EUTECTIC EC-10
OIL-FIRED WATER BOILERS/NO. 2 OIL

INSTALLATION AND OPERATING INSTRUCTIONS

SAFETY WARNING:
KEEP BOILER AREA CLEAR AND FREE FROM COM-
BUSTIBLE MATERIALS, GASOLINE AND OTHER FLAM-
MABLE VAPORS AND LIQUIDS. FAILURE TO ADHERE TO
ABOVE SAFETY WARNING, MAY RESULT IN PERSONAL
INJURY OR DEATH AND PROPERTY DAMAGE.
CONTENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .PAGE
Ratings and Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Installation Requirements:
Boiler Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 & 4
Chimney Requirements . . . . . . . . . . . . . . . . . . . . . . . . . .3
Blocked Vent Safety Switch . . . . . . . . . . . . . . . . . . . . . . .4
Baffle Placement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Air Supply and Venting . . . . . . . . . . . . . . . . . . . . . . . . .3-7
Controls and Accessories . . . . . . . . . . . . . . . . . . . . . . . . .7
Piping for Water Units . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Installing Burner . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
Oil Supply Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
Wiring the Boiler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
Vent Piping and Draft Regulator . . . . . . . . . . . . . . . . . . . .8
Operating Instructions:
Precautions Before Starting . . . . . . . . . . . . . . . . . . . . . . .8
Start-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
Cleaning and Filling New Water Boiler . . . . . . . . . . . . . . .8
Extended Shutdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
Freezing Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
Oil Burner . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
General Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . .10
Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11-16
Burner Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17-21
SERVICE COMPANY
Name ______________________________
Address_____________________________
___________________________________
Telephone ___________________________
Model #_____________________________
Serial # _____________________________
IMPORTANT: The installation of this equipment must con-
form to the requirements of the authority having jurisdiction
or, in the absence of such requirements, to the Installation of
Oil Burning Equipment, ANSI/NFPA 31, latest edition, and to
the National Electrical Code ANSI/NFPA 70, latest edition.
The installation must also conform to the additional require-
ments in this Slant/Fin Instruction Manual. Where there is any
difference, the more stringent requirement shall govern.
In addition, where required by the authority having jurisdiction,
the installation must conform to American Society of Mechanical
Engineers Safety Code for Controls and Safety Devices for
Automatically Fired Boilers, No. CSD-1, latest edition.
THIS MANUAL MUST BE LEFT WITH OWNER AND
SHOULD BE HUNG ON OR ADJACENT TO THE BOILER
FOR REFERENCE.
IMPORTANT: This boiler must be installed, serviced and
repaired by a trained, experienced, service technician,
licensed for the installation and servicing of oil burning hot
water heating system equipment or otherwise qualified by the
authorities having jurisdiction over the installation.
Printed in U.S.A. 1116
Part No. 470900000
Publication No. EC-10-40 Rev.E

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the EC-10 and is the answer not in the manual?

Questions and answers

Summary of Contents for EUTECTIC EC-10

  • Page 1: Table Of Contents

    Telephone ___________________________ water heating system equipment or otherwise qualified by the authorities having jurisdiction over the installation. Model #_____________________________ Serial # _____________________________ Printed in U.S.A. 1116 Publication No. EC-10-40 Rev.E Part No. 470900000...
  • Page 2: Ratings And Dimensions

    EUTECTIC EC-10 Figure 1: Dimensions Panel Mounted Panel Mounted Tridicator Temperature Tridicator Pressure Sensor Well Sensor Well Supply Pipe Mounted Tridicator 355mm 195mm Relief valve 3/4’’ 1-1/4 threaded supply Flue outlet øD 1-1/4 threaded return pipe 60mm 156mm Drain outlet...
  • Page 3: Boiler Location

    * Includes burner, circulator and controls and chimney. Horizontal sections of flue pipe must be B. The EC-10 Boiler has full wet base sections which sur- pitched upward to the chimney at least 1/4" per foot round fire-box for maximum heat absorption of burning (20mm/m).
  • Page 4: Blocked Vent Safety Switch

    A BLOCKED VENT SAFETY SWITCH MUST BE INSTALLED Sufficient space shall be left clear around the boiler. All EC-10 Series boilers must be installed with a Blocked Do not stack items on or box in the appliance within Vent Safety Switch. The Blocked Vent Safety Switch will the required clearances to combustibles.
  • Page 5 EUTECTIC EC-10 unreliable, CO and overfire draft* will change unpredictably. the chimney through the vent regulator into the living space. DO NOT operate this boiler and a solid fuel burning appliance DO NOT vent this boiler to the same chimney flue used by a at the same time, unless the solid fuel burner is provided with fireplace or coal or wood burning furnace or boiler.
  • Page 6 EUTECTIC EC-10 CHIMNEY CHIMNEY 12 IN MAX 305 mm 12 IN MAX 305 mm 6 IN MAX 6 IN MAX 152 mm 152 mm Figure 3a. Figure 3b. Appliances located in confined spaces. Air from Appliances located in confined spaces. Air from out- inside the building.
  • Page 7: Controls And Accessories

