Page 1
E8 Controller for MLX & EXT Series Boilers • EXT 2677 • EXT 3060 Boiler Communications Module (BCM) for MLX and EXT Series Boilers Revised: 06/05/2013 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288 06/05/13 Page 1 of 112...
Page 2
The information contained in this manual is subject to change without notice from AERCO International, Inc. AERCO makes no warranty of any kind with respect to this material, including but not limited to implied warranties of merchantability and fitness for a particular application. AERCO International is not liable for errors appearing in this manual.
Viewing Constant Set Point ................45 5.2.4 Configuring Set Point High and Low Limits Per Outside Temperature Sensor . 45 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288 06/05/13 Page 3 of 112...
Page 4
Modbus Software Set-Up ................74 7.7.1 BCM Set-Up for Modbus Operation ..............74 7.7.2 Monitoring and Configuration Only ..............75 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288 06/05/13 Page 4 of 112...
E8 Controller and the Boiler Communications Module (BCM) mounted on the front of the unit. Sections 3, 4, 5, 6, and 8 provide descriptions and procedures for the E8 Controller. Sections 7, 9, and 10 provide similar information for the BCM.
Page 8
GF-115-C Modulex E8 Controller and BCM Operations and Maintenance Manual OMM-0084_0D (This page left intentionally blank) AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288 06/05/13 Page 8 of 112...
The E8 Controller is housed in a compact enclosure measuring 5.7” (145 mm) x 3.9” (100 mm). The Controller is mounted on the front of the Modulex Boiler and contains all of the controls, indicators and displays necessary to adjust, operate and troubleshoot the Modulex Boiler.
A photo of the module is shown in Figure 2-2 below. Additional information for the BCM component can be found in Section 7, 9, and 10. Figure 2-2: Modulex BCM (Boiler Communications Module) AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288 06/05/13 Page 10 of 112...
Figure 3-1 describes the types of information provided on the LCD display when in NORMAL Mode (door closed). Note that the display in the illustration is only an example, and that an E8 Controller in service will show information appropriate for its configuration.
3.1.3 MENU Mode Operation (Door Open) Opening the E8 controller hinged door reveals the E8 controls (Figure 3-3) and initiates the AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288 06/05/13...
Rotary Knob: Used to navigate through menus and parameters or adjust parameters. 3.2 Software Menus Software menus are divided into five main menus, each with a set of sub-menus (Table 3-1). AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288 06/05/13 Page 13 of 112...
Page 14
Operations and Maintenance Manual OMM-0084_0D The rotary knob on the front of the E8 Controller is used to sequentially cycle through the menus and the sub-menus. Two small arrows at the bottom of the display point to the selected menu and sub-menu name, respectively. Note that some menus and sub-menus are read-only or not available, according to the boiler used and the initial startup configuration.
5. Repeat steps 2, 3 and 4 to view the remaining main menus and their associated sub-menus. The remaining main menus are: USER, TIME PROGRAM, EXPERT, EXPERT HS (Not Applicable to Modulex), and GENERAL. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288 06/05/13 Page 15 of 112...
Program Key. The Change LED displayed Displayed will turn off indicating the new value has been saved. value Value Saved! AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288 06/05/13 Page 16 of 112...
Refer to Section 8 for additional information on functions marked “Not Applicable” in the illustrations and tables provided. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288 PR1: 02/23/12 Page 17 of 112...
T-FLOW N-OPT-TIME RETURN SOLAR M/F T-MF1 T-MF2 T-MF3 T-MF4 T-COLLECTOR T-DHW T-DHW L RETURN Figure 4-1: DISPLAY Menu Flow Chart AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288 06/05/13 Page 18 of 112...
Page 19
Not Applicable T-CIRCL Not Applicable Press Program Key to exit the HOT RETURN WATER Sub-Menu. Table 4-1: DISPLAY Menu Listing (Continued) AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288 06/05/13 Page 19 of 112...
Page 20
Currently not used T-DHW Not Applicable Currently not used T-DHW L Not Applicable Press Program Key to exit SOLAR RETURN M/F Sub-Menu. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288 06/05/13 Page 20 of 112...
T-LIMIT N HEATSLOPE OPTIM HEAT MAX OPT-TIME ECONO OPTI PC ENABLE RETURN SOLAR M/F RETURN Figure 4-2: USER Menu Flow Chart AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288 06/05/13 Page 21 of 112...
Page 22
Not Applicable T-DHW 3 Not Applicable BOB-VALUE Not Applicable CIRCL-P- Not Applicable Press Program Key exit HOT WATER Sub- RETURN Menu. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288 06/05/13 Page 22 of 112...
