below: By means of Par.
  • Page 139: Heat Recovery Side Priority

    USER MANUAL – Release 1.2 of 01/01/2010 Page 139 of 191 Version: 02/03/2010 52.2 HEAT RECOVERY SIDE PRIORITY rC02 = 1 Heat recovery side priority Heat recovery working mode is obtained only if the unit is in cooling mode on call of the recovery temperature control.
  • Page 140: Function For Production Of Domestic Hot Water

    USER MANUAL – Release 1.2 of 01/01/2010 Page 140 of 191 Version: 02/03/2010 53. FUNCTION FOR PRODUCTION OF DOMESTIC HOT WATER The function is enabled with the unit ON. In OFF or STD-BY the function is disabled. In this mode the two temperature probes must be configured: •...
  • Page 141: Management Of The Domestic Hot Water Pump

    USER MANUAL – Release 1.2 of 01/01/2010 Page 141 of 191 Version: 02/03/2010 Maximum time for reaching the domestic hot water production set-point From when the production of domestic hot water is requested, a timer is activated that determines the maximum time for the domestic hot water set-point to be reached.
  • Page 142: Continuous Working Of The Domestic Hot Water Pump

    USER MANUAL – Release 1.2 of 01/01/2010 Page 142 of 191 Version: 02/03/2010 53.1.1 CONTINUOUS WORKING OF THE DOMESTIC HOT WATER PUMP If the parameter FS28 =1 (domestic hot water pump operational mode), domestic hot water pump switch-on is linked to unit switch-on. In this case, times FS26 and FS28 are not considered. ANTILEGIONELLA FUNCTION 53.2 The antilegionella function can be activated using parameter FS12.
  • Page 143: Solar Panels Water Pump

    USER MANUAL – Release 1.2 of 01/01/2010 Page 143 of 191 Version: 02/03/2010 The status of the solar panels water pump depends on the value of two probes: • NTC domestic hot water temperature probe n. 1 • Solar panels NTC temperature probe If the temperature detected by the solar panels probe is higher than that detected by the domestic hot water probe n.
  • Page 144: Domestic Hot Water During Working In Winter Mode

    USER MANUAL – Release 1.2 of 01/01/2010 Page 144 of 191 Version: 02/03/2010 53.6.3 DEFROST OF THE AIR-WATER UNITS (ONLY WITH CF02=2 O CF02=3) Defrost has priority over the production of domestic hot water. If the controller determines the necessity to perform a defrost cycle while the production of domestic hot water is active, the following steps are taken: Passage to the production of heating water by activating output 2 and, after the delay FS10, by •...
  • Page 145: 53.7.3 Production Of Domestic Hot Water During Working In Summer Cycle

    USER MANUAL – Release 1.2 of 01/01/2010 Page 145 of 191 Version: 02/03/2010 In the pluri-circuit units for the same purpose, the circuits that are not defrost are forced to produce hot water for the utilities. 53.7.3 PRODUCTION OF DOMESTIC HOT WATER DURING WORKING IN SUMMER CYCLE (ONLY UNITS WITH CF02 =3) Whenever domestic hot water is requested, the following cases must be discriminated: a) One or more compressors are on for the production of chilled water...
  • Page 146: Management Of The Refrigerant Load In The Case Of Domestic Hot Water Production In The Summer Cycle

    USER MANUAL – Release 1.2 of 01/01/2010 Page 146 of 191 Version: 02/03/2010 • Output 2 is activated for the production of domestic hot water • After the delay FS10, the output 1 is deactivated for the production of domestic hot water and the compressors •...
  • Page 147: Free Cooling

    USER MANUAL – Release 1.2 of 01/01/2010 Page 147 of 191 Version: 02/03/2010 54. FREE COOLING RESOURCES TO BE CONFIGURED 54.1 54.1.1 ANALOGUE INPUTS Evaporator inlet NTC temperature probe System water inlet (free-cooling) NTC temperature probe External air/water temperature (free-cooling) NTC temperature probe 54.1.2 DIGITAL OUTPUTS Relay output configured as free-cooling ON/OFF valve Relay outputs configured as fractioned coil solenoid...
  • Page 148: Free-Cooling With External Ventilation Layout

