Electric Heater Electrical Data; Field Installed Electric Heater Kit Availability - Bosch HK050-1XXX-RE Installation Instructions Manual

Hk series electric heater package
Table of Contents

Advertisement

14 HK Series

Electric Heater Electrical Data

Table 3:
Heater
Model
208
3.6
HK050-1XXX-Res
HK075-1XXX-Res
5.4
7.2
HK100-1XXX-Res
10.8
7.2
HK150-1XXX-Res
3.6
14.4
5.4
HK200-1XXX-Res
5.4
* The fan motor and electric heat elements should be rewired to be on the same circuit. MCA and MOCP
include 7 amps to accommodate for the additional motor load. 7 is the amp draw on a 1 HP motor.

Field Installed Electric Heater Kit Availability

Table 4:
Unit
5 kW
Model
TA025 HK050-1001 HK075-1001 HK100-1001
Vertical/
TA035 HK050-1002 HK075-1002 HK100-1002
Counter
flow
TA049 HK050-1002 HK075-1002 HK100-1002 HK150-1001 HK200-1001 CE049 HK050-1002 HK075-1002 HK100-1002 HK150-1001 HK200-1001
Packaged
TA061 HK050-1002 HK075-1002 HK100-1002 HK150-1001 HK200-1001 CE061 HK050-1002 HK075-1002 HK100-1002 HK150-1001 HK200-1001
Units
TA071 HK050-1002 HK075-1002 HK100-1002 HK150-1001 HK200-1001 CE071 HK050-1002 HK075-1002 HK100-1002 HK150-1001 HK200-1001
TA025 HK050-1004 HK075-1004 HK100-1004
TA035 HK050-1004 HK075-1004 HK100-1004
Horizontal
Packaged
TA049 HK050-1004 HK075-1004 HK100-1004 HK150-1002 HK200-1002 CE049 HK050-1004 HK075-1004 HK100-1004 HK150-1002 HK200-1002
Units
TA061 HK050-1004 HK075-1004 HK100-1004 HK150-1002 HK200-1002 CE061 HK050-1004 HK075-1004 HK100-1004 HK150-1002 HK200-1002
TA071 HK050-1004 HK075-1004 HK100-1004 HK150-1002 HK200-1002 CE071 HK050-1004 HK075-1004 HK100-1004 HK150-1002 HK200-1002
TA025 HK050-1005 HK075-1005 HK100-1005
TA035 HK050-1005 HK075-1005 HK100-1005
Vertical/
Counter
TA049 HK050-1005 HK075-1005 HK100-1005 HK150-1005 HK200-1003 CE049 HK050-1007 HK050-1007 HK050-1007 HK150-1004 HK200-1005
flow air
Handlers
TA061 HK050-1005 HK075-1005 HK100-1005 HK150-1005 HK200-1003 CE061 HK050-1007 HK050-1007 HK050-1007 HK150-1004 HK200-1005
TA071 HK050-1005 HK075-1005 HK100-1005 HK150-1005 HK200-1003 CE071 HK050-1007 HK050-1007 HK050-1007 HK150-1004 HK200-1005
TA025 HK050-1005 HK075-1005 HK100-1005
TA035 HK050-1006 HK075-1006 HK100-1006
Horizontal
air
TA049 HK050-1006 HK075-1006 HK100-1006 HK150-1003 HK200-1004 CE049 HK050-1007 HK050-1007 HK050-1007 HK150-1004 HK200-1005
Handlers
TA061 HK050-1006 HK075-1006 HK100-1006 HK150-1003 HK200-1004 CE061 HK050-1007 HK050-1007 HK050-1007 HK150-1004 HK200-1005
TA071 HK050-1006 HK075-1006 HK100-1006 HK150-1003 HK200-1004 CE071 HK050-1007 HK050-1007 HK050-1007 HK150-1004 HK200-1005
6 720 220 328
kW
Number
Hz
of Stages
240
4.8
1
60
7.2
1
60
9.6
1
60
14.4
1
60
9.6
1
60
4.8
1
60
19.2
1
60
7.2
1
60
7.2
1
60
CE / TA Field Installed Electric Heater Kit Model Numbers
7.5 kW
10 kW
15 kW
X
X
X
X
X
X
X
X
electric Heater electrical Data
Heater
Amps
Phase
208
240
1
17.3
20.0
1
26.0
30.0
1
34.6
40.0
1
51.9
60.0
1
34.6
40.0
1
17.3
20.0
1
69.2
80.0
1
26.0
30.0
1
26.0
30.0
Unit
20 kW
5 kW
Model
X
CE025 HK050-1001 HK075-1001 HK100-1001
X
CE035 HK050-1001 HK075-1001 HK100-1001
X
CE025 HK050-1004 HK075-1004 HK100-1004
X
CE035 HK050-1004 HK075-1004 HK100-1004
X
CE025 HK050-1007 HK050-1007 HK050-1007
X
CE035 HK050-1007 HK050-1007 HK050-1007
X
CE025 HK050-1007 HK050-1007 HK050-1007
X
CE035 HK050-1007 HK050-1007 HK050-1007
Subject to change without prior notice
MCA*
Circuit
Fuses
208
240
F1/F2
30.4
33.8
F1/F2
41.2
46.3
F1/F2
52.0
58.8
73.7
83.8
F1/F2
52.0
58.8
F3/F4
30.4
33.8
95.3
108.8
100
F1/F2
41.2
46.3
F3/F4
41.2
46.3
7.5 kW
10 kW
15 kW
X
X
X
X
X
X
X
X
Revised 05-13
MOCP*
208
240
35
35
45
50
55
60
80
90
55
60
35
35
110
45
50
45
50
20 kW
X
X
X
X
X
X
X
X

Advertisement

Table of Contents
loading

This manual is also suitable for:

Hk075-1xxx-reHk100-1xxx-reHk150-1xxx-reHk200-1xxx-re

Table of Contents