Panasonic WH-SDC03E3E5 Service Manual page 99

Air-to-water
Hide thumbs Also See for WH-SDC03E3E5:
Table of Contents

Advertisement

16.5.24 Outdoor High Pressure Switch Abnormal (F27)
Malfunction Decision Conditions:
During compressor stop, and outdoor high pressure switch is remain opened.
Malfunction Caused:
1
Faulty connector connection.
2
Faulty switch.
3
Faulty outdoor unit PCB (main).
Abnormality Judgment:
Continue for 1 minute.
99