For roll follower input applications, a 1,000 ohm TCS-200-1 Template . . . . . . . . . . . . 21 potentiometer with a rating of .5 watts, 10 percent tolerance, and .5 percent linearity is required for best...
(found in other Warner Electric tension control The front panel TENSION ADJUST feeds a small systems) are included in the TCS-200-1 series controls . voltage to a comparator, which compares this signal to a triangular wave . This is where the PWM pulse is Technical Specifications generated .
. connected brakes . Active high input . 2 . The TCS-200-1 cannot operate a single brake • Brake Run – Voltage to the brake is controlled by or brakes that require more than 4 .25 amps any of the sensor inputs and/or the front panel tension adjust .
Roll Follower Adjust Potentiometer (Optional) o 5 . Use shielded cable when possible for o 1 . Mount the roll follower potentiometer and connecting the TCS-200-1 to external switches, determine the amount of angular rotation at the the sensor potentiometer, PLC’s, and ultrasonic potentiometer shaft .
Refer to Figure 2 for actual wiring connections . terminal screw . Make sure the panel itself is properly grounded . 1 . Unlatch the front cover of the TCS-200-1 . Power Determine if 115 VAC or 230 VAC will be used to...
Page 8
3 of terminal block TB2 of the end of the remote potentiometer to terminal 11 TCS-200-1 . Secure the terminal screw . FACTORY FACTORY INSTALLED of terminal block TB1 in the TCS-200-1 . Snug INSTALLED JUMPERS JUMPERS NEUTRAL NEUTRAL terminal only .
10 11 end of the roll follower potentiometer to terminal external mode selector switch . 11 of terminal block TB1 of the TCS-200-1 . Do SEE FIG. 3 not tighten the terminal screw . Snug down only . FOR THIS...
Page 10
CAUTION ELECTRO DISC 2 WIRE TENSION section of this manual . THAN ONE MAGNET SEE FIG. 5 SEE FIG. 5 block TB1 of the TCS-200-1 . Tighten the screw . DO NOT WIRE BRAKES CAUTION BRAKES BETWEEN TERMINALS FOR JUMPER...
1 . Apply power to the control system . o 4 . Locate the five-position jumper mounted on o 2 . Check that the green LED marked “power” is the board on the inside cover of the TCS-200-1 . illuminated . Remove the two position black selector from positions 4 &...
Page 12
. o 10 . Slowly rotate the tension adjust potentiometer from fully counterclockwise to full clockwise, noting the output voltage increases from zero to approximately 24 VDC at maximum output . 12 Warner Electric • 800-825-9050 P-2003-2 • 819-0420...
Page 13
. terminal block TB2 and secure the leads to the Proceed to step 14 in next section . terminals . o 14 . Reapply power to the control system . Warner Electric • 800-825-9050 P-2003-2 • 819-0420 13...
Page 14
0 .8 VDC, refer to mA with the positive (+) lead connected to terminal 1 Table 1 for the nominal output current available . and the negative (-) lead connected to the wire . 14 Warner Electric • 800-825-9050 P-2003-2 • 819-0420...
Page 15
1 .3 VDC, decrease the front panel tension adjust until a 1 .3 VDC reading is obtained . o 8 . Place the mode selector switch in the brake “stop” position . The meter should read Warner Electric • 800-825-9050 P-2003-2 • 819-0420 15...
Page 16
. Note: Refer to Table 2 and Table 3 for various inputs o 25 . Close the cover of the TCS-200-1 and latch it by tightening the screw that is provided . and outputs when using the analog input system .
Page 17
13 . Set the front panel tension adjust for the and tighten the terminal screw . starting torque required for the application . Proceed to step 19 . o 14 . Start the machine and draw the web through . Warner Electric • 800-825-9050 P-2003-2 • 819-0420 17...
Page 18
Note: If start-up and adjustment procedures do not provide the desired results, consult the troubleshooting section of this manual . o 21 . Close the cover of the TCS-200-1 and latch by tightening the screw that is provided . 18 Warner Electric • 800-825-9050...
Recheck wiring and magnet connections and rewire if necessary . Local or remote tension adjust Recheck set-up procedures for the incorrectly set mode of operation in which the control is used . Readjust if necessary . 20 Warner Electric • 800-825-9050 P-2003-2 • 819-0420...
Page 22
Warner Electric LLC be liable for consequential, indirect, or incidental damages of any kind incurred by reason of the manufacture, sale or use of any defective product . Warner Electric LLC neither assumes nor authorizes any other person to give any other warranty or to assume any other obligation or liability on its behalf .