Heat recovery ventilator

Advertisement

.
M8 threaded rod
M8 nut holds the mounting plate
steady when the unit is lifted up
ceiling mounting plate
rubber cushion or sleeve
Picture 7: ceiling mounting example
1.5 Condensation drainage HRV 'FAIR' is equipped with a drain equipped with a plug. Depending on the
humidity of the apartment condensation may occur in some situations inside the HRV and, therefore, it is
advisable to lead the condensate through the drain (1/4'' in-thread) into the nearest floor drain or sink basin.
Condensation water pipe should not be connected directly into the sewerage without a water trap. The water
trap should be installed directly on the bottom of the HRV. Recommended water level in the water trap
should be 100 mm.
When the HRV maintenance work is done, it should be checked that there is enough water in the water
trap. Add more water if needed.
1.6 Introduction
Before using the machine, make sure that
- the device is installed according to these instructions and connected to the ductwork according to HVAC
plan.
-the filters are in their places and there are no extra items inside the device..
- the control panel is connected to the device.
Note! Don't switch the unit on if the service hatch is open.
8mm threaded rods
air
Outdoor
washer
8 mm nut
6
Exhaust air
(the duct is isolated)