Table of contents Technical data FUSIO W 5 - FUSIO W 8, brine/water with Optiplus controller FUSIO W 11 - FUSIO W 18, brine/water with Optiplus controller Dimension drawings FUSIO W 5 - FUSIO W 8, brine/water Optiplus controller FUSIO W 11 - FUSIO W 18, brine/water with Optiplus controller...
Page 3
Notes _______________________________________________________________________________ Western Airconditioning B.V. reserves the right to alter specifications...
Technical data FUSIO W FUSIO W 5 - FUSIO W 8 brine/water with Optiplus controller Heat pump type FUSIO W 5 FUSIO W 6 FUSIO W 8 Model All in One All in One All in One Controller Optiplus integrated...
Technical data FUSIO W FUSIO W 5 - FUSIO W 8 with Optiplus controller Heat pump type FUSIO W 5 FUSIO W 6 FUSIO W 8 All in One All in One Controller Optiplus integrated integrated integrated WPZ-test number Electrical data...
1) Free field value 2) Free compression is specified for highest level 3) Expansion vessel heater is enclosed from fusio w 11 4) FUSIO W 5 and FUSIO W 6 without soft starter _______________________________________________________________________________ Western Airconditioning B.V. reserves the right to alter specifications...
Page 7
– Pressure gauge 0–4 bar – flexible connection-hoses – Heat pump controller Optiplus – Temperature sensor – Expansion vessels (heating vessel enclosed from FUSIO W 11 – Pressure controller – Flow sensor _______________________________________________________________________________ Western Airconditioning B.V. reserves the right to alter specifications...
Dimension drawings Dimension drawing FUSIO W OH FUSIO W 5- FUSIO W 11, brine/water optiplus controller Front view Lateral view Connection side Tableau Electric Sensor Feeder Connections cable cable Hot water Inlet-outlet Outlet Heat source Inlet Layout Legend 1 Hot water outlet...
8 Connection expansion vessel heater 1500 mm hose length from the outlet All dimensions are in mm The external sensor (QAC 34/101) and the documents are enclosed in the electric panel. _______________________________________________________________________________ Western Airconditioning B.V. reserves the right to alter specifications...
Page 10
Power curves FUSIO W 1- FUSIO W 5 Volume flow source minimum / nominal / standard 0.88/1.01/1.17 m Volume flow heater minimum / nominal / standard 0.43/0.61/0.86 m Performance data as per EN 14511 Heat output in kW tv = 30°...
9°C 11°C 13°C 15°C Heat source temperature Electric output in kW Performance data COP -5°C 0°C 5°C 10°C 15°C -5°C 0°C 5°C 10°C 15°C Heat source temperature Heat source temperature _______________________________________________________________________________ Western Airconditioning B.V. reserves the right to alter specifications...
Page 12
9°C 11°C 13°C 15°C Heat source temperature Electric output in kW Performance data COP -5°C 0°C 5°C 10°C 15°C -5°C 0°C 5°C 10°C 15°C Heat source temperature Heat source temperature _______________________________________________________________________________ Western Airconditioning B.V. reserves the right to alter specifications...
Page 13
9°C 11°C 13°C 15°C Heat source temperature Electric output in kW Performance data COP -5°C 0°C 5°C 10°C 15°C -5°C 0°C 5°C 10°C 15°C Heat source temperature Heat source temperature _______________________________________________________________________________ Western Airconditioning B.V. reserves the right to alter specifications...
9°C 11°C 13°C 15°C Heat source temperature Electric output in kW Performance data COP -5°C 0°C 5°C 10°C 15°C -5°C 0°C 5°C 10°C 15°C Heat source temperature Heat source temperature _______________________________________________________________________________ Western Airconditioning B.V. reserves the right to alter specifications...
Page 15
9°C 11°C 13°C 15°C Heat source temperature Electric output in kW Performance data COP -5°C 0°C 5°C 10°C 15°C -5°C 0°C 5°C 10°C 15°C Heat source temperature Heat source temperature _______________________________________________________________________________ Western Airconditioning B.V. reserves the right to alter specifications...
