V D 4 G I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N S
18
5. Description
Accessories with the same number are alternatives.
9 Position contact (-BGT3)
It is used in conjunction with the locking magnet in
the operating mechanism (-RLE1) to prevent remote
closing during movement in the cubicle.
It is only supplied for the withdrawable circuit-
breaker version for UniGear ZS1 switchgear and
PowerCube modules.
It cannot be supplied when transmitted contacts in
the truck are required (-BGT1; -BGT2).
10 Transmitted contacts in truck (-BGT1;-BGT2)
Transmitted contacts of withdrawable circuit-
breaker (installed in circuit-breaker truck - only for
withdrawable circuit-breaker VD4G/P).
These contacts are additional or alternative to the
position contacts (for signaling circuit-breaker
withdrawn) in the cubicle. They also act as position
contacts (-BGT3).
Contacts -BGT1 and BGT2 have the same general
and electrical characteristics as auxiliary contacts
"7b. -BGB1, -BGB2, -BGB3".

Advertisement