Table of Contents

Advertisement

MultiCONT
Manufacturer:
NIVELCO Process Control Co.
H-1043 Budapest, Dugonics u. 11.
Tel.: (36-1) 889-0100
Fax: (36-1) 889-0200
E-mail:
sales
@nivelco.com
www.nivelco.com
BKI 11 ATEX 0017
prw2101a0600p_01
1 / 105

Advertisement

Table of Contents
loading

Summary of Contents for NIVELCO MultiCONT

  • Page 1 MultiCONT Manufacturer: NIVELCO Process Control Co. H-1043 Budapest, Dugonics u. 11. Tel.: (36-1) 889-0100 Fax: (36-1) 889-0200 E-mail: sales @nivelco.com www.nivelco.com   BKI 11 ATEX 0017 prw2101a0600p_01 1 / 105...
  • Page 2  prw2101a0600p_01 2 / 105...
  • Page 3: Table Of Contents

    The structure of the system................6 5.2.2. Wiring.......................31 1.1.2.1 Point-to-point connection ..............7 5.2.3. Putting the MultiCONT into operation ..............32 1.1.2.2 Multipoint connection (Multidrop). Multiple slaves connected in parallel.8 5.3. M ..................... 33 1.1.3. Properties of HART-capable devices ..............9 AIN MENU 1.1.4.
  • Page 4 EMOTE ROGRAMMING 9.4.1. Problems that may occur during remote programming:........99 5.6.1. Editing the linearisation table ................68 9.4.2. MultiCONT transmits the parameters without examining them, and the testing is 5.7. R ................69 ELAY ONFIGURATION done by the device...................99 5.7.1.
  • Page 5: Introduction

    The MultiCONT unit is a universal interface between NIVELCO’s HART-capable intelligent level transmitters and the other elements of the process control system like the PC-s , PLC-s, displays and the actuators. Besides its role as an interface, the MultiCONT ensures the powering of the 2-wire transmitters while being capable of complex control tasks.
  • Page 6: The Hart System

    The HART communication is basically a master-slave type, which means that the transmitter – slave – only sends a response when the master (of which there can be only one in the system) sends a query. The master can be a Hand-held Communicator, a PC with a HART modem or a universal interface, in this case, a MultiCONT (naturally, only one can be active).
  • Page 7: Point-To-Point Connection

    1.1.2.1 Point-to-point connection When a master (communicator or HART modem with PC or MultiCONT) and a slave are alone in a system, we talk of a point-to-point connection MultiCONT +U s 250  I– L– Transmitter Universal interface RS485 In this case the flowing current is the output current of the transmitters, so if permitted by the loop voltage, even a local indicator can be included into the loop.
  • Page 8: Multipoint Connection (Multidrop). Multiple Slaves Connected In Parallel.8

    In a Multidrop system, the „burst mode” does not work * An 820 ohm resistor should be connected between the L- and SH terminals of the Ex version MultiCONT when it is used with the 3 (max. allowed) Ex version MicroTREK microwave level transmitter.
  • Page 9: Properties Of Hart-Capable Devices

    Can be reconfigured Date Date. Can be assigned to the device. Can be reconfigured Factory ID Factory ID. For NIVELCO devices: 151, cannot be reconfigured Device type ID Device type ID, cannot be reconfigured Device ID The manufacturer’s electronic production number, cannot be reconfigured The Factory ID, the Device Type ID and the Device ID together form the “Long Address”.
  • Page 10: Universal Commands

    1.1.4.1 Universal commands These are commands understood by all devices, and to which all devices give the same reply. 0. Read unique identifier the addressed device provides the following in it’s reply:  Manufacturer’s code (provided by the HART foundation, see appendix) ...
  • Page 11: General Commands

    12. Read device message This reads the 32 character message stored in the non-volatile memory of the device (e.g. T18 35% HCL TANK) 13. Read the 8 character ”short TAG”, 16 character descriptor and date 14. Read PV sensor information 15.
  • Page 12: Technical Data