Heat pump controller Optiplus built-in entire heating period. Pressure gauge Built-in brine pump Condenser pump built-in Overflow valve • Subject to technical changes. • Installation of additional components as per local regulations and conditions. • This presentation is used as planning aid for the fitter. _______________________________________________________________________________ Western Airconditioning B.V. reserves the right to alter specifications...
Built-in brine pump be supplemented with an external vessel. Overflow valve • Subject to technical changes. • Installation of additional components as per local regulations and conditions. • This presentation is used as planning aid for the fitter. _______________________________________________________________________________ Western Airconditioning B.V. reserves the right to alter specifications...
Condenser pump built-in Balancing valve Safety valve Domestic hot water Overflow valve Power contactor+fuse in on-site tableau • Subject to technical changes. • Installation of additional components as per local regulations and conditions. • This presentation is used as planning aid for the fitter. _______________________________________________________________________________ Western Airconditioning B.V. reserves the right to alter specifications...
Domestic hot water Overflow valve Power contactor+fuse in on-site tableau • Subject to technical changes. • Installation of additional components as per local regulations and conditions. • This presentation is used as planning aid for the fitter. _______________________________________________________________________________ Western Airconditioning B.V. reserves the right to alter specifications...
The buffer storage can be charged at Condenser pump built-in reduced rate. Balancing valve Safety thermostat Heating circuit mixer • Subject to technical changes. • Installation of additional components as per local regulations and conditions. • This presentation is used as planning aid for the fitter. _______________________________________________________________________________ Western Airconditioning B.V. reserves the right to alter specifications...
Safety thermostat Safety valve Domestic hot water • Subject to technical changes. • Installation of additional components Heating circuit mixer as per local regulations and conditions. Power contactor and fuse in on-site tableau • This presentation is used as planning aid for the fitter. _______________________________________________________________________________ Western Airconditioning B.V. reserves the right to alter specifications...
Non-return valve controller. Safety thermostat Safety valve • Subject to technical changes. Domestic hot water • Installation of additional components Heating circuit mixer as per local regulations and conditions. Power contactor+fuse in on-site tableau • This presentation is used as planning aid for the fitter. _______________________________________________________________________________ Western Airconditioning B.V. reserves the right to alter specifications...
• Subject to technical changes. Heating circuit mixer • Installation of additional components Power contactor+fuse in on-site tableau as per local regulations and conditions. Solar system on-site, independent of control • This presentation is used as planning aid for the by heat pump. fitter. _______________________________________________________________________________ Western Airconditioning B.V. reserves the right to alter specifications...
1.0 A (or 400 V via ext. power contactor) Opt: Safety thermo- stat (ST) in series with Q2 • Subject to technical changes. • Installation of additional components as per local regulations and conditions. • This presentation is used as planning aid for the fitter. _______________________________________________________________________________ Western Airconditioning B.V. reserves the right to alter specifications...
Parameterisation in the heating circuit 2 is done in the parameter points 1010-1151, which appear for the connection of the extension module. No additional software required! • Subject to technical changes. • Installation of additional components as per local regulations and conditions. • This presentation is used as planning aid for the fitter. _______________________________________________________________________________ Western Airconditioning B.V. reserves the right to alter specifications...
Terminal assignment: as per basic concept heating with electric heating insert heating solar (additional) Solar sensor • Subject to technical changes. • Installation of additional components as per local regulations and conditions. • This presentation is used as planning aid for the fitter. _______________________________________________________________________________ Western Airconditioning B.V. reserves the right to alter specifications...
W10/W35) must be accepted by the swimming pool heat exchanger. The swimming pool must be taken into consideration when designing the soil sensor. • Subject to technical changes. • Installation of additional components as per local regulations and conditions. • This presentation is used as planning aid for the fitter. _______________________________________________________________________________ Western Airconditioning B.V. reserves the right to alter specifications...
For available room thermostat valves, these must be adaptable for the cooling as well as the heating operation. • Subject to technical changes. • Installation of additional components as per local regulations and conditions. • This presentation is used as planning aid for the fitter. _______________________________________________________________________________ Western Airconditioning B.V. reserves the right to alter specifications...