    USER MANUAL – Release 1.2 of 01/01/2010 Page 148 of 191 Version: 02/03/2010 FREE-COOLING WITH EXTERNAL VENTILATION LAYOUT 54.3 Relay output configured as external free-cooling goes into ON when: the free-cooling ON/OFF relay output is ON • the free-cooling mixer valve analogue output is in regulation mode •...
  • Page 149: Free-Cooling Working In Heating Mode

    USER MANUAL – Release 1.2 of 01/01/2010 Page 149 of 191 Version: 02/03/2010 In the same way, the analogue output (piloting the relative proportional 3-way valve) will assume a value from 0 to 10V always depending on the temperature detected by the temperature control probe: If the temperature difference between the value detected by the system water inlet probe and that detected by the external air probe drops below the value set in the Input differential/free-cooling outlet (FC02) parameter for the Input/free-cooling output time delay (FC03) the free-cooling ON/OFF output is...
  • Page 150: Free Cooling Ventilation Working Mode

    USER MANUAL – Release 1.2 of 01/01/2010 Page 150 of 191 Version: 02/03/2010 FREE COOLING VENTILATION WORKING MODE 54.7 If FC01 = 2 and FC06 =1 the ventilation of the unit follows the regulation indicated in the graphics below: Steps Proportional In the same way, if FC01=3 the external fans will be activated from the free cooling ON/OFF ventilation relay output, piloted according to the layout below:...
  • Page 151: Auxiliary Relay Function

    USER MANUAL – Release 1.2 of 01/01/2010 Page 151 of 191 Version: 02/03/2010 55. AUXILIARY RELAY FUNCTION One completely configurable relay output per circuit is available to the user, also released from normal working of the controlled unit. The relay outputs can be managed by analogue inputs in dedicated temperature or pressure mode (circuit n° auxiliary output NTC temperature probe or circuit n°...
  • Page 152: Working Of The Auxiliary Analogue Outputs (0÷10 Volt)

    USER MANUAL – Release 1.2 of 01/01/2010 Page 152 of 191 Version: 02/03/2010 56. WORKING OF THE AUXILIARY ANALOGUE OUTPUTS (0÷10 VOLT) The regulation is carried out according to the following graphics: Auxiliary output 1 / 2 / 3 / 4 direct action Auxiliary output 1/ 2 / 3 / 4 direct action Auxiliary output 1 / 2 / 3 / 4 reverse action Auxiliary output 1/ 2 / 3 / 4 reverse action...
  • Page 153: Alarms

    USER MANUAL – Release 1.2 of 01/01/2010 Page 153 of 191 Version: 02/03/2010 57. ALARMS The alarm codes and signals are made up from letters and numbers that identify the different types. Types of alarm: Letter A = unit alarm •...
  • Page 154: Probe Breakdown

    USER MANUAL – Release 1.2 of 01/01/2010 Page 154 of 191 Version: 02/03/2010 PROBE BREAKDOWN 57.2 Display label meaning AP1 probe alarm PB1 -…AP10 probe alarm PB10 Cause of activation Probe configures and value converted out of range Reset Probe not configures or value converted within range Reset Automatic Icon...
  • Page 155: Compressor Flow High Temperature Alarm From Digital Input

    USER MANUAL – Release 1.2 of 01/01/2010 Page 155 of 191 Version: 02/03/2010 Condensation ventilation If the Par. FA02= 0 fan working mode dependent on the compressor. With alarm active the fans are forced to maximum speed for 60 seconds before switching-off If the Par.
  • Page 156: Low Pressure Pressure Switch Alarm

    USER MANUAL – Release 1.2 of 01/01/2010 Page 156 of 191 Version: 02/03/2010 LOW PRESSURE PRESSURE SWITCH ALARM 57.5 Display label meaning LP1…LP4 (circuit n° 1…4 low pressure pressure switch alarm) Cause of activation With circuit low pressure pressure switch active •...
  • Page 157: Oil Float/Pressure Switch Alarm

    USER MANUAL – Release 1.2 of 01/01/2010 Page 157 of 191 Version: 02/03/2010 OIL FLOAT/PRESSURE SWITCH ALARM 57.6 Display label meaning OPC1…OPC16 (compressor n°1…16 oil pressure switch alarm) Cause of activation The alarm is not signalled: on compressor switch-on for the time AL12. After time AL12 it is not signalled with unit in normal working conditions for time AL13 Reset...
  • Page 158: Condensation Temperature/High Pressure Alarm

