The dome sounder can be programmed to the system by the following procedure: To log the device onto the 5000 FirePoint, take the device to the front of the panel. Insert the key into the Panels Control Key switch, located on the bottom right of the Panel.
Page 4
EMS 5000 FIREPOINT | System Mode >Engineers Config < Press the “” key until the screen displays: | Printer Options Yes= Select Time Enter Your PIN Press the “YES” key and the screen will now For Access> Then Press YES...
EMS 5000 FIREPOINT | Slot is :IN USE | >Logon is DISABLED< Press the “YES” key twice and the screen will now | /\/\/\/\/\/\/\/\/\/\ | display: 01 FAULT TOT 02 Default Device 125 Press the “NO” key three times and the screen...
EMS 5000 FIREPOINT Sounder switches shown below in Figure 4. Sounder Volume Switches (Where the Switch in an Upwards orientation = the On Position) Figure 4 Sounder Configuration Label, shown below in figure 5. Sounder Dome Configuration Sticker Figure 5 Note: The Sensitivity switches are not used on this model.
EMS 5000 FIREPOINT PLEASE NOTE: Tamper Knockout requires removal in order to fit the Anti Tamper Screw 4. Dome Sounder Installation When installing, ensure all dome sounders are sited in accordance with survey and design details. The mounting plate is shown in Figure 6. The plate can be removed by turning the mounting plate in an anticlockwise rotation, whilst holding the sounder/dome section.