    2. TECHNICAL DATA P - 2- Transmitter Power Supply 30 V DC / 60 mA (For Ex Version: 25 V DC / 22 mA) Display 128 x 64 dot-matrix Max. 2 galvanically isolated 4 … 20 mA outputs, Analogue max load of 500 ohm, with over-voltage protection Relay Max.
  • Page 13: Accessories

    2.1. A CCESSORIES   Warranty Card Declaration of Conformity   User’s and Programming manual 2 universal cable gland sealings  prw2101a0600p_01 13 / 105...
  • Page 14: Order Code

    3. ORDER CODE MultiCONT – – XPANSION NCLOSURE NPUT UTPUT OWER UPPLY Expandable * IP 65 wall enclosure 1 HART unit Display only 85 … 255 V AC Standard 2 HART units 1 relay 24 V AC / DC IP 65 wall enclosure +...
  • Page 15: Dimensions

    3.1. D IMENSIONS 75.5 75.5 A Pg9 or M16 B Pg11 or M20 A Pg9 or M16 C Pg11, Pg13.5 or M20 B Pg11 or M20 C Pg11, Pg13.5 or M20 PW PC, PD RRANGEMENT OF OUNTING OLES PW PC PD ...
  • Page 16: Conditions Of Use Of Thee

    3.2. C ONDITIONS OF USE OF THE X UNITS  The units should be mounted outside the hazardous zone!  Device should be protected against direct sunshine!  The power supply and ambient temperature values must not exceed the specifications in the Technical data! ...
  • Page 17: Electrical Connection

    4. ELECTRICAL CONNECTION 4.1. A RRANGEMENT OF THE ABLE ERMINALS 4.1.1. Four relays version After loosening and removing screws fastening the CURRENT cover the cables can be connected. The same cable MAINS RELAY 1 RELAY 3 USER RS485 DEVICES OUT 1 should not be used for AC and DC as well as for SELV 85 ...
  • Page 18 Cabel Capacitance (pF / m) Number of Transmitters 2800 2000 1300 1000 2500 1800 1100 2200 1600 1000 1850 1400 Shielding of the connecting cable between the transmitter and the controller should be grounded at one end, connected either to the internal or external part of the earthing screw.
  • Page 19: Wiring

    Transmitter 1 Shielded twisted cable pair ransmitter MultiCONT ransmitter +U s 250  I– L– ransmitter Shielding grounded at the MultiCONT Universal interface In non-Ex versions only MODULE USER RS485 RS485 Ex area Non-Ex area PJK-100 Universal interface modules ...
  • Page 20: Wiring Of 4-Wire Units (Transmitters With Separate Power Supply)

    Transmitter 1 Shielded twisted cable pair ransmitter MultiCONT ransmitter 250  L– I– Universal interface ransmitter MODULE USER 85...255 VAC RS485 RS485 11.4...28 VAC Shielding grounded 11.4...40 VDC at the MultiCONT PJK-100 Universal Interface Modules  prw2101a0600p_01 20 / 105...
  • Page 21: Wiring Of Combined Systems (Containing Both 2- And 4-Wire Transmitters)

    4.2.1.3 Wiring of Combined Systems (containing both 2- and 4-wire transmitters) Transmitter 1 Shielded twisted Shielding grounded cable pair at MultiCONT ransmitter ransmitter MultiCONT +U s 250  I– L– ransmitter I– Universal interface 85...255 VAC 11.4...28 VAC 11.4...40 VDC...
  • Page 22: Wiring Of Universal Interface Modules (Pjk-100)

    The terminal resistor is connected to the two farthest points of the cable. (TB and B terminals are connected in PJK 100; and on the MultiCONT the K2 terminal resistor, located Module RS485 next to the terminals, is switched on.)
  • Page 23: Programming Of Multicont

     Automatic detection of devices (transmitters) connected to the MultiCONT, and putting them into the list of devices. Devices not on the list are part of the system but are unable to communicate with the MultiCONT (see 5.2.3 Main menu / MultiCONT config / DEV detect).
  • Page 24: Steps Of Programming

