CONNECTION AND CONFIGURATION
Connecting the Keyboard
CL(n-l)
CL 1
CL 2
CL n
A
B
CL = Client
The clients are connected in a parallel way to the RS485 line
(conductors A and B). Up to 32 clients with a max. connection length
of 6 m can be connected to the main line.
A
120Ω
120Ω
B
1200m
Start
End
The RS485 line can have a length of up to 1200 m. A transmission line
with 120 Ohm has to be connected to the start and to the end of it in
order to avoid signal reflections. The terminating resistor for the RS485
can be connected to each client with a jumper.