OPERATOR MANUAL IMPORTANT INFORMATION, KEEP FOR OPERATOR This manual provides information for: THIS MANUAL MUST BE RETAINED FOR FUTURE REFERENCE. READ, UNDERSTAND AND FOLLOW THE INSTRUCTIONS AND WARNINGS CONTAINED IN THIS MANUAL. NOTIFY CARRIER OF DAMAGE AT ONCE It is the responsibility of the consignee to inspect the container upon receipt of same and to determine the possibility of any damage, including concealed dam- age.
Table of Contents Types of Systems ................page 4 Installation Requirements for Avtec Ventilation Hoods ....page 5 Canopy Hoods ................page 5 UV Electrical .................. page 9 Exhaust Fans & Ducts ..............page 13 Control Panels ................page 14 Fresh Air Supply Fans ..............
Page 3
Retain this manual for future reference. NOTICE: Due to a continuous program of product improvement, Avtec reserves the right to make changes in design and specifications without prior notice. NOTICE: Please read the entire manual carefully before installation. If certain recommended procedures are not followed, warranty claims will be denied.
Surface, plenum and duct collar extinguishing systems may be factory supplied. ULTRAVIOLET (UV) SERIES The EcoArch Energy Efficient Ventilation UVc is a door assembly integrally installed in the exhaust plenum of an EcoArch canopy, consisting of UVc filtration system designed for use in the ventilation control of commercial cooking operations of listed hood systems.
ALL AVTEC VENTILATION SYSTEMS MUST BE INSTALLED IN ACCORDANCE WITH NFPA- canopies. Low side wall ventilators should be installed directly upon a Avtec base or on a VENTILATION HOODS 96, REMOVAL OF SMOKE AND GREASE-LADEN VAPORS FROM COMMERCIAL COOKING rerated wall.
Page 6
Installation Instructions ECOARCH CANOPIES EQUIPPED If your EcoArch hood comes equipped with an UV assembly please refer to the following steps. WITH UV ASSEMBLY General CAUTIONS & Guidelines • Installation of UV Exhaust canopies must be completed by HVAC ventilation system contractors or employees trained and qualified to do ventilation hood and exhaust system installation.
UV light switch will terminate. THE POWER AT (TS-2) IS 115V/1/60. Connect one PLEASE ADHERE TO ALL ELECTRICAL side of the switch to terminal 1 and the other side of the switch to terminal 2. Please NATIONAL, STATE, AND LOCAL CODES. make sure the switch is connected to ground. OM-ECOARCH 9...
9. A duct transition should be provided below exhaust fan inlet. 10. The exhaust duct must be fluid welded to hood collar. 11. Make all necessary electrical connections and check fan for proper rotation. NOTE: Fan will exhaust air running in wrong direction. OM-ECOARCH 13...
Electrical back draft damper is recommended in cold climates. 9. Bolt or screw fan to fan curb. 10. Make all necessary electrical connections and check fan for proper rotation. NOTE: Fan will supply air running in wrong direction. *Dependent on local code requirements. OM-ECOARCH...
Page 15
Installation Instructions FOR CONTROL PANEL (IF PROVIDED) Figure 7 OM-ECOARCH 15...
2. Skirts are to overlap the outside of the hood. Bolts and acorn nuts should be attached per the drawing (stainless bolts and acorn nuts supplied). 3. Skirt flange should be screwed to the wall (screws not provided). Figure 8 OM-ECOARCH...
2. Slide enclosure panel under clips. 3. If enclosure panels are installed on one or more hoods butted end to end, the butting ends of the front enclosure panels should be bolted together. Figure 9 OM-ECOARCH 17...
4. Slip one end of wall panel into seam strip, pull out middle of panel and slip other end of panel into other seam strip. Gently apply pressure over entire wall panel to secure to wall. Wall bands for side walls are provide with 1” return bend, which is to be located behind rear wall panels. OM-ECOARCH...
4. Adjust speed of exhaust fan to obtain proper air velocities and CFM through grease filters. SUPPLY FAN OR 1. Start the supply fan and/or make-up unit only. Do not run the exhaust fan. MAKE-UP AIR UNIT 2. Refer to drawings or UL information label on hood for proper CFM requirements. OM-ECOARCH 19...
6. If all vapors are not totally captured, fine tune the system by adjusting the air volume control damper installed in the supply collar. Slightly reduce the amount of supply air directed under the hood until full capture is obtained. OM-ECOARCH...
UV lamp exterior using a dry towel and a non-detergent cleaning agent such as sanitizing solution or white vinegar. IMPORTANT: Do not allow cleaner to run into lamp fittings or socket enclosures. IMPORTANT: UV System will not work properly without daily cleaning of the UV lamp. OM-ECOARCH 21...
Parts List EcoArch Parts ITEM NO. AVTEC PART NO. DESCRIPTION HD HDL010 4” Chrome Handle AS SEAL395 3/8” Quickseal AS GLB0201 Incandescent Work Light Globe AS FIX0201 Incandescent Work Light Cage AS LGT1220 3’-0” Fluorescent Work Light AS LGT1420 4’-0” Fluorescent Work Light AS LGT1020 2’-0”...
Page 23
Service Log Model No: Purchased From: Serial No: Location: Date Purchased: Date Installed: Purchase Order No: For Service Call: Date Service Performed Performed By OM-ECOARCH 23...