    Bargraph image (output range) Further menu points up and down the line menu Relays Further menu points up the line User image, see 5.4 MultiCONT configuration point Current generators Relay assignment table Current output assignment table Error list, see 6. Error codes ...
  • Page 25: Scrolling And Selecting Menu Items

    5.1.1. Scrolling and selecting menu items The various display modes (M, B, U, R, C, E) can be selected using buttons. With button can enter into the Programming Mode or the selected menu point and can return with button. The desired menu item can be selected using (repetitive functioning i.e.
  • Page 26: Activation (Of Devices, Relays And Current Outputs) Selection (Of Language, Operation Mode, Etc.)

    5.1.2. Activation (of devices, relays and current outputs) selection (of language, operation mode, etc.) Devices on the list may be active ( ) or inactive ( ). Only active devices will be queried. Active relays and current outputs operate according to their configuration, inactive relays are de-energized while inactive current outputs remain 0 mA.
  • Page 27: Assignment Of Outputs (Relay And Current) To The Device

    Value has a negative sign (for differential measurement)  Values from devices marked this way will be averaged The above settings can be changed using Assignment of device SE380-1 to the relay R_IN_1 in the MultiCONT should be performed as below: 01: R_IN_1 Programming Source Source ...
  • Page 28: Entering Parameter Values

    5.1.4. Entering parameter values Parameters have signs and absolute values. Positioning the cursor to the sign and digits can be done using are for modifying the value of either the sign or the digit. Switching between the (+) and (-) signs Parameter Parameter RP1 =...
  • Page 29: Editing Character Variables (E.g. Short Tag)

    Configuration of the state of the transmitters. Devices (transmitters) placed in the device list during the detection process automatically become active i.e. the MultiCONT queries them constantly. This can be avoided by setting their state to be inactive (see chapter 5.2.3) ...
  • Page 30: Preparation Of The Transmitters And The Universal Interface Modules

    EVICE ADDRESS CURRENT TAG” TYPE Ex) MultiCONT is max. 60 mA, and it is max. 22 mA for the Ex certified PARAMETER PARAMETER version. If the loop current exceeds this value the voltage at the terminals EchoTREK 4 wire X X X X X X...
  • Page 31: Preparing Of The Universal Interface Modules

    5.2.1.2 Preparing of the Universal Interface Modules The MultiCONT can be expanded by a maximum of 32 Universal Interface Modules. They can be differentiated from each other using their „Short Addresses”. Two or more modules with the same ADDR. Example for setting the address: 4+8=12, this is the „Short Address”...
  • Page 32: Putting The Multicont Into Operation

    5.2.3. Putting the MultiCONT into operation Switching on initiates a 40 sec test process, during which MultiCONT tests the integrity of the memory where its settings are stored (See 5.9 The Boot Process). If everything goes perfectly, then the following...
  • Page 33: Main Menu

    Reset to default. Clears device list, relay and current output parameters, assignments and resets the parameters of "MultiCONT conf." Does not clear the switching number and work time. The steps in 5.2.3 have to be repeated (Putting the MultiCONT into operation). Restart Simulate repowering ( RESET ) ...
  • Page 34: Configuration

    CONT ULTI CONFIGURATION The selected menu item appears in inverted mode on the display, and is marked in grey in this manual. Select menu items Main menu MultiCONT conf.  35 using buttons DEV detect Devices Enter by pressing Relays...
  • Page 35: Dev Detect

    5.4.1. DEV detect: Queries the transmitters via HART line from 0 to 15, and lists them with 1…9, A, B, C, D, E, F tag.  prw2101a0600p_01 35 / 105...
  • Page 36 MultiCONT detects devices in accordance to the Short address (that is why two or more devices must not have the same Short address) After detection however, query will be performed using the Long address that consists of the following three parts: ...
  • Page 37 MultiCONT only handles units above the line. Note: If the number of the devices in the loop is known and MultiCONT detected them already, detection process can be interrupted by pressing the ← button (the ← button should be pressed until „DEV detection end” message appears).
  • Page 38 The lenght of the list depends on the 2: SEA-360 (- -) type of the MultiCONT (1, 2, 4, 8, 15, see order code) - - - - > SAVE < - - - -...
  • Page 39  prw2101a0600p_01 39 / 105...
  • Page 40: Ext Detect

