Summary of Contents for GV D1010S-046

  • Page 1 D1010S-046 - D1010D-046 INSTRUCTION MANUAL INSTRUCTION MANUAL Repeater Power Supply Smart-Hart compatible DIN-Rail Models D1010S-046, D1010D-046 D1010-046 - Repeater Power Supply Smart-Hart compatible ISM0066-8...
  • Page 2: Technical Data

    Characteristics General Description: The single and dual channel DIN Rail Repeater Power Supply, D1010S-046 and D1010D-046, provides a fully floating dc supply for energizing conventional 2 wires 4-20 mA transmitters, or separately powered 3, 4 wires 4-20, 0-20 mA transmitters located in Hazardous Area, and repeats the current in floating circuit to drive a Safe Area load.
  • Page 3: Ordering Information

    Ordering information Model: D1010 1 channel S-046 2 channels D-046 Power Bus enclosure Front Panel and Features • Input from Zone 0 (Zone 20), installation in Zone 2. • 4-20 or 0-20 mA Input, Output Signal. • Wide Band Smart Communication, Hart compatible. •...
  • Page 4: Parameters Table

    Parameters Table In the system safety analysis, always check the Hazardous Area devices to conform with the related system documentation, if the device is Intrinsically Safe check its suitability for the Hazardous Area and gas group encountered and that its maximum allowable voltage, current, power (Ui/Vmax, Ii/Imax, Pi/Pi) are not exceeded by the safety parameters (Uo/Voc, Io/Isc, Po/Po) of the D1010-046 series Associated Apparatus connected to it.
  • Page 5 When used with separate powered intrinsically safe devices, check that maximum allowable voltage, current (Ui/Vmax, Ii/Imax) of the D1010-046 Associated Apparatus are not exceeded by the safety parameters (Uo/Voc, Io/Isc) of the Intrinsically Safe device, indicated in the table below: D1010-046 D1010-046 Associated Must...
  • Page 6: Function Diagram

    Powered Tx Sink I In 2 Out 2 2 Wire Tx Source I Source V External Powered Tx Sink I MODEL D1010S-046 Supply 24 Vdc In 1 Out 1 2 Wire Tx Source I Source V External Powered Tx Sink I D1010-046 - Repeater Power Supply Smart-Hart compatible G.M.
  • Page 7 Function Diagram HAZARDOUS AREA ZONE 0 (ZONE 20), GROUP IIC SAFE AREA, ZONE 2, GROUP IIC T4 Connections for Duplication of 2 wires Transmitter Input Safety Description Restriction on specifications for 2 wires Transmitter Input: Terminals 14-11 Bidirectional communication for Smart Transmitter is provided only on channel 1 Uo/Voc = 27.4 V The minimum supply voltage available for Transmitter (Vtx) is 12.9 V at 20 mA input Io/Isc = 79 mA...
  • Page 8: Operation

    On the section “Function Diagram” and enclosure side a block diagram identifies all connections and configuration DIP switches. Identify the number of channels of the specific card (e.g. D1010S-046 is a single channel model and D1010D-046 is a dual channel model), the function and location of each connection terminal using the wiring diagram on the corresponding section, as an example: Connect 24 Vdc power supply positive at terminal “3”...
  • Page 9 The power dissipated Pd inside the enclosure for analog signal isolators is: Pd = Current Consumption (A) * Supply Voltage (V) - Power Dissipated into the input / output loads Analog signal isolators have higher dissipation than digital signal isolators, in addition 2 channels barriers (D1010D-046) have higher dissipation than single channel units (D1010S-046).
  • Page 10 Configuration An output configuration DIP Switch is located on component side of pcb, by closing switch “ON” (1-2 for channel 1, 3-4 for channel 2) output signal is configured for 0/1-5 Volts (250 W internal shunt), opening the switch produces the conventional 0/4-20 mA. Dip switch configuration Side A Panel View Switch positions...
  • Page 11 Calibration instruction and Troubleshooting In case a calibration check or readjustment is necessary the following equipment is required: Equipment Required Instrument Identification Adjustable Power Supply Range 0-35 V Resolution 0.1 V, Agilent Accuracy 1% Output Capability 200 mA E3611A Current Meter range 20 mA, Resolution 1 µA Accuracy 0.01% Agilent or Voltage Meter Range 10 V, Resolution 1 mV Accuracy 0.01% 34410A...