Summary of Contents for PR 5725

  • Page 1 5 7 2 5 P r o g r a m m a b l e f r e q u e n c y i n d i c a t o r N o . 5 7 2 5 V 1 0 0 - U K F r o m s e r .
  • Page 2 PR electronics A/S tilbyder et bredt program af analoge og digitale signalbehandlingsmoduler til industriel automation. Programmet består af Isolatorer, Displays, Ex-barrierer, Temperaturtransmittere, Universaltransmittere mfl. Vi har modulerne, du kan stole på i selv barske miljøer med elektrisk støj, vibrationer og temperaturudsving, og alle produkter opfylder de strengeste internationale standarder.
  • Page 3: Table Of Contents

    Technical characteristics ............ Mounting / installation ............Applications ................ 10 Electrical specifications ............11 Order: 5725 ................ 11 Sensor error indication, inside and outside range ..... 15 Connections ............... 16 Block diagram ..............17 Routing diagram for 5725A ..........19 Routing diagram for 5725D ..........
  • Page 4: Warning

    The following operations should only be carried out on a disconnected device and under ESD safe conditions: VoLTAGE Troubleshooting the device. Repair of the device must be done by PR electronics A/S only. SymBoL IDENTIFIcATIoN Triangle with an exclamation mark: Warning / demand. Potentially lethal situations.
  • Page 5: Safety Instructions

    Should there be any doubt as to the correct handling of the device, please contact your local distributor or, alternatively, PR electronics A/S www.prelectronics.com Mounting and connection of the device should comply with national legislation for mounting of electric materials, i.e. wire cross section, protective fuse, and location.
  • Page 6 LIABILITy To the extent the instructions in this manual are not strictly observed, the custom er cannot advance a demand against PR electronics A/S that would otherwise exist according to the concluded sales agreement. 5725V 1 01 - I N...
  • Page 7: Ec Declaration Of Conformity

    Ec DEcLARATIoN oF coNFoRmITy As manufacturer PR electronics A/S Lerbakken 10 DK-8410 Rønde hereby declares that the following product: Type: 5725 Name: LED frequency / pulse converter is in conformity with the following directives and standards: The EMC Directive 2004/108/EC and later amendments...
  • Page 8: Front And Back Layout

    FRoNT AND BAcK LAyoUT Picture 1: Front of 5725. Picture 2: Back of 5725. 5725V 1 01 - I N...
  • Page 9: Application

    • 5725 is a digital indicator for readout of frequency signals and pulse signals. • Typical applications are indication and conversion of process speed measurements and flow rate. • The indicator can also be used for measuring the passing time on e.g. a conveyor line, as the 5725 can handle period time measurements. • Process control is possible as the type 5725D contains 2 pairs of potential- free change-over relays and an analogue output. • The display offers IP65 protection from the front and the splash-proof cover - PR type 8335 - can be used against atmospheres and liquids.
  • Page 10: Applications

    coNNEcTIoNS Input signals: + Sup 5...17 V ∼ + Sup + Sup + Input ∼ tacho ∼ Input gnd Special trig Namur Contact Tacho current & voltage (NPN) Output signals: Relay 2 Relay 1 Analogue, 0/4...20 mA Supply: 21.6...253 VAC 19.2...300 VDC 5725V 1 01 - I N...
  • Page 11: Electrical Specifications

    5725 Type Version 5725 Standard....: Analogue output and 2 relays . .: Accessories: 8335 = Splash proof front Electrical specifications Environmental conditions: Specifications range ........
  • Page 12 Input: General: Frequency range, F/I conversion function ..0.001 Hz to 50 kHz Time range, Period time function ....999.9 sec to 20 µsec Response time (0...90%, 100...10%) ... < 1 period + 100 msec Low cut off frequency ......... 0.0009 Hz Low cut off period time .......
  • Page 13 TTL input: Trig-level LOW ..........≤ 0.8 VDC Trig-level HIGH ..........≥ 2.0 VDC Input impedance ......... ≥ 100 kΩ / < 1.5 nF Sensor supply - pin 44, programmable ..5 -17 V / 20 mA S0 input acc. to DIN 43864: Trig-level LOW ..........
  • Page 14 output: current output (5725D): Programmable signal ranges ...... 0...20, 4...20 & 20...0, 20...4 mA Load (max.) ..........20 mA / 800 Ω / 16 VDC Current limit ..........≤ 28 mA Load stability ..........≤ 0.01% of span / 100 Ω Programmable response time .....
  • Page 15: Sensor Error Indication, Inside And Outside Range

    Sensor error indication, inside and outside range Sensor error indication in 5725, only available for NAMUR input: Out of range Relay Analogue Display Condition limit behaviour output value redaout Sensor input > 6.9 mA Set to user Set to user- ”SE.SH”...
  • Page 16: Connections

    coNNEcTIoNS Supply: 31 32 Inputs: Special current Special voltage Tacho 41 42 43 44 41 42 43 44 41 42 43 44 + Sup 5-17V + Sup 5-17V ∼ Contact (NPN) 41 42 43 44 41 42 43 44 41 42 43 44 + Sup 5-17V + Sup 5-17V + Sup...
  • Page 17: Block Diagram

