Page 3
Pointek CLS 200 is to be used only in the manner outlined in this instruction manual. The Pointek CLS 200 capacitance level switch provides output on high or low process material levels. When the measured material approaches or contacts the switch’s probe, an increase in capacitance is sensed and a high level alarm can be triggered.
SPECIFICATIONS Power: » 12 - 250 V ac/dc 50/60 Hz, 2 VA / 2 W max Environmental: » location: » indoor / outdoor » altitude: » 2000 m max » ambient temperature: » -40 to 85 °C (-40 to 185 °F) »...
Page 5
Probe: length, max. mounting * extension tensile, max. sensor ® Standard 5.5 m (18 ft) " NPT, 1" BSP, 316 stainless n / a Kynar " BSP, steel 316 stainless steel ® Sanitary 5.5 m (18 ft) 1", 1 " and 2", 3A 316 stainless n / a Kynar...
This product is susceptible to electrostatic shock. Follow proper grounding procedures. The Pointek CLS 200 standard probe length is normally mounted into the vessel top (high detection alarm) or through the tank wall at the detection level (high or low detection alarm).
Page 7
DIMENSION CLS 200 VERSIONS Standard 120 mm 145 mm (4.7") (5.7") electronics / enclosure probe / sensor * 120 mm (4.7") 76 mm (3") 2 " NPT 59 mm clip (2.3") Standard with Thermal Isolator 245 mm 120 mm (9.7") (4.8") thermal isolator...
Page 8
Sanitary 100 mm 165 mm (3.9") (6.5") electronics / enclosure probe / sensor * 120 mm (4.7") 76 mm (3") sanitary Tri-clamp 2 " NPT 59 mm clip (2.3") Sanitary with Extension 165 mm 5.5 m (6.5") (10 ft) max. extension sensor 23 mm (0.9") Ø...
Page 9
Cable 76 mm (3") clip 120 mm 59 mm (4.7") (2.3") electronics / 2 " NPT enclosure 145 mm (5.7") nominal value flexible extension * cable to set the sensor at the desired alarm point, by shortening the cable, refer to Appendix \ 35 m Shortening the Cable (115 ft)
MOUNTING DO’S AND DONT’S STANDPIPES < 50 mm (2") > 100 mm (4") Ø MULTIPLE UNITS 100 mm (4") min 100 mm (4") min 100 mm (4") min Mount diagonally if there is Sensors must be 100 mm apart. not enough vertical space. PL-540...
DO’S and DONT’S (cont’d) PROCESS CONCERNS keep out of path of falling material consider material angle of repose 50 mm (2") protect probe from falling material tensile load must not exceed probe or vessel rating avoid areas where material build up occurs PL-540...
Page 13
INTERCONNECTION Loosen the lid clip and remove the lid. identification label (underside of lid) Switch and potentiometer settings are for illustration purposes only. Refer to Operation \ Setup. All field wiring must have insulation suitable for at least 250 V. Relay contact terminals are for use with equipment having no accessible live parts and wiring having insulation suitable for at least 250 V.
RELAY OUTPUT CONNECTION relay shown in de-energized state, K2 contacts rated for 8 A at 250 V ac / 5 A at 30 V dc SOLID STATE SWITCH solid state switch to customer’s control or instrumentation device Switch shown in de-energized state, K3 contact rated for 250 V ac / 300 V dc, 100 mA max, non-polarized.
ANCILLARY 2-WIRE OUTPUT CONNECTION output optically isolated switch customer supplied (Phoenix DEK-OE-5DC/48DC/100 or equivalent) V dc refer to Power Connection POWER CONNECTION Nominal 24 V dc 48 V dc 22 – 26 V 46 – 50 V Ω Ω 12 - 250 V ac / dc PL-540...
OPERATION SET UP Set up can be done in the field with the Pointek CLS mounted into process, or in the shop prior to mounting. Dip Switch 1 Set on to open the alarm relay immediately when the sensor detects a change in contact. Use this setting when time is critical.
Page 17
delay on delay off fail-safe delay test sensitivity S1 - 1 S1 - 2 S1 - 3 S1 - 4 S1 - 5 disabled disabled high test normal enabled enabled normal START UP After the CLS is properly mounted and the switch bank set up, apply power to the unit. The green LED (L3) lights to indicate the unit is powered and operational.
ALARM OUTPUT ALARM OUTPUT STATUS high alarm alarm SETPOINT ADJUSTMENT In order to assist you in properly adjusting the alarm setpoint for reliable and accurate detection of the process material, we have categorized the materials and applications into three cases. Follow the setup procedure associated to the case which covers your application. Case 1: this is the general case encountered in most applications, characterized by the following:...
Page 19
trip point switches delay sensor power status (green) output (yellow) status (red) Case 1 - insure that L3 (green) is ‘ on ’ Preamble: - turn both potentiometers, P1 and P2, fully ccw (counterclockwise) - set S1 switches 1 to 4 ‘ off ’ and S1 switch 5 to ‘ on ’ (normal sensitivity) 1.
Page 20
DELAY The alarm actuation can be delayed for either or both ‘on alarm’ and ‘off alarm’ conditions. The selection is made by setting S1-1 and S1-2, refer to Set Up \ Switch Bank. The amount of delay is adjustable from 1 to 60 seconds by setting potentiometer, P1. After completing the set up, replace the Pointek CLS lid and lid clip.
TROUBLESHOOTING Symptom Observation Action No alarm response L3 off check power supply Alarm doesn’t switch when L1 doesn’t respond to check sensitivity S1-5, sensor is uncovered. uncovering the sensor. sensor (and zener barrier, if used) L1 responds to uncovering check that relay changes the sensor state when S1-3 is toggled Alarm doesn’t switch when...
APPENDIX SHORTENING THE CABLE Allowed in general purpose version only, see device nameplate. Preamble Measure the actual length of the cable and subtract the desired length to determine the length to be cut off in step 5. e.g. actual length 10 m desired length - 9 m...
Page 23
tension block connection 3. Remove the insulation covering the solder connections. 4. Unsolder the connections. Do not cut the connection to the probe leads, as this can render them too short to work with later. 5. Remove the sheathing around the tension block. Remove the block for reuse in step 7, and cut off the excess length of cable.
Page 24
12. Re-dress the probe sleeve thread with Teflon tape or sealant. 13. Reassemble the sleeve and cable gland. Insure that the cable is not turned excessively, as this could break the leads. 14. Check unit for proper operation. PL-540...