1
SET CLOCK, YEAR, MONTH, DAY
NOTE:
Display of
Clock is not
available when
for non-
programmable
operation.
1. Press ▲/ ▼ to select 12 / 24 Hr mode, then press
2. Press ▲/ ▼to select hour, then press Next.
3. Press ▲/▼to select minutes, then press Next.
4. Press ▲/ ▼ to select current year, then press Next.
5. Press ▲/ ▼ to select current month, press Next.
6. Press ▲/ ▼ to select the calendar day number.
7. Press
to complete operation.
Done
note: Select
Clock, to access after setup.
More >
2
ACCESS SERVICE MENUS
1. Hold lower right and left keys for fi ve seconds.
2. Press
or
to select a Service Menu.
Next
Go Back
3. Press ▲/ ▼ to select option.
4. Press
when complete.
Done
3
CONFIGURE SERVICE MENUS
The following Service Menus (SM) commonly require
confi guration. Please verify that these are set for your
specifi c application. additional confi guration may be
required. refer to Table 2 for all available Service Menus.
• SM 100 = Programmable or nonprogrammable
• SM 110 = System Type
• SM 121 = number of fan Speeds
• SM 130 = reversing valve
• SM 135 = W1 heat output no or nc
• SM 170 = remote Sensors
• SM 265 = Single or dual Setpoint operation
© COPYRIGHT 2016 ENTERGIZE, LLC. ALL RIGHTS RESERVED.
PERFORMANCE PRO MULTI-FAN
OCCUPANCY THERMOSTAT
4
WIRE TERMINAL DESIGNATIONS
1. connect wires for appropriate system type (Table 1).
!
WARNING: DISCONNECT POWER BEFORE BEGINNING INSTALLATION.
• CAUTION: Use copper wire only. Insulate or wire-nut all unused leads.
• Use care to avoid electrostatic discharge to thermostat
• CAUTION: Do not connect unused wires together
• ALL ELECTRICAL LOADS MUST BE CONNECTED TO TERMINAL C
(24 VAC).
TABLE 1. TERMINAL BLOCK
Fan Coil (Conventional)
C
24 VAC, Unswitched side
Next.
W1
Stage 1 Heat
W2
Stage 2 Heat
G
FAN High
A
FAN Medium
E
FAN Low
Y1
Stage 1 Cool
Y2
Stage 2 Cool
24 VAC Power for heating,
RH
switched side
24 VAC Power for cooling,
RC
switched side
SC
Sensor Common
S1
Indoor Remote Sensor
S2
Occupancy Sensor
Seasonal Changeover Switch
S3
OPEN=Cooling in Summer
Service
CLOSED=Heating in Winter
Menu
Current
option
5
TYPICAL FAN COIL
WIRING DIAGRAM
24 VAC Unswitched
C
WI
Heat Valve
Y1
Cool Valve
G
FAN HIGH
A
FAN MED
E
FAN LO
RH
24 VAC Switched Side
RC
Sensor Common
SC
S1
Remote Sensor
S2
OCC Sensor
Aquastat
S3
OPEN= Summer CLOSED = Winter
1
QUICK START GUIDE
Heat Pump
C
24 VAC, Unswitched side
B/O
Reversing Valve
AUX
Auxiliary Heat (Stage 2 or 3)
G
FAN High
A
FAN Medium
E
FAN Low
Y1
Compressor Stage 1
Y2
Compressor Stage 2
24 VAC Power for heating,
RH
switched side
24 VAC Power for cooling,
RC
switched side
SC
Sensor Common
S1
Indoor Remote Sensor
S2
Occupancy Sensor
S3
NA
6
FAN SPEED
SELECTION
1. Press the
Fan
select speed/operation.
2. Press
when complete.
Done
fan Speed is noted as
follows:
on = continuous fan operation
AUTO = Fan Cycles with Heating
and Cooling
24 VAC
FAN HIGH
FAN MED
FAN LOW
P/N 71969 3220-2345 REV 00=E
button to

Advertisement

loading
Need help?

Need help?

Do you have a question about the T8532OCC and is the answer not in the manual?

Questions and answers

Summary of Contents for Entergize T8532OCC

  • Page 1 • SM 135 = W1 heat output no or nc FAN LOW Aquastat • SM 170 = remote Sensors OPEN= Summer CLOSED = Winter • SM 265 = Single or dual Setpoint operation © COPYRIGHT 2016 ENTERGIZE, LLC. ALL RIGHTS RESERVED. P/N 71969 3220-2345 REV 00=E...
  • Page 2 SETBACK OPERATION NOTES Occupancy Sensor Detection Performance The T8532OCC Thermostat has an onboard occupancy sensor that will setback Detection Distance: 16.4 Ft (5 meters) operation when a room becomes vacant. Service Menu 325 Occupied Sensor Detection Range: 94° Horizontal x 82° Vertical Operation is turned on to enable this operation.
  • Page 3 ON or Auto: Occupant can choose either selection System Mode Allows ability to determine which system modes the occupant can select. OFF, Auto OFF, Heat, Cool, Auto OFF, Heat, Cool Heat, Cool, Auto © COPYRIGHT 2016 ENTERGIZE, LLC. ALL RIGHTS RESERVED. P/N 71969 3220-2345 REV 00=E...
  • Page 4 System Fan Test Disabled Output Low Speed Medium Speed High Speed Factory Use Only Factory Use Only Factory Use Only Factory Use Only Factory Use Only Factory Use Only © COPYRIGHT 2016 ENTERGIZE, LLC. ALL RIGHTS RESERVED. P/N 71969 3220-2345 REV 00=E...