    BLocK DIAGRAm Supply VREG 21.6...253 VAC 5...17 V 19.2...300 VDC Supply Option D Gnd. Output Freq. Common detector Option D Relay 1 N.O. f in Relay 1 N.C. Common EEPROM Relay 2 N.O. Relay 2 N.C. 5725A & D 57 2 5 V 1 0 1 - I N...
  • Page 18: Routing Diagram For 5725A

    RoUTING DIAGRAm FoR 5725A If no key is activated for 2 minutes, the display returns to default state ”Monitor” without saving configuration changes. 1 Increase value / choose next parameter 2 Decrease value / choose previous parameter 3 Accept the chosen parameter and go to the next menu Hold 3 Back to previous menu / return to default state ”Monitor”...
  • Page 19 IN. U N IN. L O IN. H I FILT DEC. P DI. L O DI. H I TXT 38/39 HZ/KHZ HZ/KHZ TXT 48 TXT 49 TXT 50 TXT 51 TXT 40/41 TXT 44/45 -1999 -1999 1111 9999 9999 0. 0 00 0.
  • Page 20: Routing Diagram For 5725D

    RoUTING DIAGRAm FoR 5725D If no key is activated for 2 minutes, the display returns to default state ”Monitor” without saving configuration changes. 1 Increase value / choose next parameter 2 Decrease value / choose previous parameter 3 Accept the chosen parameter and go to the next menu Hold 3 Back to previous menu / return to default state ”Monitor”...
  • Page 21 IN. U N IN. L O IN. H I FILT DEC. P DI. L O DI. H I TXT 38/39 HZ/KHZ HZ/KHZ TXT 48 TXT 49 TXT 50 TXT 51 TXT 40/41 TXT 44/45 -1999 -1999 1111 9999 9999 0. 0 00 0.
  • Page 22: Scrolling Help Texts

    ScRoLLING HELP TExTS TR.Lo (when special voltage input is selected) Top line Scrolling text TEXT NR xxxx SET LOW TRIGGER LEVEL IN VOLT Language menu UK - SELECT ENGLISH HELP TEXT TR.Lo (when special current input is selected) DK - VAELG DANSK HJAELPETEKST xxxx SET LOW TRIGGER LEVEL IN mA DE - WAEHLE DEUTSCHEN HILFETEXT...
  • Page 23 REL.U oF.DE PERC SET RELAY IN PERCENTAGE xxxx RELAY OFF-DELAY IN SECONDS DISP SET RELAY IN DISPLAY UNITS Po.DE REL1 xxxx RELAY POWER ON DELAY IN SECONDS RELAY 1 DISABLED SETP ENTER RELAY 1 SETUP A.oUT SKIP SKIP RELAY 1 SETUP 20-4 OUTPUT RANGE IN mA 20-0...
  • Page 24: Configuration / Operating The Function Keys

    coNFIGURATIoN / oPERATING THE FUNcTIoN KEyS Documentation for the routing diagram In general: When configuring the display you are guided through all parameters, allowing you to choose the settings which fit the application. For each menu there is a scrolling help text which is automatically shown in the display if no key has been activated for appr.
  • Page 25 Password protection: Using a password will block access to the menu and parameters. There are two levels of password protection. Passwords be tween 0000 and 4999 allow access to the fast setpoint adjustment and relay test menus (using this password blocks access to all other parts of the menu). Passwords between 5000 and 9999 block access to all parts of the menu, fast setpoint and relay test (current setpoint is still shown).
  • Page 26: Graphic Depiction Of The Relay Function Setpoint

    Graphic depiction of the relay function setpoint Relay units Relay units Hysteresis = 10 Setpoint = 50 Setpoint = 50 Hysteresis = 10 Off N.O. On N.O. Off N.O. Off N.O. On N.O. Off N.O. On N.C. On N.C. On N.C. On N.C.
  • Page 27 Displays Programmable displays with a wide selection of inputs and outputs for display of temperature, volume and weight, etc. Feature linearisation, scaling, and difference measurement functions for programming via PReset software. Ex interfaces Interfaces for analogue and digital signals as well as HART signals between sensors / I/P converters / ®...
  • Page 28  www.prelectronics.it  sales@prelectronics.it  www.prelectronics.se  sales@prelectronics.se  www.prelectronics.co.uk  sales@prelectronics.co.uk  www.prelectronics.com  sales@prelectronics.com Head office Denmark www.prelectronics.com PR electronics A/S sales@prelectronics.dk Lerbakken 10 tel. +45 86 37 26 77 DK-8410 Rønde fax +45 86 37 30 85...