Page 23
RETURN. Press Program Key again to RETURN redisplay SOLAR M/F. Turning the Rotary Knob clockwise will advance thd display to the TIME PROGRAM Menu. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288 06/05/13 Page 23 of 112...
HEATSOURCE 2 STORAGE HS 2 BUFFER RETURN CONTINUED ON SHEET 2 Figure 4-4: EXPERT Menu Flow Chart (Sheet 1 of 2) AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288 06/05/13 Page 25 of 112...
Page 26
RELAY FUNC 4 T-MF 4 SETP MF4 HYST F15 FUNCTION RETURN Figure 4-4: EXPERT Menu Flow Chart (Sheet 2 of 2) AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288 06/05/13 Page 26 of 112...
Page 27
32.0°F – 248.0°F 185.0°F Stop/Start voltage level. Going below/above CURVE 11-UO 0.00V – 10.00V 1.00 this setting will stop/start the Boiler. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288 06/05/13 Page 27 of 112...
Page 28
Not Applicable SEQUENCE 1 Boiler sequence 1 12345678 SEQUENCE 2 Boiler sequence 2 87654321 Table 4-3: EXPERT Menu Listing (Continued) AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288 06/05/13 Page 28 of 112...
Page 29
Not Applicable LOAD THROUGH Not Applicable RETURN Press Program Key to exit HOT WATER Sub-Menu. Table 4-3: EXPERT Menu Listing (Continued) AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288 06/05/13 Page 29 of 112...
Page 30
Press Program Key to exit HEAT CIRCUIT 1 RETURN (or 2) Sub-Menu. Table 4-3: EXPERT Menu Listing (Continued) FUNCTION DESCRIPTION ENTRY DEFAULT AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288 06/05/13 Page 30 of 112...
5.0 V 4.0 V 0.1 V 68°F 194°F 5.0 V 4.5 EXPERT HS Menu (Not Used) (Not applicable to Modulex boilers) AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288 06/05/13 Page 31 of 112...
The GENERAL Menu contains a DATE/TIME Menu and a SERVICE Menu. 4.6.1 DATE / TIME Menu This Sub-Menu is used to set the time, date, holiday (vacation) schedule and, where AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288 06/05/13 Page 32 of 112...
Page 33
Set current time (min., hours) 00:00 – 24:00 YEAR Set current year XXXX MONTH Set current month 01 – 12 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288 06/05/13 Page 33 of 112...
Function values. When prompted by a “CODE NO.” display, enter 0000 (four zeros) by pressing the Program Key four (4) times. This will allow function access. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288 06/05/13...
Page 35
Controlller. These relays are numbered 00 through 11 and are defined as shown below. CODE NO. Entry is required to access these relays. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288 06/05/13 Page 35 of 112...
Page 36
Table 4-6: SERVICE Menu Listing (Continued) FUNCTION DESCRIPTION REMARKS SENSOR TEST Sub-Menu Flow temperature heating circuit 1 or temperature multifunction 1 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288 06/05/13 Page 36 of 112...
Initial startup of the Modulex Controller requires a number of one-time entries to be made in the initial INSTALLATION Menu that appears in the display when the E8 controller door is first opened. Table 4-7 on the next page lists the description, entry range, and default entry for all parameter.
Page 38
LANGUAGE Set Language ENGLISH TIME Set current time (min., hrs) 00:00 – 24:00 YEAR Set current year XXXX (4 digits) AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288 06/05/13 Page 38 of 112...
CAP/MODULE Function (Setting Max. Kw per Burner) 1. Press the Program Key. The display will show CODE NO., requesting the valid code to be AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288 06/05/13...
Table 4-8 lists the available Function selections for Multi-Function (MF) Relays 1 thru 4: Table 4-8: Relay 1-4 Functions FUNCTION DESCRIPTION No MF Relay Function Header Pump AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288 06/05/13 Page 40 of 112...
Page 41
Solid Fuel Boiler Integration (Not Applicable) Solar Integration Return Flow Temperature Increase HS1 Return Flow Temperature Increase HS2 Return Flow Temperature Increase Via Buffer Storage AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288 06/05/13 Page 41 of 112...
The outdoor air sensor MUST be connected as described in paragraph 5.1.1 above, prior to configuring the Controller for Indoor/Outdoor Reset Mode operation. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288 PR1: 02/23/12 Page 42 of 112...
