Energy Saver; Front Desk Control - LG PTAC Type Product Data Book

60hz/r410a
Table of Contents

Advertisement

Control Device
• Remote/Local Control
When remote/local switch #1 is on, it allow the unit to operate by the Remote Wall Thermostat.
The unit control by knobs are not available.

• Energy Saver

The energy saver switch #2 is on. This switch is set at cycle fan to provide continuous fan operation in cool or heat
modes. When the switch is off the continuous fan allows continuous circulation of room air and make the more balanced
temperature of the room. When the switch is on, the fan is on or off with the compressor or with the heater.

• Front Desk Control

When the pair wire is connected to the connector FD2 and FD1, the unit can be turned ON or OFF with a switch located at
the Front Desk Control panel. When the front desk switch is ON, the fan operates according to the setting without working
compressor and heater. When the front desk switch is OFF, the unit can operate according to the setting of controls.
Wire # AWG
Maximum Length
#22
600 ft (180 m)
#20
900 ft (270 m)
#18
1500 ft (450 m)
#16
2000 ft (610 m)
Motion Sensor
Motion Sensor
Door Switch
Door Switch
Front Desk Control
Front Desk Control
FD2 FD1 DR2 DR1 MS2 MS1
(Molex Housing Spec 396-06V)
Note : The following figures show wiring schematics for heat pump and straight cool units with
electric heat, respectively.
Wiring Schematic for Remote Heat Pump
47
Wiring Schematic for Straight Cool Unit.
PTAC
6RWU0-03A
Product Data