    USER MANUAL – Release 1.2 of 01/01/2010 Page 158 of 191 Version: 02/03/2010 CONDENSATION TEMPERATURE/HIGH PRESSURE ALARM 57.7 Display label meaning hp1…hp4 (circuit n° 1…4 analogue input high pressure) Cause of activation With unit working in cooling or heating mode, if the condensation control probe measures a value >...
  • Page 159 USER MANUAL – Release 1.2 of 01/01/2010 Page 159 of 191 Version: 02/03/2010 LOW CONDENSATION TEMPERATURE/PRESSURE (IF THE LOW PRESSURE 57.8 TRANSDUCERS ARE NOT USED) Display label meaning b1lP (circuit n° 1 analogue input low pressure) b2lP (circuit n° 2 analogue input low pressure) b3lP (circuit n°...
  • Page 160 USER MANUAL – Release 1.2 of 01/01/2010 Page 160 of 191 Version: 02/03/2010 LOW EVAPORATION PRESSURE IF THE LOW PRESSURE TRANSDUCERS 57.9 ARE USED Warning, if low pressure transducers are configured, the low pressure alarm regulation only takes place on the same.
  • Page 161 USER MANUAL – Release 1.2 of 01/01/2010 Page 161 of 191 Version: 02/03/2010 AIR/AIR UNIT EVAPORATOR/CONDENSER AIR OUTLET LOW TEMPERATURE 57.10 IN COOLING WORKING MODE ANTI-FREEZE ALARM Display label meaning b1AC..b4AC (anti-freeze alarm in circuit n° 1..4 cooling working mode) b1Ac..b4Ac (anti-freeze alarm signal in circuit n°...
  • Page 162 USER MANUAL – Release 1.2 of 01/01/2010 Page 162 of 191 Version: 02/03/2010 AIR/AIR UNIT EVAPORATOR/CONDENSER AIR OUTLET LOW TEMPERATURE 57.11 IN HEATING WORKING MODE ANTI-FREEZE ALARM Display label meaning b1AH..b4AH (anti-freeze alarm in circuit n° 1..4 heating working mode) b1Ah..b4Ah (anti-freeze alarm signal in circuit n°...
  • Page 163: Cold Side Flow Switch Alarm (Differential Pressure Switch)

    USER MANUAL – Release 1.2 of 01/01/2010 Page 163 of 191 Version: 02/03/2010 COLD SIDE FLOW SWITCH ALARM (DIFFERENTIAL PRESSURE SWITCH) 57.12 Display label meaning AEFL (evaporator side flow switch alarm) Cause of activation (the flow switch alarm is only active in the units configured as air/water - water/water) ID active for the AL16 time from water pump start-up, after ID active for AL18 time...
  • Page 164: Hot Side Flow Switch Alarm (Differential Pressure Switch)

    USER MANUAL – Release 1.2 of 01/01/2010 Page 164 of 191 Version: 02/03/2010 HOT SIDE FLOW SWITCH ALARM (DIFFERENTIAL PRESSURE SWITCH) 57.13 Display label meaning ACFL (Condenser side flow switch alarm) Cause of activation (the flow switch alarm is only active in the units configured as air/water - water/water) ID active for the AL22 time from water pump start-up (alarm by-pass time), after ID active for AL24 time...
  • Page 165 USER MANUAL – Release 1.2 of 01/01/2010 Page 165 of 191 Version: 02/03/2010 FLOW SWITCH ALARM NOTES PA1 / PA17=0 No water pump The alarm is only managed if a digital input configured as flow switch always has automatic reset. PA1 / PA17=1 Water pump with continuous working.
  • Page 166: Supply Fan Circuit Breaker Alarm

    USER MANUAL – Release 1.2 of 01/01/2010 Page 166 of 191 Version: 02/03/2010 SUPPLY FAN CIRCUIT BREAKER ALARM 57.14 Display label meaning AtSF (Flow fan circuit breaker alarm) Cause of activation If CF01 = 0 with ID active On fan start-up, the alarm is ignored for time AL16 Reset ID not active Reset...
  • Page 167: Domestic Hot Water Pump Flow Switch Alarm

    USER MANUAL – Release 1.2 of 01/01/2010 Page 167 of 191 Version: 02/03/2010 DOMESTIC HOT WATER PUMP FLOW SWITCH ALARM 57.15 Display label meaning AHFL (domestic hot water pump flow switch alarm) Cause of activation (the flow switch alarm is only active with FS01 ! 0) ID active for the AL16 time from water pump start-up, after ID active for AL18 time Reset...
  • Page 168: Circuit Breaker Alarm

