FUNCTION SETTING

Setting an indoor unit address and installation option

f Set the indoor unit address and installation option with remote controller option.
f
Set the each option separately since you cannot set the ADDRESS setting and indoor unit installation setting option at the same time.
You need to set twice when setting indoor unit address and installation option.
The procedure of option setting
Step 1. Entering mode to set option
1. Remove batteries from the remote controller.
2. Insert batteries and enter the option setting mode while pressing High Temp button and Low Temp button.
3.
Check if you have entered the option setting status.
Step 2. The procedure of option setting
After entering the option setting status, select the option as listed below.
Option setting is available from SEG1 to SEG 24
• SEG1, SEG7, SEG13, SEG19 are not set as page option.
CAUTION
• Set the SEG2~SEG6, SEG8~SEG12 as ON status and SEG14~18, SEG20~24 as OFF status.
SEG1 SEG2 SEG3 SEG4 SEG5 SEG6 SEG7 SEG8 SEG9 SEG10 SEG11 SEG12
0
X
X
SEG13 SEG14 SEG15 SEG16 SEG17 SEG18 SEG19 SEG20 SEG21 SEG22 SEG23 SEG24
2
X
X
NASA PJT_AHU Kit_MXD-K@@@AN Series_EN_03711A(1).indd 19
Entering mode for
option setting
High Temp Button
Low Temp Button
X
X
X
1
X
X
X
X
3
X
Option setting mode
Mode change
High Fan Button
Low Fan Button
On(SEG1~12) Off(SEG13~24)
X
X
X
X
X
X
X
X
19
2013-01-11 오후 3:20:28