    The query process is similar to that of the DEV detect mode, the only difference being that the modules that get into the list remain in an inactive state. (See 5.2.3 Putting the MultiCONT into operation) The detected relays or current outputs (4-20 mA) will placed at end of the Detected EXT list.
  • Page 41: Source

    5.4.3.1 Source The quantity to be displayed in the “Main display” can be selected independently for each transmitter. Cross-check your selection in “Main menu”/”MultiCONT config.”/”HART”/”CommandSet”, to confirm the selection of the appropriate command containing the desired quantity. Main display Source...
  • Page 42: Rounding

    5.4.3.2 Rounding The MultiCONT by default rounds to 4 decimal digits i.e., the quantity is displayed with precision of 4 decimals. The rounding is for the main image quantity only. Main display Source Rounding Rounding SE360 Step 1: SE380 2: SE360 x.xxx...
  • Page 43: List Display

    ** The MultiCONT calculates the value of PV rate of change in every 5 sec. If there are more transmitters in the loop and this cycle time is more than 5 sec, calculation of PV_Rate ( t1 - t2 ≥ 5 sec) is performed per cycles.
  • Page 44: User Display

    5.4.5. User Display: In measuring mode (See chapter 5.10) the user can select a display format besides the display showing the measured data and this can be seen in the user display. We will receive an error message in the use’s image if: ...
  • Page 45: The Resulted User Displays

    SPA-360 and SPA-380  Average List number of devices whose average value is calculated by MultiCONT A 134 The average value calculated from the measurement result of the selected devices can be stepped using 3 P 380 LEV : S A- 15.32 m...
  • Page 46: Hart

    5.4.6. HART In this menu, it is possible to configure MultiCONT properties, the settings related to the transmitter query and also to choose the HART commands which the MultiCONT uses to communicate with the devices. HART Short TAG Polling address...
  • Page 47: Polling Address

    5.4.6.2 Polling Address If multiple MultiCONT-s are to be connected to a single system via RS485, then this address differentiates them. Polling address 5.4.6.3 Message An arbitrary message (usually related to the operation, and max 32 characters) can be assigned to a device.
  • Page 48: Date

    NIV129 The communication between the MultiCONT and the devices is via different commands. The MultiCONT sends a command containing the address of the device, which responds in accordance with the standards. Some of the commands are universal, while others are device-specific. The appropriate commands are selected automatically based on the data required to control the display, relays, and current outputs.
  • Page 49 NIV128: device specific command optimalized for DIST, LEV, VOL measurements  NIV129: device specific command optimalized for DIST, LEV, FLOW, TOT1, TOT2 measurements The table below shows the contents of the responses of NIVELCO-manufactured devices to given commands: COM3: 03 Universal HART command EchoTREK 4-wire.
  • Page 50 NIV128: NIVELCO device specific commands optimized for VOL measurement EchoTREK 4-wire. EchoTREK 2-wire. NIVOTRACK NIVOCAP EasyTREK EasyTREK Base 3. Pos. 4. Pos Base 3. Pos. 4. Pos Base 3. Pos. 4. Pos Base 3. Pos. 4. Pos. DIST Curr. DIST Curr.
  • Page 51: User Rs485

    No parity  output values of the devices ODD parity EVEN parity The MultiCONT units have separate addresses so they can be connected into a system. (max. 30 MultiCONT-s). 2 communication protocols are available: STOP bit 1 STOP bit ...
  • Page 52 The time-windows are independent from the trend logger and even all four saving modes can operate at the same time (time/event-controlled, time-windows). Time-window logger function can be used only for NIVELCO manufactured transmitters used in flow-metering mode. Setting Source 5:SPA-360...
  • Page 53: Trend Logger