    USER MANUAL – Release 1.2 of 01/01/2010 Page 168 of 191 Version: 02/03/2010 CIRCUIT BREAKER ALARM 57.17 Display label meaning C1tr (compressor n° 1 circuit breaker alarm) -…C16tr (compressor n° 16 circuit breaker alarm) Cause of activation The alarm is not detected for AL27 on compressor switch-on With ID active The alarm is not detected with compressor off if AL30=0 Reset...
  • Page 169: Evaporator Water Inlet High Temperature Alarm

    USER MANUAL – Release 1.2 of 01/01/2010 Page 169 of 191 Version: 02/03/2010 DISCHARGE COMPRESSORS HIGH TEMPERATURE ALARM FROM 57.18 ANALOGUE INPUT Display label meaning C1dt…C16dt (compressor n° 1…16 high discharge temperature alarm) Cause of activation The temperature measured by the probe configured as discharge high temperature >...
  • Page 170: Condensation Fan Circuit Breaker Alarm

    USER MANUAL – Release 1.2 of 01/01/2010 Page 170 of 191 Version: 02/03/2010 The alarm remains in stand-by, OFF remote or with compressor off due to temperature control only if it was present before and with MANUAL reset. CONDENSATION FAN CIRCUIT BREAKER ALARM 57.20 Display label meaning b1tF (circuit n°...
  • Page 171: Defrost Alarm

    USER MANUAL – Release 1.2 of 01/01/2010 Page 171 of 191 Version: 02/03/2010 DEFROST ALARM 57.21 Display label meaning b1dF (circuit n° 1 defrost alarm signal) b2dF (circuit n° 2 defrost alarm signal) b3dF (circuit n° 3 defrost alarm signal) b4dF (circuit n°...
  • Page 172 USER MANUAL – Release 1.2 of 01/01/2010 Page 172 of 191 Version: 02/03/2010 UNLOADING SIGNAL DUE TO HIGH CONDENSATION 57.22 TEMPERATURE/PRESSURE IN COOLING WORKING MODE Display label meaning b1Cu (circuit n° 1 unloading from condenser coil signal) b2Cu (circuit n° 2 unloading from condenser coil signal) b3Cu (circuit n°...
  • Page 173 USER MANUAL – Release 1.2 of 01/01/2010 Page 173 of 191 Version: 02/03/2010 HEAT RECOVERY DISABLING SIGNAL DUE TO HIGH CONDENSATION 57.23 TEMPERATURE/PRESSURE IN COOLING WORKING MODE Display label meaning b1rC (circuit n° 1 recovery disabling signal) b2rC (circuit n° 2 recovery disabling signal) b3rC (circuit n°...
  • Page 174 USER MANUAL – Release 1.2 of 01/01/2010 Page 174 of 191 Version: 02/03/2010 UNLOADING SIGNAL DUE TO LOW EVAPORATION PRESSURE IN HEATING 57.24 WORKING MODE Display label meaning b1Cu (circuit n° 1 unloading from condenser coil signal) b2Cu (circuit n° 2 unloading from condenser coil signal) b3Cu (circuit n°...
  • Page 175 USER MANUAL – Release 1.2 of 01/01/2010 Page 175 of 191 Version: 02/03/2010 UNLOADING SIGNAL DUE TO EVAPORATOR WATER INLET HIGH 57.25 TEMPERATURE Display label meaning AEun (unloading signal from evaporator) Cause of activation In working mode if the evaporator water inlet temperature measured > Un1 set for the time set in the Par.
  • Page 176 USER MANUAL – Release 1.2 of 01/01/2010 Page 176 of 191 Version: 02/03/2010 PUMP DOWN ALARM WITH LOW PRESSURE PRESSURE 57.26 SWITCH/TRANSDUCER IN STOPPING Display label meaning b1PH (pump-down alarm in circuit n° 1 shutdown) b2PH (pump-down alarm in circuit n° 2 shutdown) b3PH (pump-down alarm in circuit n°...
  • Page 177: Pump Down Alarm With Low Pressure Transducer In Start-Up

    USER MANUAL – Release 1.2 of 01/01/2010 Page 177 of 191 Version: 02/03/2010 PUMP DOWN ALARM WITH LOW PRESSURE TRANSDUCER IN START-UP 57.27 Display label meaning b1PL (pump-down alarm in circuit n° 1 start-up) b2PL (pump-down alarm in circuit n° 2 start-up) b3PL (pump-down alarm in circuit n°...
  • Page 178: Evaporator Water Pumping Unit Circuit Breaker Alarm