    EUTECTIC EC-10 The opening size recommendation just given is for guidance If system pressure needs further control, add another only. It is the installer’s responsibility to provide air for combus- tank in parallel with the original tank or install a large tion and ventilation to all appliances, under all operating con- capacity tank.
  • Page 8: Oil Supply Piping

    EUTECTIC EC-10 A. Boiler and system are full of water. All air is vented from OIL SUPPLY PIPING system. See below. Install the oil tank or tanks and piping from tank to burner. B. All wiring is completed. See page 11 through 15.
  • Page 9: Care And Maintenance

    EUTECTIC EC-10 II. Filling and venting the water boiler after cleaning 1. Remove the flue pipe from the boiler flue collar and A. Refill the system with fresh water. clean thoroughly. B. Bring water temperature to at least 180° F (82˚C) promptly.
  • Page 10: Iii. Oil Burner

    EUTECTIC EC-10 Replacements are available from dealer or III. OIL BURNER hardware stores. All service to the oil burner, oil filter, oil strainer, etc., 7.Protect all of the fireside surfaces by swabbing with neu- should be performed by a professionally trained service tral mineral oil.
  • Page 11: Wiring Diagrams

    EUTECTIC EC-10...
  • Page 12 EUTECTIC EC-10...
  • Page 13 EUTECTIC EC-10...
  • Page 14 EUTECTIC EC-10 Honeywell L 7248C –1030 Aquastat Control Multiple Zoned (Circulator or Zone Valve) Single Zone, Heat Wise or Riello Burner...
  • Page 15 EUTECTIC EC-10 Honeywell L7248L, See “Adjusting Settings” & “error Codes” for Beckett 7600A and L7248L on page 16 HydroLevel 3250 Controls...
  • Page 16 EUTECTIC EC-10 FOR  L7248L °F or °C. Pressing the I button again (on L7224 models) will display the ADJUSTING SETTINGS Low Limit (LL) followed by a three-digit number and the corresponding To discourage unauthorized changing of Aquastat settings, a procedure degree designator.
  • Page 17 EUTECTIC EC-10 AQUASMART QUICK REFERENCE GUIDE To ensure smooth appliance operation, the AquaSmart requires a NOTE: Boiler manufacturer’s temperature requirements separation between the High and Low limits no less than the greater supersede this recommendation. differential plus 5°F. 3. Press the “ENTER (RESET)” key. Confirm the setting by For example: If the High Limit is set to 180°F, the High Diff to 20°F, and...
  • Page 18: Burner Data

    EUTECTIC EC-10 BURNER DATA—CARLIN BURNERS FOR PACKAGED BOILERS ONLY Nozzles Firing Head Approx. Shutter Boiler Burner Blast Oil Pump Rate Adjusting Air Band Non- Size Angle & Model Model Tube (PSIG) MFR. Plate † Setting Adjustable Type 0.65 45˚A Delavan .60/.65...
  • Page 19 EUTECTIC EC-10 BURNER DATA—BECKETT BURNERS FOR PACKAGED BOILERS ONLY Nozzles Approx. Boiler Burner Blast Oil Pump Approx. Approx. Firing Rate Model Model Tube Size Head Air Band Angle & Shutter MFR. Setting † Setting Type Setting † L/hr. L/hr. (PSIG) kPa.
  • Page 20 EUTECTIC EC-10 Check/Adjust “Z” Dimension – L1 & L2 Heads Figure 9. Head Adjustment L1 & L2 Beckett Head 1. See figure above. The important “Z” dimension is the distance from the leading edge of the head to the end of the air tube.
  • Page 21 EUTECTIC EC-10 BURNER DATA - RIELLO BURNERS FOR PACKAGED BOILERS ONLY (RIELLO R-40 SERIES W/SHORT TUBE) Nozzles Boiler Burner Blast Oil Pump Approx. Approx. Firing Rate Model Model Tube (PSIG) Size Head Angle & MFR. Setting † Setting † Type...
  • Page 22 EUTECTIC EC-10 BURNER DATA - RIELLO (continued) 1. Regulation of the combustion air flow is made by adjustment of the manual AIR ADJUSTMENT PLATE (4) after loosening the FIXING SCREWS (3&5). The initial setting of the air REGULATION OF THE TURBULATOR AND AIR SHUTTER FOR PROPER COMBUSTION adjustment plate should be made according to figure 13.
  • Page 23 Notes:...
  • Page 24 ©Slant/Fin Corp. 2015. SLANT/FIN CORPORATION, Greenvale, N.Y. 11548 • Phone: (516) 484-2600 Canada: Slant/Fin Mississauga, Ontario FAX: (516) 484-5921 • LTD/LTEE, www.slantfin.com...

Table of Contents