    5.4.8.1 Trend logger Trend logger function is only available on PRD- and PED- instruments. Trend logging can be time-controlled (store an entry after a programmed time elapse) or event-controlled (logging upon measurement changes). These two modes can be working simultaneously and conditions of the logging can be set from the menu (programmed trend logging).
  • Page 54 For using the trend logging function, the following data should be set:  In the “Source” menu point the transmitter can be selected which measured value will be logged and the additional three values can be selected to be logged besides the primary value.
  • Page 55: Time-Window Tot (Total Flow Logging)

    This function is only available for NIVELCO manufactured transmitters operating in flow measurement mode (for this option NIV129 should be selected in “Main menu”/”MultiCONT conf.”/”HART”/”Command set”). The 8 highest values of the flow are stored with time within the selected time interval in LP3 parameter in the “Parameters”...
  • Page 56: Using A Memory Card For Logging

    Trend logging function is facilitated by a LOGGER unit connected to the front panel. It contains a FLASH memory chip and an SD (Secure Digital) card slot. Communication between the central unit of the MultiCONT and the LOGGER unit is indicated by two LED-s on the front panel. The green LED (read) flashes when a new logging entry is created, the red LED (wire) indicates when data are stored to the SD card.
  • Page 57 200 byte, so this capacity provides storing entries more than a million. The LOGGER unit of the MultiCONT senses automatically the inserted SD card. Then saving the FLASH memory into the memory card commences automatically. State of this process can be followed in the trend bargraph. Before remove the memory card, the end of the write process (when the red LED does not flash) has to be waited.
  • Page 58: File System Of The Sd Card And File Content Of A Logging Entry

    LED during write process). The LOGGER unit finds the last dated directory and examines if the files are more than 200 in this subdirectory. If not, MultiCONT continues the write process. If there are more than 200 files, a new directory is created. One logging file can contain max. 1000 entries, but new logging files are created when turning ON/OFF, restart of the MultiCONT and exiting from the LOG menu.
  • Page 59 The PRffffff.TXT named logging files in the directories consist of two main parts: header and data field. The header contains the following information: << DataLogger and MultiCONT version NIVELCO DataLogger Ver.:1.08 MultiCONT Ver.:01.02.02 << Date of file creation Date:2001.01.01 01:02...
  • Page 60 Comments:  If logging entry type is not 2, then MultiCONT is the source ( DEV=255, TAG=P-100, Error=0, Status=0), instead of the PV and the three additional selected values use NAN (no data) caption can be read.  Insertion of SD card: 2010.05.07...
  • Page 61 Software reset Device restart from menu Entry of measured value Programmed TREND logging entry Settings of MultiCONT have changed. CRC calculated when entering MultiCONT CRC altered Main menu differs from the CRC calculated when quitting the Main menu. TOT1 clear Clearing TOT1 from a NIVELCO instrument used for flow-metering.
  • Page 62: Secret Code

    5.4.9. Secret code The viewing and modification of MultiCONT settings can be protected with a secret code differing from 00000000. If there is a password, the following symbol appears left of the menu identifier, and flashes after being unlocked. The password remains temporarily unlocked until returning to the measuring process.
  • Page 63: Language

    5.4.10. Language This is where to select the language used during measurement and programming. The selected language will be switched to immediately. Language English Default: english select using German French Hungarian 5.4.11. Background lighting The background lighting of the display can be modified here. Backlight In auto mode, pressing any button sets the backlight to "high".
  • Page 64: Report

    Type of MultiCONT SW type: oftware type of MultiCONT SW version: 01.00 Software version of MultiCONT Serial: B9718160 Serial no. of MultiCONT processor Date: 2005/11/15 Date of MultiCONT software update Working: 6/18/59 MultiCONT work time (days/hrs/mins) Power cnt: No. of MultiCONT "power-on"s Temp min.:...
  • Page 65: Programming Devices

