SETTING THE
VENTILATION
PROFILE
As the default factory setting, the
following voltages have been set for the
cooker hood:
Away profile 70V
At home profile 135V
Boost profile 230V
To change these values, move the
transformer wires to more suitable
connectors (see the wiring diagrams).
Measuring and adjusting performance values
Standard ventilation
The volume flow rate of the air inside the cooker hood is measured
with the damper closed and, where required, adjusted based on the
static pressure loss and the performance scheme of the cooker hood.
• The static pressure loss is measured from the hole in the damper
using the measuring tube found in the accessory bag (see figure).
• Determine the volume flow rate from
the performance scheme based
on the measured pressure and the
number of open holes in the damper.
Adjustment:
• Cover the required number of holes
in the damper with the magnetic
strip that is delivered with the cooker
hood.
Boost ventilation
The volume flow rate of the air inside
the cooker hood is measured with
the damper open based on the static
pressure loss and the performance
scheme of the cooker hood.
• Measure the static pressure
loss of the cooker hood. The
measuring point must be located 2
times the duct diameter above the
outlet collar of the cooker hood
(see figure).
• Determine the volume air flow based on the measured pressure
and the performance scheme (with the damper open).
External electrical connection to the ventilation unit
TRANSFORMER
Underneath the lid
of the left electric box
Opening the door of a Vallox ventilation unit
Cuts power supply to the cooker hood.
If the cooker hood has been connected
to some other device, a switch must
be added in the immediate vicinity
of the hood that cuts power supply
to both N and L.
External electrical connection to a roof fan
TRANSFORMER
Underneath the lid
of the left electric box
dp
dp
Measuring point,
min. 2 x duct diameter
Vallox Oy | Myllykyläntie 9-11 | 32200 LOIMAA | FINLAND
www.vallox.com | Exchange +358 10 7732 200 | Aftersales +358 10 7732 270
MOTHERBOARD
OF THE PTC AC HOOD
SPEED SWITCH
S1 S2 S3 out
E.g. Vallox 95/75
MOTHERBOARD
OF THE PTC AC HOOD
SPEED SWITCH
S1 S2 S3 out
400
Adjustment position
300
200
L
, dB(A)
45
pA
40
100
90
80
70
35
60
50
30
40
30
25
20
10
2
3
4
5
6 7 8 9 10
Air flow, dm /s
Standard ventilation (settings 2-8)
2 = 20 holes open
3 = 30 holes open
4 = 40 holes open
5 = 50 holes open
NOTE!
Do not connect
the power cord
N
L
N
L
L1
N
L1
1
2
3
10A
Distribution board
AC-fan
2
3
4
5
6
7
8
Damper open
45
40
35
30
25
20
30
40 50 60 70
6 = 60 holes open
7 = 70 holes open
8 = 80 holes open
L
N