Page 43
Press the Program Key to exit the HTG CIRCUIT 1 sub-menu. Outside Temperature ( F ) Figure 5-1: Heat Slope Diagram AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288 06/05/13 Page 43 of 112...
Operations and Maintenance Manual OMM-0084_0D 5.1.3 Viewing the Boiler Setpoint The setpoint temperature setting is viewed in the E8 controller display as shown below. Viewing the Boiler Setpoint Turn the Rotary Knob to the DISPLAY menu. The first sub-menu displayed will be INSTALLATION.
180º F whenever the outside temperature is 15º F or below, and 120º F whenever the outside temperature is 60º F or higher. Four parameters must be set in the E8 Controller to accomplish this. They are: HEATSLOPE, MAX T-FLOW, MIN T-FLOW, and MAX T-COLL.
Continue scrolling through the HTG CIRCUIT 1 sub-menu until RETURN is displayed. Press the Program Key to exit the HTG CIRCUIT 1 sub-menu. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288 06/05/13 Page 46 of 112...
Page 47
Continue scrolling through the HTG CIRCUIT 1 sub-menu until RETURN is displayed. Press the Program Key to exit the HTG CIRCUIT 1 sub-menu. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288 06/05/13 Page 47 of 112...
1 (F-15) and 2 (GND) of connector number 3 (III) on the rear of the Controller. See Section 6 for illustrations and pin-outs of the connectors located on the rear of the Controller. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288 06/05/13 Page 48 of 112...
SOLAR / MF item, the EXPERT HS menu will be displayed. this occurs, slowly turn Rotary Knob counterclockwise until SOLAR / MF is again displayed. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288 06/05/13 Page 49 of 112...
10. With the desired high voltage limit displayed, press the Program Key to set the U2 voltage. The red LED will go off. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288 06/05/13 Page 50 of 112...
7. Press the Program Key to return to exit the INSTALLATION sub-menu. To view the remote set point temperature, proceed to paragraph 5.3.5. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288 06/05/13 Page 51 of 112...
ON/OFF switch to the OFF position, then back to the ON position. This is necessary to ensure that the Controller recognizes the added sensor. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288 06/05/13...
8. With THERM INPUT again displayed and the red LED lit, turn Rotary Knob to change to 00 for sensor operation. 9. Press Program Key to store 00 setting for THERM INPUT. Red LED is off. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288 06/05/13 Page 53 of 112...
Press Program Key to store the temp setting. The red LED will go off. Continue scrolling through the HOT WATER sub-menu until RETURN is displayed. Press the Program Key to exit the sub-menu. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288 06/05/13 Page 54 of 112...
2. Press the Program Key to enter the INSTALLATION sub-menu. 3. Turn the Rotary Knob clockwise until T-COLL DES is displayed along with corresponding temperature reading. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288 06/05/13 Page 55 of 112...
Connector “I” and then set the boiler to Standby mode ( ). To set the boiler to Standby mode, close the swing-down front panel door of the E8 and turn the wheel counterclockwise until the Standby symbol ( ) is displayed. With terminals 3 and 4 closed, the Standby symbol, and others in the display, will be blinking.
Page 57
GF-115-C Modulex E8 Controller and BCM Operations and Maintenance Manual OMM-0084_0D (This page left intentionally blank) AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288 06/05/13 Page 57 of 112...
F15 = 0-10V input/light sensor/Room sensor for heating circuit 2 (2+3) F17 = Pulse counter for output measurement (1+2) Data line CAN bus (3+4) Power supply CAN bus AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288 PR1: 02/23/12 Page 58 of 112...
• BCM provides a fault relay which energizes when any fault condition occurs in the Modulex Boiler. • BCM serves as a Back-up Controller in the event that the primary E8 Controller fails. • BCM can be selected as the Primary Controller instead of the E8.
Page 63
Modulex Boiler 10-Pos. Rotary on the input Modbus or Ebus Network. Switch AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288 06/05/13 Page 63 of 112...
BCM. However, if the cause of the fault has not been corrected, the Fault Relay will again be activated. SWITCHES Figure 7-3: BCM Fault Relay & Reset Switch Wiring AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288 06/05/13 Page 64 of 112...
When the BCM is configured as the Back-Up Controller for the E8, it will assume control of the Modulex Boiler if the E8 fails. In the event of an E8 Controller failure, the BCM will operate the Modulex Boiler in the Constant Setpoint Mode (default setpoint = 180°F [82°C]). The primary Boiler Pump must also be wired to the BCM so it will run when the BCM assumes control in the Back-Up Mode.
