SYSTEM CONTROL - ACVMAX Prestige 42 - 50 - 75 - 100 - 120 Solo 24 - 32 Solo 24 - 32 Excellence Excellence LG For boilers produced in 2015 660Y2800 • C...
TABLE OF CONTENTS PRESET CONFIGURATION 7 - SOLO (2 PUMPS) ............40 RECOMMENDATIONS .....................3 High and Low temperature heating circuits, with room control on Heating Circuit 1 (CH1) and possible Important instructions - read before proceeding ......................3 second room control, possibly with optional outdoor temperature sensor and room thermostat..40 USER'S GUIDE ........................4 High and Low temperature heating circuits, with room control on Heating Circuit 1 (CH1) and possible How to use this manual ................................4...
RECOMMENDATIONS IMPORTANT INSTRUCTIONS - READ BEFORE PROCEEDING NOTE This manual contains important information with respect to the installation and set-up of the boiler. Essential recommendations for safety This manual must be provided to the installer, who will keep it in a safe place. •...
USER'S GUIDE HOW TO USE THIS MANUAL BOILER EASY SETUP This manual is for the exclusive use of ACV-approved installers. The main parameters of the Prestige boilers can be set up using the EZ (easy) setup function of the controller. The EZ setup function allows the user/installer to quickly setup the appliance for immediate The first section of the manual contains a description of the ACVMax controller and of the keys, screens operation according to the system configuration.
APPLIANCE DESCRIPTION AND OPERATION ACVMAX OPERATING INFORMATION Main Icons of ACVMax display Central Heating - indicates information related to the CH circuit. The ACVMax system control is designed to be flexible yet easy to use. It monitors and controls the DHW - indicates information related to the Domestic Hot Water circuit.
APPLIANCE DESCRIPTION AND OPERATION INSTALLER MENU STRUCTURE INSTALLER MENU DESCRIPTION The installer Menu contains the following icons : 84°C CH & DHW Settings – Allows the installer to adjust the boilers central/space heating and domestic hot water settings for the application. Refer to "CH & DHW Settings / Heating Settings" 61°C on page 7.
Page 7
APPLIANCE DESCRIPTION AND OPERATION CH & DHW Settings / Heating Settings Heating Settings CH Settings The Heating Settings menu contains settings related to central heating operation. Each Heating Operation Enabled Demand Thermostat & Setpoint line contains a CH Setting followed by its current value. Six CH Settings are displayed on Abs.
Page 8
APPLIANCE DESCRIPTION AND OPERATION CH & DHW Settings / Heating settings (Cont'd) Demand Type Demand Type Thermostat & Outdoor Curve – A central heating call from a dry contact switch will enable the Prestige Thermostat & Outd. Curve Thermostat & Outd. Curve and the setpoint will vary with the outdoor temperature for central heating calls.
Page 9
APPLIANCE DESCRIPTION AND OPERATION CH & DHW Settings / Heating Settings (Cont'd) 0 - 10V Modulation Signal - This option allows the Prestige firing rate to be controlled by an external control system. Based on the control input voltage, the appliance will start to operate for heat demand. The CH temperature is limited by the Absolute maximum temperature (87°C).
Page 10
APPLIANCE DESCRIPTION AND OPERATION CH & DHW Settings / Heating settings (Cont’d) Absolute Max CH Setpoint limits the setpoint during a central heating call. This setting can be used to prevent a user from adjusting the central heating setpoint or outdoor curve above Abs.
Page 11
APPLIANCE DESCRIPTION AND OPERATION CH & DHW Settings / Heating settings (Cont’d) Outdoor Curve Heating Settings Heating Settings Outdoor Curve Coldest Day is the coldest outdoor design temperature of the heating sys- Coldest Day tem when an Outdoor Curve option is chosen in Demand Type. This setting is not applicable Heating Operation Enabled Heating Operation...
Page 12
APPLIANCE DESCRIPTION AND OPERATION CH & DHW Settings / Heating Settings (Cont’d) CH2 Min. Heating Settings Heating Settings CH2 Minimum Setpoint is the minimum setpoint for a CH2 heating call when an Out- Setpoint door Curve option is chosen in Demand Type. This setting is not applicable when a Set- CH1 Max.