    5.5. P ROGRAMMING EVICES  prw2101a0600p_01 65 / 105...
  • Page 66: Remote Programming

    5.6. R EMOTE ROGRAMMING Select the device to be programmed as described above.  prw2101a0600p_01 66 / 105...
  • Page 67 Press OK ** Parameters entered during remote programming via MultiCONT will be sent without being checked to the device where the data is checked. In the event of bad parameter value, or if the given parameter is not defined in the given device, then...
  • Page 68: Editing The Linearisation Table

    5.6.1. Editing the linearisation table Warning! For the transmitter to compute the measurement results using the linearisation table, linearisation has to be enabled in parameter P47 (See the Installation and Programming Manual of the given transmitter)  prw2101a0600p_01 68 / 105...
  • Page 69: Relay Configuration

    Thus if the chosen value is LEVEL [m] then the RPx parameters also have to be entered in LEVEL [m]. 5.7.1. Relay Selection It is impossible to enter the relay menu if the system does not contain a single relay. The number of relays in the system can be viewed under Main menu/MultiCONT config/ Report. (See chapter 5.4.12.)
  • Page 70: Properties Of The Selected Relay

    Actual state of the relay 9729718161 Relay ID number Parent: 9728718160 In case of an internal relay, the MultiCONT's ID, if not then the module's ID Location of the relay (Internal=in MultiCONT, Location: Internal External=in an external module)  prw2101a0600p_01 70 / 105...
  • Page 71: Relay Programming

    Upon selelcting the quantity, confirm that the appropriate HART command has been seleceted for the device (See Main menu/MultiCONT config/HART / command set, see chapter 5.4.5.5) ...
  • Page 72: Function

    5.7.3.2 Function Not selected Function Relay: R1_IN Program Selected Hyst. Program Source Select using Alarm Short TAG Function Alarm, K Info Parameter Invert Alarm, G Window Clear TOT Window, D Update TOT Error Test Impulse, F TOT 1 Alt., S Sequential PV rate of change ...
  • Page 73 PERATING MODE UNCTION Hysterisis. (2-point control) Default: filling with energized relay: Invert = OFF, above RP1 the relay will be de-energized below RP2 it will be RP1, energized Inverted operation: by interchanging RP1 and RP2 Energised or by selecting Invert = ON Relay Main menu/Relays/Program/Invert De-energised...
  • Page 74 Window (window comparator) Default: Invert= OFF Between RP1 and RP2 relay will be energized Inverted operation (Between RP1 and RP2 relay will be de- RP1, energized) or by selecting Invert = ON Energised Relay De-energised Window D (comparator with delayed switching) Default: Invert = OFF Between RP1and RP2 relay will be energized using delay in RP1,...
  • Page 75 TOT1 TOT1 RP1=20 Default: Invert = OFF relay will be de-energized when TOT1 reaches value in RP1 Operation can be inverted by selecting Invert = ON (relay will be energized) Energised Relay De-energised Alt (optimized pump control) Default: Invert = OFF More relays (max 8) can be assigned to one source (transmitter) and they are controlled such that the switching number will be the same for all of them.
  • Page 76 PV rate of change Default: „Invert = OFF” RP1>RP2≥0 The MultiCONT counts PV rate of change in every 5 seconds. PV rate When there are more transmitters in the loop and cycle time is of change more than 5 seconds, PV_Rate is calculated per cycles.
  • Page 77 Sequential Default: „Invert = OFF” More operation modes are possible to use depending on the values of the parameters. There is only one relay in energized state. When all relays are in de-energized state, then new cycle is started and relays will be reversed. In the followings, there is an example for the operation in case of two relays ( max.
  • Page 78 Sequential R2 ON RP1 R1 ON RP1 R2 ON RP1 Same switching points for the relays for turning ON and R1 OFF RP2 R2 OFF RP2 Rx-RP1 > Rx-RP2 ON RP1 Emptying with energized relay RELAY 1 In case of x ( x=2..8 ) relays, relays are operating alternately OFF RP2 ON RP1 RELAY 2...
  • Page 79 Sequential R2 OFF RP2 R1 OFF RP2 Different switching points for turning ON and same switching points for turning OFF for the relays R1 ON RP1 R2 ON RP1 Rx-RP1 < RX-RP2 ON RP1 Filling with energized relay RELAY 1 OFF RP2 ON RP1 RELAY 2...
  • Page 80: Configuring Parameters