NOTE: When the BCM is configured as the primary controller, the E8 will display the fault code “E200”. The BCM can be configured as the Primary Controller, instead of the E8, when it is connected to a Modbus Network. However, the E8 must be disconnected from the e-Bus connection on the BCM Board (see Paragraph 7.4.3).
Modbus wiring connections are made at terminals 1 and 2 of BCM connector Y2 as shown in Figure 7-7. BCM FRONT VIEW Figure 7-7: BCM Modbus (RS485) Connections AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288 06/05/13 Page 67 of 112...
If the BCM was retrofitted in the field utilizing Technical Service Bulletin 2007-07, refer to this bulletin and disconnect CBL 24 from Connector VII on the E8 Controller. However, if the Modulex Boiler was shipped with the BCM factory-installed, it will contain a 3-position switch mounted above the BCM (Figure 7-8).
7.4.4 AERCO BMS II/ACS Master to BCM Slave Wiring Connections. The AERCO BMS II/ACS contains a RS232 port for connection to an EMS/BAS or personal computer. In addition, the BMS II/ACS contains a RS485 port for connection to the BCM’s Modbus input.
1K ohm resistor as shown in Figure 7-9. DO NOT install this bias resistor if the controlling Master is an AERCO BMS II or ACS. Bias will be provided by the BMS II/ACS DIP switches. The last unit in the chain must be energized (even if disabled) to enable bias.
Page 71
Also, twisted-pair wiring shields should only be terminated at the controlling Master for the Modbus Network. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288 06/05/13 Page 71 of 112...
Page 72
GF-115-C Modulex E8 Controller and BCM Operations and Maintenance Manual OMM-0084_0D AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288 06/05/13 Page 72 of 112...
Page 73
GF-115-C Modulex E8 Controller and BCM Operations and Maintenance Manual OMM-0084_0D AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288 06/05/13 Page 73 of 112...
See Section 9 of this document and Section 2 of GF-124 for Modbus points for the BCM and BMS II/ACS. Figure 7-12: Location of BCM Address Selection Switch SW1 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288 06/05/13 Page 74 of 112...
A multiple Modulex boiler plant offers inherent standby protection and ease of installation along with longevity. In a multiple boiler plant of over two boilers, the use of an AERCO Boiler Management System II (BMS II) Model 5R5-384/AERCO Control System (ACS) is recommended for maximum efficiency and flexibility of operator control.
Refer to BMS II Operations and Maintenance Manual GF-124/ACS Manual GF-131, and Product Spec BMS-II for details. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288 06/05/13 Page 76 of 112...
Page 77
GF-115-C Modulex E8 Controller and BCM Operations and Maintenance Manual OMM-0084_0D (This page intentionally blank) AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288 06/05/13 Page 77 of 112...
Temperature of storage tank 3 (e.g. solar T-STORAGE 3 pool-heating) MODGRAD Modulation degree of HS (BUS) Press Program Key to exit RETURN INSTALLATION Sub-Menu. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288 PR1: 02/23/12 Page 78 of 112...
Page 79
Upper hot water temperature Currently not used T-DHW L Hot water temperature in-feed RETURN Press Program Key to exit SOLAR M/F Sub-Menu. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288 06/05/13 Page 79 of 112...
Circulation Pump for Domestic Hot CIRCL-P-DHW 00, 01 (OFF/ON) 00 = OFF Water Press Program Key exit HOT WATER RETURN Sub-Menu. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288 06/05/13 Page 80 of 112...
Page 81
Press Program Key again to redisplay RETURN SOLAR M/F. Turning the Rotary Knob clockwise will advance thd display to the TIME PROGRAM Menu. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288 06/05/13 Page 81 of 112...
See prev. OFF: 22:00h RETURN Press Program Key to exit CIRCL sub-menu Table 8-3: TIME PROGRAM Menu Sub-Menus and Parameters (Continued) AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288 06/05/13 Page 82 of 112...
Page 83
22:00h Press Program Key to exit HOTW – RETURN PROG sub-menu. Table 8-3: TIME PROGRAM Menu Sub-Menus and Parameters (Continued) AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288 06/05/13 Page 83 of 112...
Page 84
HTG PROG 1 above. Press Program Key to exit HTG – PROG 2 sub- RETURN menu. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288 06/05/13 Page 84 of 112...
CURVE 11-UO 0.00V – 10.00V 1.00 this setting will stop/start the Boiler. Table 8-4: EXPERT Menu Sub-Menus and Parameters (Continued) AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288 06/05/13 Page 85 of 112...