Page 13
APPLIANCE DESCRIPTION AND OPERATION CH & DHW Settings / Heating Settings (Cont’d) CH Post Pump Time sets how long the central heating circulators will continue to op- erate at the completion of a heating call. Refer to “Pumps” on page 32 to know which CH Post Heating Settings Heating Settings...
Page 14
APPLIANCE DESCRIPTION AND OPERATION CH & DHW Settings / Heating Settings (Cont’d) Parallel Shift allows the CH setpoint to be externally adjusted when a Constant option is chosen in Demand Type. When a Constant option is chosen in Demand Type, continuous CH1 and CH2 heating calls are generated.
Page 15
APPLIANCE DESCRIPTION AND OPERATION CH & DHW Settings / DHW settings DHW Settings DHW Settings The DHW Settings menu contains settings related to domestic hot water operation. DHW Operation Enabled Demand Thermostat Each line contains a DHW Setting followed by its current value. Six DHW Settings are DHW Boiler Setpoint 75°C displayed on the screen at one time.
Page 16
APPLIANCE DESCRIPTION AND OPERATION CH & DHW Settings / DHW settings (Cont’d) DHW Settings DHW Settings DHW Boiler Setpoint is the fixed boiler setpoint temperature during a domestic hot wa- Boiler Setpoint DHW Operation Enabled DHW Operation Enabled 75°C ter call when the Thermostat option is chosen in Demand Type. Demand Thermostat Demand...
Page 17
APPLIANCE DESCRIPTION AND OPERATION CH & DHW Settings / DHW settings (Cont’d) DHW Storage Adder is used to compute the boiler setpoint when the Sensor option is DHW Settings DHW Settings DHW Storage Adder chosen in Demand Type. The boiler setpoint will be DHW Storage Setpoint + DHW Storage DHW Operation Enabled DHW Operation...
Page 18
APPLIANCE DESCRIPTION AND OPERATION CH & DHW Settings / DHW settings (Cont’d) DHW Priority allows the domestic hot water priority function to be enabled and disabled. Press the UP or DOWN buttons to select Enabled or Disabled then press the OK button to store the setting.
Page 19
APPLIANCE DESCRIPTION AND OPERATION CH & DHW Settings / DHW settings (Cont’d) The Antilegionella Function ensures that an Indirect Water Heater is heated at least once per week to prevent the growth of Legionella bacteria. Press the UP or DOWN buttons to select Enabled or Disabled then press the OK button to store the setting.
Page 20
APPLIANCE DESCRIPTION AND OPERATION CH & DHW Settings / Boiler Settings The Boiler Settings menu contains settings related to boiler operation. Each line contains Boiler Settings Prestige Model Boiler Settings a boiler setting followed by its current value. Four boiler settings are available. Press the UP or DOWN buttons to scroll through the settings, then on OK to validate your Prestige Model Solo (2 pumps)
Page 21
APPLIANCE DESCRIPTION AND OPERATION CH & DHW Settings / Boiler Settings (cont’d) Preset Pump Con g Con g 1 Con g 2 Con g 3 Con g 4 Con g 5 Con g 6 Pump Settings Pump Settings In the Preset Pump Config. (preferred selection) you can choose from a number of preset pump configurations Current Pump Con g Modi ed Current Pump Con g...
Page 22
APPLIANCE DESCRIPTION AND OPERATION CH & DHW Settings / Boiler Settings (cont’d) Each relay function has several options. Activation will happen when one of the following options has been chosen: Flexible Pump Con g Flex. Relay 1 (CH) CH1, CH2, DHW, MIX OPEN, MIX CLOSE, ERROR, FLAME. CH1 / CV1 Flex.
Page 23
APPLIANCE DESCRIPTION AND OPERATION CH & DHW Settings / Boiler Settings (cont’d) Flex. Relay 1 (CH) Flex. Relay 1 (CH) CH1 / CV1 CH1 / CV1 When selecting Mix Close, the Mixing valve close input is activated. Provided there is a mixing valve in the CH2 / CV2 CH2 / CV2 hydraulic circuit, runtime is assumed to be 120 sec.