For available room thermostat valves, these must be adaptable for the cooling as well as the heating operation. • Subject to technical changes. • Installation of additional components as per local regulations and conditions. • This presentation is used as planning aid for the fitter. _______________________________________________________________________________ Western Airconditioning B.V. reserves the right to alter specifications...
Design of expansion system with central bus power supply 460 m Fit adequate dipping sleeves for sensors, thermostats Bus load rate E = 3 and thermometer Observe structural conditions (insertion, installation, ...) _______________________________________________________________________________ Western Airconditioning B.V. reserves the right to alter specifications...
Cu cable 1.5 mm , 2. Wire cannot be interchanged with controller-bus power supply (per controller) 250 m with central bus power supply 460 m Bus load rate E = 3 _______________________________________________________________________________ Western Airconditioning B.V. reserves the right to alter specifications...
(per controller) 250 m with central bus power supply 460 m Bus load rate E = 3 • Subject to technical changes. • Installation of additional components as per local regulations and conditions. • This presentation is used as planning aid for the fitter. _______________________________________________________________________________ Western Airconditioning B.V. reserves the right to alter specifications...
(per controller) 250 m with central bus power supply 460 m Bus load rate E = 3 • Subject to technical changes. • Installation of additional components as per local regulations and conditions. • This presentation is used as planning aid for the fitter. _______________________________________________________________________________ Western Airconditioning B.V. reserves the right to alter specifications...
(per controller) 250 m with central bus power supply 460 m Bus load rate E = 3 • Subject to technical changes. • Installation of additional components as per local regulations and conditions. • This presentation is used as planning aid for the fitter. _______________________________________________________________________________ Western Airconditioning B.V. reserves the right to alter specifications...
(per controller) 250 m with central bus power supply 460 m Bus load rate E = 3 • Subject to technical changes. • Installation of additional components as per local regulations and conditions. • This presentation is used as planning aid for the fitter. _______________________________________________________________________________ Western Airconditioning B.V. reserves the right to alter specifications...
3 kW 110K6 6 14 Main switch installed for HP Standard Attention: The rotating field to the right is absolutely necessary. Local regulations must be followed. Subject to technical changes. _______________________________________________________________________________ Western Airconditioning B.V. reserves the right to alter specifications...
3 kW 110K6 6 14 Main switch installed for HP Standard Attention: The rotating field to the right is absolutely necessary. Local regulations must be followed. Subject to technical changes. _______________________________________________________________________________ Western Airconditioning B.V. reserves the right to alter specifications...
10 kW additional protection for 12 and 15 kW The rotating field to the right is absolutely necessary. Local regulations must be followed. Subject to technical changes. _______________________________________________________________________________ Western Airconditioning B.V. reserves the right to alter specifications...
10 kW Attention: additional protection for 12 and 15 kW The rotating field to the right is absolutely necessary. Local regulations must be followed. Subject to technical changes. _______________________________________________________________________________ Western Airconditioning B.V. reserves the right to alter specifications...
3 kW 110K6 6 14 Main switch installed for HP Standard Attention: The rotating field to the right is absolutely necessary. Local regulations must be followed. Subject to technical changes. _______________________________________________________________________________ Western Airconditioning B.V. reserves the right to alter specifications...
10 kW Attention: additional protection for 12 and 15 kW The rotating field to the right is absolutely necessary. Local regulations must be followed. Subject to technical changes. _______________________________________________________________________________ Western Airconditioning B.V. reserves the right to alter specifications...
10 kW Attention: additional protection for 12 and 15 kW The rotating field to the right is absolutely necessary. Local regulations must be followed. Subject to technical changes. _______________________________________________________________________________ Western Airconditioning B.V. reserves the right to alter specifications...
10 kW Attention: additional protection for 12 and 15 kW The rotating field to the right is absolutely necessary. Local regulations must be followed. Subject to technical changes. _______________________________________________________________________________ Western Airconditioning B.V. reserves the right to alter specifications...
Page 44
FUSIOW23062016 Western Airconditioning B.V. De Wel 10, 3871 MV HOEVELAKEN Tel. +31 (0) 33 247 7800 www.western.nl _______________________________________________________________________________ Western Airconditioning B.V. reserves the right to alter specifications...