If, for technical or other reasons, this solution is impossible and there exists a suitable communication channel (cable or other media) between the points, the NRC86 remote controller can be used for driving the capacitor contactors.
Page 5
Novar-NRC KMB systems Detailed description of the Novar power factor controllers can be found on the manufacturers website www.kmbsystems.eu...
Default values are –0.95 / -0.97 / 1.00 / 0.97 / 0.95 , but they can be freely changed. According this setting the PFC keeps preset target PF value that is dynamically controlled by the remote controlled PF serial number from the NRC86 unit ( standard target PF value in parameter 01 has no meaning in this mode).
Page 7
Novar-NRC KMB systems Tab. 2.1 : Novar-1xxx NRC Additional and Affected Parameters name range step default comment target PF for 0.80 L ÷ 0.80 C 0.01 0.98 L in the „RCC“-mode (see par. 53), depending on the metering rate 2 parameter setting and metering rate 1 „EX.XX“...
( i.e. a medium with no transmission delay) is used (it depends on preset communication rate and remote control mode). If usual metallic cable is used maximum distance between the PFC and the NRC86 unit is up to 1 km, but it can be nearly unlimited for suitable wireless media.
If the metering rate 2 control is enabled and any of the RCC-modes is set simultaneously, the target PF is remote controlled by external NRC86 unit only when the metering rate 2 (tariff 2) just active. In such case, the actual value of remote controlled PF with preceding „E“ character is displayed in parameter 07 ( in the same way as in the parameter 01 when the metering rate 2 control disabled).
When temporary interruption of the connection between the PFC and the NRC86 unit/units appears, the situation will look as follows : 1. Approximately after 20 seconds of communication link fault the PFC disconnects all of outputs step by step and it will stay in standby mode until the connection is restored.
GSM/GPRS modems, LAN etc., it is necessary to set this parameter value to maximum wait time for response from the NRC86 i seconds ( in range 1 – 2 – 3 – 5 – 8 ). If the remote control mode is switched off the parameter 52 has its usual meaning – the type of communication protocol.
Page 12
NRC86 unit, all of others must be set as „slaves“, that means to passive RCC-mode marked as RCCP. As soon as the mode is set, the master PFC starts to send commands to the NRC86 unit(s). The unit (with address of 200 if more units connected) receives them, processes them and sends confirmation back to the master PFC.
In the RCC-mode , co called serial number of remote controlled PF is periodically transferred from the (first) NRC86 unit to the PFC (or multiple PFCs). Its range is 1 ÷ 5 and actual value is displayed in parameter 81with identification string „ECn“; for example, if its value is 2, the...
3. NRC 86 Remote Controller The unit is designed for power factor compensation systems either with remote controlled PF or with remote controlled outputs. The unit operates in combination with special version of Novar power factor controller – Novar1xxx NRC.
3.2.1 Remote Controlled Power Factor (Cosinus) Mode – the „RCC“ Mode Up to five pulse signals can be connected to the NRC86 unit. A pulse of correct duration on one of inputs 1÷5 is evaluated as target PF serial number request. The unit saves the number into its memory and confirms by switching of appropriate output on ( this signal is transmitted back to the supervising system for checking ).
KMB(P0) / Modbus-RTU(P1) KMB(P0) remote control mode must be set to P0 (KMB) protocol set by the NRC86 unit ; indicates type of alarm : 20 alarm status -- / E / C E … external alarm (= indicates cooperating Novar1xxx NRC PFC alarm active state) C …...
O1. 3.3.4 Parameter 06 – Daisy-Chain Communication Mode („Cascade“) If more than one NRC86 units connected to a PFC all of the units but the last one must be set to the daisy-chain communication mode (i.e. set to 1 1 1 1 This mode must be switched off at the last unit in the cascade , i.e.
I I I I … 1 ( active ) 3.4 Installation The NRC86 unit is designed for mounting on a DIN-35 bar. Maximum cross section area of connection wires is 2.5 square millimetres. Examples of unit wiring are shown below.
KMB systems 3.4.3 Logic Inputs The NRC86 unit can have up to 8 galvanically isolated logic inputs (depending on unit model). The inputs are passive – a voltage of appropriate level ( specified in technical parameters, see below ) must be applied. For direct voltage inputs the applied voltage polarity is free. The input voltages must be connected to terminals 29 ÷...
For remote controlled power factor the NRC86-85 24 VDC remote controller is needed. If remote controlled outputs using additional NRC86 units in cascade necessary too it is better to use the NRC86-07 230 VAC models with 7 outputs each for this task.
I1÷ I5 inputs of the NRC86 and check response of all connected PFCs. 4.2 Remote Controlled Outputs Compensation Systems For these applications, the NRC86-07 230 VAC remote controller with 7 outputs is optimal. Up to 7 of such NRC86 units depending of number of compensation system outputs (contactors) and required spatial spread can be used.
Page 22
(No. 51) to any improper value – the PFC must during approx. 20 seconds start indicating the remote control failure alarm and switch all of its outputs off step-by-step. The NRC86 unit(s) must start to indicate the communication link failure alarm during approx. 15 seconds and after 30 seconds to disconnect all of outputs at once.
KMB systems 7. MAINTENANCE, TROUBLESHOOTING NRC86 remote controller does not require any maintenance. For reliable operation you only have to comply with the operating conditions specified and prevent mechanical damage to the instrument. In the event of the product’s breakdown, you have to return it to the supplier at their address.
Need help?
Do you have a question about the NRC86 and is the answer not in the manual?
Questions and answers