Page 24
APPLIANCE DESCRIPTION AND OPERATION CH & DHW Settings / Boiler Settings (cont’d) There are three possible selections to activate the Error Relay (alarm) contact: Flexible Pump Con g Flexible Pump Con g Error Relay • On Lockout, Blocking and Warning: the error relay is activated at a non-volatile lock- On Lockout, Blocking and Warning out (e.g.
Page 25
APPLIANCE DESCRIPTION AND OPERATION Manual Operation Manual Operation Manual Operation FAN - Press the OK button while the FAN icon is highlighted to manually fire the burner and power the CH (1) circulator. Released Press the LEFT and RIGHT buttons to adjust the firing rate from 0% (Low Fire) to 100% (High Fire). Hold down the LEFT or RIGHT buttons to rapidly increase or decrease the firing rate.
CONFIGURATION OF REGULAR SYSTEMS ELECTRICAL CHARACTERISTICS PRESTIGE 42 - 50 - 75 SOLO 230 V power supply plug Ground PRESTIGE SOLO ON/OFF master switch Gas valve rectified Main Characteristics Burner power supply Rated voltage Terminal block for optional items Rated frequency 230 VAC OUTPUT ! : Alarm (ERR terminal) Electrical consumption...
CONFIGURATION OF REGULAR SYSTEMS ELECTRICAL CHARACTERISTICS PRESTIGE 100-120 SOLO 230 V power supply plug Ground ON/OFF master switch PRESTIGE SOLO Gas valve Main Characteristics Burner power supply Terminal block for optional items Rated voltage Rated frequency : Alarm (ERR terminal) Electrical consumption 230 VAC OUTPUT ! Class...
CONFIGURATION OF REGULAR SYSTEMS ELECTRICAL CHARACTERISTICS PRESTIGE 24-32 SOLO/EXCELLENCE 230 V power supply plug Ground PRESTIGE ON/OFF master switch Solo Excellence Gas valve rectified Burner power supply Main Characteristics Terminal block for optional items Rated voltage : Alarm (ERR) 230 VAC OUTPUT ! Rated frequency Max.
Page 31
CONFIGURATION OF REGULAR SYSTEMS Blue Black Brown PUMP PWM Grey NTC 5 NTC 2 NTC 1 Orange 3 2 1 3 2 1 STEPPER Violet X100 X100 White Y/Gr. Yellow/Green A B C D 1 2 3 4 5 4 3 2 1 1 2 3 1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6...
CONFIGURATION OF REGULAR SYSTEMS - PRESTIGE SOLO (2 PUMPS) GENERAL ACCESSING THE PRESET CONFIGURATION PAGE FOR SOLO (2 PUMPS) This section contains information on the electrical connections, hydraulic connections and ACVMax controller set-up for Prestige 42-50-75-100-120 Solo, that are required to operate the system To access the preset configuration page, follow the selections shown on the screens below (Installer menu) configuration you have selected.
PRESET CONFIGURATION 1 - SOLO (2 PUMPS) High temperature heating circuit, possibly with optional outdoor temperature High temperature heating circuit, circulator pumps on return lines, possibly with optional outdoor temperature sensor and room thermostat, and with sensor and room thermostat, without DHW circuit. DHW circuit.
PRESET CONFIGURATION 1 - SOLO (2 PUMPS) High temperature heating circuit, with additional load pump, possibly with Refer to "Accessing the preset configuration page for Solo (2 pumps)" on page 32, to know optional outdoor temperature sensor and room thermostat, and with DHW how to get to the relevant page of the ACVMax controller.
PRESET CONFIGURATION 1 - SOLO (2 PUMPS) High temperature heating circuits, with additional load pump, possibly with High temperature heating circuits, with additional load pump, possibly with optional outdoor temperature sensor and room thermostats, and with DHW optional outdoor temperature sensor and room thermostats, and with DHW circuit.