Page 86
SEQUENCE 1 Boiler sequence 1 12345678 SEQUENCE 2 Boiler sequence 2 87654321 Table 8-4: EXPERT Menu Sub-Menus and Parameters (Continued) AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288 06/05/13 Page 86 of 112...
Page 87
01 = ON 00 = OFF LOAD THROUGH 00 (OFF) 01 = ON Table 8-4: EXPERT Menu Sub-Menus and Parameters (Continued) AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288 06/05/13 Page 87 of 112...
Page 88
0 hours) 48°F Heating slope distance. 32°F – 194°F SLOPE OFFSET (N/A) Table 8-4: EXPERT Menu Sub-Menus and Parameters (Continued) AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288 06/05/13 Page 88 of 112...
Press Program Key to exit SOLAR M/F RETURN Sub-Menu. 8.5 GENERAL Menu The GENERAL Menu contains a DATE/TIME Sub-Menu and a SERVICE Sub-Menu. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288 06/05/13 Page 89 of 112...
The SERVICE Menu contains all the test and diagnostic functions/values required for Customer Service Engineers to troubleshoot the equipment in a timely manner. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288 06/05/13 Page 90 of 112...
Page 91
Heat generator /header temperature Outside temperature Table 8-6: GENERAL Menu / SERVICE Sub-Menus and Parameters (Continued) FUNCTION DESCRIPTION REMARKS SENSOR TEST Sub-Menu AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288 06/05/13 Page 91 of 112...
Page 92
DO NOT USE RESET EXPERT DO NOT USE RESET T-PRG 00 DO NOT USE RETURN Exit level using Program Key AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288 06/05/13 Page 92 of 112...
Page 93
GF-115-C Modulex E8 Controller and BCM Operations and Maintenance Manual OMM-0084_0D (This page left intentionally blank) AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288 06/05/13 Page 93 of 112...
No more than 1.5 character times of silence between received and transmitted characters. Heartbeat Timeout: Adjustable (0 or 1 – 240 seconds) AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288 PR1: 02/23/12 Page 94 of 112...
The Read Only, Write Only or Read/Write status for each function in Table 9-4 is shown in the Default/Comments column. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288 06/05/13 Page 95 of 112...
Page 96
0 = No action (Read/Write) 1023 Pump Control 1 = Switch OFF 2 = Switch ON 1030 Error/Reset enum (0x5A) (Read/Write) AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288 06/05/13 Page 96 of 112...
Page 97
Target Setpoint 100°C) (Value x 10) DHW Maximum 32°F to 212°F (0°C to (Read Only) 1019 Setpoint 100°C) (Value x 10) AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288 06/05/13 Page 97 of 112...
Page 98
100°C) (Value x 10) BMM #n Actual Modulation 0 – 100% 2n08 (Read Only) Level (n = 0 – 7) AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288 06/05/13 Page 98 of 112...
Page 99
1 – 10 minutes 3006 Pump Over-run Time (Read/Write) 5 min. Table 9-4: BCM Standard Holding Register Address Mapping (Continued) AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288 06/05/13 Page 99 of 112...
Page 100
0x5A: Test mode request messages are executed only in Test mode. Table 9-4: BCM Standard Holding Register Address Mapping (Continued) AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288 06/05/13 Page 100 of 112...
Page 101
Mode [0, 1] bit 4: DL1 [OFF, ON] bit 5: eBUS TX bit 6: eBUS-1 TX bit 7: eBUS Supply [OFF, AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288 06/05/13 Page 101 of 112...
7. Monitor the display to ensure no other Fault Codes appear. 8. Resume normal operation after all faults have been cleared. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288 06/05/13 Page 103 of 112...
BMM (Burner Management Module): These fault codes are shown in Table 10-4. In order to derive the correct error code from that displayed in the E8 Controller display, use Table 10-1 below to determine the working error code. To use the table, identify the displayed number from the first column, identify the affected module from the second column, apply the formula from the third column, and identify the Error Table to reference from the fourth column.
OMM-0084_0D FAULT CODE FAULT DESCRIPTION Communication Fault E8: Address 0 and 1 on BUS. IDs BUS 0 and 1 may not bee used E 90 simultaneously E 91 E8: BUS ID used. The set BUS ID is already in use by another device...
Page 107
Subtract 65280 from Displayed Number = BCM Fault Code in Table 10-3 65280 Table 10-3: BCM Fault Codes CODE DESCRIPTION EFFECT CORRECTION RESET AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288 06/05/13 Page 107 of 112...
Need help?
Do you have a question about the E8 and is the answer not in the manual?
Questions and answers