    5.7.3.3 Configure parameters Parameter to be edited Program Parameter Selection of digit position Source RP1 = + 0003.45 Modifying sign and number Function RP2 = 12.45 For RP1 steps back to "Programming" sub-menu, Parameter RP3 = for RP2 and RP3 steps back to the previous parameter Invert Accepts parameter change and steps to the next, Clear TOT...
  • Page 81: Invert

    5.7.3.5 Deleting TOT Quantity (TOT1 and TOT2) summation is done in the flow-measuring transmitters. In the MultiCONT it is possible to transmit the TOT2 in preset units in the form of relay impulses. In order to do this, the relay has to be switched to ‘Impulse F’ mode. In the ‘RP3’ parameter (belonging to the relay), specify the volume that will trigger 1 impulse (the length of 1 impulse is about 200 ms).
  • Page 82: Refreshing Tot

    Once in the menu, pressing ’OK’ will copy the transmitter’s ’TOT2’ value into the relay’s ’TOTAL’ variable, and then delete the contents of the relay’s ’PULSE’. The transmitter and the MultiCONT become synchronised. The update operation is followed by the window below.
  • Page 83 3. More than one device can be assigned to any of the relays (Main menu/Relays/Program/Source) 4. The result will be the mathematical combination of the sources. If the measurement mode or dimensions of devices are different MultiCONT will send error message (See 6. Errors, Error messages) 5. The result of the transmitters marked with are added.
  • Page 84: Operation And Parameters Of Current Outputs

    5.8.1. Selection of Current outputs It is impossible to enter the current output menu if the system does not contain a single current output. The number of relays in the system can be viewed under Main menu/MultiCONT config/ Report. (See chapter 5.4.12) Main menu Select using &...
  • Page 85: Properties Of The Selected Current Output

    (if CP1...CP3 are known) Actual value of the output current Output: 12.45 mA ID of the current output 9729718161 For an internal curr.out., this is the MultiCONT's ID, Parent: 9728718160 for an external one, this is the module's ID Location: Internal Location of the curr.
  • Page 86: Function

    Upon selecting the value, confirm that the appropriate HART command has been seleceted for the device (See Main menu/MultiCONT config/HART / command set, see chapter 5.4.5.5) 5.8.3.2 Function...
  • Page 87: Parameter Configuration

    Note: 1. The device will display an error if the selected mode is “Variable” and CP1=CP2 2. Value of the output current will not change (HOLD), if the assigned device does not respond or responds with an “Err xx” error! 3.
  • Page 88: The Boot Process

    5.9. T ROCESS At every powering on, a test program runs testing the MultiCONT hardware. The whole process can be followed on the display in English. The procedure takes about 40s.  prw2101a0600p_01 88 / 105...
  • Page 89 LOGGER PRESENT LOGGER NOT PRESENT Hardware check is successful. MultiCONT is in measurement mode and queries the active transmitter 1: SE300 - - - Still no valid data 2010.01.21 A 09.32 1: SE300 DIST 1 On the display, the result of the first number list-tagged transmitter can be seen.
  • Page 90: Measurement Modes

    In this mode, it is possible to view the „Bargraph display”, the „User display” (Range, Double, Difference, Average see Main menu / MultiCONT config / User display - chapter 5.4) selected by the user, the relay-device and current output-device assignments, and also the error list, using for selection.
  • Page 91: Saving

    OADING THE CONFIGURATION OF THE Settings of the MultiCONT are stored in a non-volatile FLASH memory (FMA). The content of this FLASH memory is replaced into the operative memory (OM) (which is a volatile memory) when MultiCONT is turned ON or restarted. Settings are saved automatically when exiting from the Menu.
  • Page 92: Error Codes