    USER MANUAL – Release 1.2 of 01/01/2010 Page 178 of 191 Version: 02/03/2010 EVAPORATOR WATER PUMPING UNIT CIRCUIT BREAKER ALARM 57.28 Display label meaning AtE1 (evaporator n° 1 water pump circuit breaker) AtE2 (evaporator support n° 2 water pump circuit breaker) Cause of activation ID configured as evaporator n°...
  • Page 179: Unit N. 1 Block General Alarm

    USER MANUAL – Release 1.2 of 01/01/2010 Page 179 of 191 Version: 02/03/2010 HEAT RECOVERY CONDENSER WATER PUMPING UNIT CIRCUIT BREAKER 57.29 ALARM Display label meaning AtC1 (condenser n°1 water pump circuit breaker) AtC2 (condenser support n°2 water pump circuit breaker) Cause of activation ID configured as condenser n°...
  • Page 180: Unit N. 2 Block General Alarm

    USER MANUAL – Release 1.2 of 01/01/2010 Page 180 of 191 Version: 02/03/2010 UNIT N. 2 BLOCK GENERAL ALARM 57.31 Display label meaning ALc2 Cause of activation With AL56 = 0 ID configured unit n° 2 signal alarm active after the time set in the Par.
  • Page 181: Compressors Maintenance Alarm

    USER MANUAL – Release 1.2 of 01/01/2010 Page 181 of 191 Version: 02/03/2010 COMPRESSORS MAINTENANCE ALARM 57.32 Display label meaning C1Mn …C16Mn (compressor n° 1…16 maintenance request) Cause of activation Compressor working hours > timer set Reset Reset working hours (in functions menu) Reset Automatic (after the hours reset) Icon...
  • Page 182: Rtc Alarm

    USER MANUAL – Release 1.2 of 01/01/2010 Page 182 of 191 Version: 02/03/2010 RTC ALARM 57.35 Display label meaning ArtC (clock alarm) Cause of activation Clock to be regulated Reset Regulated clock Reset Manual. (reset procedure in functions menu) Icon flashing Action Alarm relay + buzzer activated...
  • Page 183: Network Frequency Alarm

    USER MANUAL – Release 1.2 of 01/01/2010 Page 183 of 191 Version: 02/03/2010 NETWORK FREQUENCY ALARM 57.38 Display label meaning AFr (network frequency alarm) Cause of activation Network frequency different to that configured in the Par. SP11 Reset Network frequency control disabled by parameter SP11 = 2 or frequency return into the set range Reset Automatic...
  • Page 184 USER MANUAL – Release 1.2 of 01/01/2010 Page 184 of 191 Version: 02/03/2010 UNIT CONFIGURATION 57.39 Display label meaning ACF1 Unit configured as cooling and heating (CF2 = 3) and circuit reverse valve not configured Incorrect combination in the values of the defrost parameters (dF26/dF27) See table in Defrost chapter Parameters dF26 and/or dF27 equal to zero with unique ventilation (FA05 = 0) and anti-freeze management in defrost mode disabled (dF33 = 0)
  • Page 185 USER MANUAL – Release 1.2 of 01/01/2010 Page 185 of 191 Version: 02/03/2010 ACF7 If the pump down function is enabled but in at least one circuit The relevant solenoid valve relay is not configured Pump down pressure switch or circuit evaporating pressure transducer are not configured and the pump down is enabled also at start or not even the low pressure pressure switch is configured If at least one pump-down solenoid valve has been configured but there is no...
  • Page 186 USER MANUAL – Release 1.2 of 01/01/2010 Page 186 of 191 Version: 02/03/2010 ACF14 The temperature control has been configured on two circuits (ST12 = 1) but: • the second circuit is not configured or circuits 3 and/or 4 are also configured •...
  • Page 187 USER MANUAL – Release 1.2 of 01/01/2010 Page 187 of 191 Version: 02/03/2010 REMOTE TERMINAL ALARM 57.40 Display label meaning noL (no link signal) Cause of activation Incorrect connection between remote terminal and controller or two remote terminals configured as present and both with the same HW address Reset Correct connection - two different HW addresses Reset...

Table of Contents