PRESET CONFIGURATION 4 - SOLO (2 PUMPS) NTC 5 NTC 2 NTC 1 High temperature heating circuits, with additional load pump, possibly with Electrical board terminals Terminal name --> Connected to Y/Gr optional outdoor temperature sensor and room thermostats, and with DHW Y/Gr X100 .....
NTC 5 NTC 2 NTC 1 PRESET CONFIGURATION 4 - SOLO (2 PUMPS) High temperature heating circuits, with additional load pump, possibly with X100 Electrical board terminals Terminal name --> Connected to Y/Gr optional outdoor temperature sensor and room thermostats, and with DHW Y/Gr 1 2 3 4 5 3 2 1...
PRESET CONFIGURATION 7 - SOLO (2 PUMPS) NTC 5 NTC 2 NTC 1 High and Low temperature heating circuits, with room control on Heating Circuit Electrical board terminals Terminal name --> Connected to X100 Y/Gr 1 (CH1) and possible second room control, possibly with optional outdoor Y/Gr 1 2 3 4 5 3 2 1...
PRESET CONFIGURATION 9 - SOLO (2 PUMPS) High and low temperature heating circuits, possibly with optional outdoor Pump power is limited in this system configuration, as both pumps (CH1 and CH1Low) need to be connected in parallel. Additionally, a second relay can be used. temperature sensor and room thermostat, and with DHW circuit.
PRESET CONFIGURATION 12 - SOLO (2 PUMPS) NTC 5 NTC 2 NTC 1 High and Low temperature heating circuit, possibly with optional outdoor Electrical board terminals Terminal name --> Connected to X100 temperature sensor and room thermostat, and with DHW circuit. Y/Gr Y/Gr 1 2 3 4 5...
Page 44
CONFIGURATION OF CASCADE SYSTEMS - SOLO (2 PUMPS) Cascade Menu / Cascade Information Cascade Information provides real time operating information of the Cascade System. Each Cascade Info. Cascade Info. line contains an information item followed by its current value. Cascade Role Master Cascade Role - Displays the current role of the Prestige in the Cascade System.
Page 45
CONFIGURATION OF CASCADE SYSTEMS - SOLO (2 PUMPS) Cascade Menu / Cascade Settings (also refer to “Cascade system connection (4-boiler Cascade)” on page 50) Cascade Settings The Cascade Settings menu contains settings related to cascade operation. Each line contains a Cascade Setting followed by its current value. Six Cascade Settings are displayed on the screen at one time.
CASCADE MENU DESCRIPTION AND OPERATION - SOLO (2 PUMPS) Cascade Menu / Cascade Settings (Cont’d) Maximum Firing Rate is the maximum capacity of a single boiler in the Cascade System. Cascade Setting Cascade Setting Maximum Press the LEFT or RIGHT buttons to adjust the Maximum Firing Rate then press the OK button Firing Rate Stage Delay 60 sec...
Page 47
CASCADE MENU DESCRIPTION AND OPERATION - SOLO (2 PUMPS) Cascade Menu / Cascade Settings (Cont’d) CH Proportional Gain allows the cascade response to be adjusted for a central heating call. CH Proportional Gain has the greatest influence when the system temperature is far away from the setpoint.
Page 48
CASCADE MENU DESCRIPTION AND OPERATION - SOLO (2 PUMPS) Cascade / Cascade Settings (Cont’d) DHW Proportional Gain allows the cascade response to be adjusted for a domestic hot water call. DHW Proportional Gain has the greatest influence when the system temperature is far away from the setpoint.
Page 49
CASCADE MENU DESCRIPTION AND OPERATION - SOLO (2 PUMPS) Cascade / Cascade Autodetection The Cascade System must be configured after wiring is completed and any required adjustments are made in Cascade Settings. Refer to "Cascade system connection (4-boiler Cascade)" on page 50 before using this function. Cascade Autodetect.
CONFIGURATION OF CASCADE SYSTEMS - SOLO (2 PUMPS) CASCADE SYSTEM CONNECTION (4-BOILER CASCADE) Set-up conditions • Gas conversion done as required • Boilers switched off using the ON/OFF master switch • External power supply closed • Gas supply closed NTC 5 NTC 2 NTC 1 •...