    (e.g. in solid applications, STD-300 transmitters may not respond until the amplification reaches operation conditions). ** A device that had been working perfectly suddenly stops responding. Possible reasons:  the device has gone wrong  broken cable  noisy HART line (See Main menu/MultiCONT config/HART test)  prw2101a0600p_01 92 / 105...
  • Page 93 *** A special error message belongs to sensor failures. This error can appear in 1: SE300-12 DIST the case of ultrasonic transmitters due to the breakdown of the transducer or Device responds but there is no during a dusty filling process, when if there is a display, a NoEcho message is SENSERR valid result because of sensor displayed.
  • Page 94: Hardware Protection Of The Settings

    Service menu  denying permission to run DEV detect, EXT detect under MultiCONT config The switch does not prevent modifications that do not influence the operation of the MultiCONT (such as language, backlight, user image, sorting, restart, etc) ...
  • Page 95: Fuse Replacement

    8. FUSE REPLACEMENT In order to change the fuse loosen four nuts fastening the front panel, carefully tilt the front panel forward, such that the cable band is not under tension and replace the fuse. Warning! Only use fuses specified in the table below: OWER UPPLY 85…255 V AC 50…60Hz...
  • Page 96: Servicing

    Load error Error when reading from FLASH memory No comp. Device Device is not NIVELCO compatible HART:Parse error The received data are not applicable HART:Invalid sel. The received HART command is unknown to the MultiCONT  prw2101a0600p_01 96 / 105...
  • Page 97: Other Messages

    Bad parameter sent during remote programming HART:Access restr. HART:Busy HART:Comm. not. imp. The received HART command is unknown to the MultiCONT Please wait! DEV detect cannot run due to periodic disturbance on the HART line, which causes continuous error! TOT cleared...
  • Page 98: Troubleshooting

    9.3.1. It is impossible to enter the „Main menu”/”Relays” or „Main menu”/„Current outputs” menu: There is no relay or current output in the unit. Check the number of relays and/or current outputs in „Main menu”/”MultiCONT config.”/”report” menu. 9.3.2. It is impossible to enter the „Main menu”/”Devices” menu: The device list is empty.
  • Page 99: Additional Information

    9.4.3. Use of Second HART Master ( Hand-Held or HART modem + Eview configuration software) Normally, there can only be one master in HART systems. Since the MultiCONT is a master, other masters can only be used if if the status of every device is set to inactive, i.e.
  • Page 100 "WIKA", "Paine", "Druck", "Bopp & Reuther Heinrichs", prw2101a0600p_01.doc "Rochester Instrument "SOR", "PR Electronics", 2010. december 11. Systems", "Elcon Instruments", "Jordan Controls", NIVELCO reserves the right to change "Ronan", "EMCO", "Valcom s.r.l.", technical specification without notice!  prw2101a0600p_01 100 / 105...
  • Page 101 2. T MultiCONT P-200 PPENDIX YSTEM OF THE Main display Bargraph display User display Relay assignment 4-20mA assignment Error report 1: SE300 LEV 2 M 1 2 3 4 5 1:SE300 LEV 1234567 1234567 Error report 1.234m - ------- - - - - - - - 01:SE300 :Reply 1.234...
  • Page 102 2. T MultiCONT P-200 (C PPENDIX YSTEM OF THE 1:SE380 Detected DEV 2:SP360 1:SE300 (01) 2:SP360 (- -) SP360  --SAVE----- 3:SCA380 (08) Current Source 4:STD330 (12) Percent 1:REL_O_S1 1: SE380 Level 2: ST360 Detected EXT Level % REL_O_S1 3: ST330...
  • Page 103 3. R PPENDIX ELAY ROGRAMMING  prw2101a0600p_01 103 / 105...
  • Page 104 4. C PPENDIX URRENT OUTPUT ROGRAMMING  prw2101a0600p_01 104 / 105...
  • Page 105 5. M PPENDIX EASUREMENT  prw2101a0600p_01 105 / 105...

Table of Contents