CONFIGURATION OF CASCADE SYSTEMS - SOLO (2 PUMPS) CASCADE START-UP PROCESS ACCESSING THE CASCADE AUTODETECTION PAGE Set-up conditions • Cascade electrical connection done (refer to “Cascade system connection (4-boiler Cascade)” on page 50). 84°C • Condensate trap full of water •...
PRESET CONFIGURATION 2 (CASCADE) - SOLO (2 PUMPS) 3-boiler cascade configuration, high temperature, with DHW circuit General remarks • Refer to "Accessing the preset configuration page for Solo (2 pumps)" on page 32, to know how to get to the relevant page of the ACVMax controller. •...
Page 53
PRESET CONFIGURATION 2 (CASCADE) - SOLO (2 PUMPS) Master Slave Electrical board terminals Terminal name --> Connected to Electrical board terminals Terminal name --> Connected to Y/Gr Y/Gr 6 7 8 9 10 1 2 3 4 5 6 ..... ERR -->...
PRESET CONFIGURATION 2 (CASCADE) - SOLO (2 PUMPS) 3-boiler cascade configuration, high temperature, with DHW circuit General remarks • Refer to "Accessing the preset configuration page for Solo (2 pumps)" on page 32, to know how to get to the relevant page of the ACVMax controller. •...
PRESET CONFIGURATION 5 (CASCADE) - SOLO (2 PUMPS) 3-boiler cascade configuration, with two high temperature heating circuits and DHW circuit General remarks • Refer to "Accessing the preset configuration page for Solo (2 pumps)" on page 32, to know how to get to the relevant page of the ACVMax controller. •...
CONFIGURATION OF REGULAR SYSTEMS - PRESTIGE SOLO/EXCELLENCE (3-WAY VALVE) GENERAL PUMPS This section contains information on the electrical connections, hydraulic connections and ACVMax The pump configurator system is based on the demands of the hydraulic system that you design. In the controller set-up for Prestige 24-32 Solo/Excellence, that are required to operate the system table below, you will find the 4 configurations that have been preset in the ACVMax controller for the configuration you have selected.
PRESET CONFIGURATION 1 - PRESTIGE SOLO/EXCELLENCE (3-WAY VALVE) ACCESSING THE PRESET CONFIGURATION PAGE FOR THE SOLO/EXCEL. Two heating circuits, with two room thermostats and optional outdoor sensor, (3-WAY VALVE) and with DHW circuit. To access the preset configuration page, follow the selections shown on the screens below (Installer menu) CH &...
ACVMAX PARAMETERS FOR THE SPECIALIST ACVMAX PARAMETERS FOR THE SPECIALIST LIST OF STATUS LINE MESSAGES Status Line Message Description Standby Indicates that the Prestige is ready to respond when a demand is received. CH Demand A central heating call has been received. DHW Demand A domestic hot water call has been received.
ACVMAX PARAMETERS FOR THE SPECIALIST LIST OF INFORMATION ITEMS Information Items Description Boiler Status Displays the current operating state of the Prestige. This is the same as the status line on the home screen. Heating Call Displays if a central heating call is present. DHW Call Displays if a domestic hot water call is present Boiler Firing Rate...
BLOCKAGE AND ERROR CODES BLOCKAGE AND ERROR CODES Codes Description of the fault Solution for the fault 1. Check gas supply to boiler. 2. Check Ignition cable connection in control box. E 01 Failed ignition: The burner failed to light after 5 ignition attempts. 3.
Page 66
BLOCKAGE AND ERROR CODES Codes Description of the fault Solution for the fault 1. Check supply temperature sensor and wiring harness for a short circuit. Supply Sensor Shorted: A short circuit has been detected in the boiler supply tem- 2. If necessary replace the sensor, or the wire harness. E 30 perature sensor circuit 3.
Page 67
BLOCKAGE AND ERROR CODES Codes Description of the fault Solution for the fault 1. Check Mix circuit temp. sensor and wiring harness for an open circuit. 2. If necessary replace the sensor, or the wire harness. E 79 Mix-circuit sensor Open 3.